Evco S.r.l. • File EVC80P16N7DSM00_EVC99T00X0XXX01_(GB)_A4_v1.00.pdf • page 3/6
• time of switchover to storage mode
• ora di un’eventuale interruzione del ciclo di funzionamento
• time of any operational cycle interruption.
Printing of the temperature occurs at operational cycle start, and at
intervals (see parameter P72).
6.4
Printing HACCP alarm information
The module prints the information reported in the table in section 5.2.
To print the information relating to the alarms:
• ensure the device is in "off" mode and no procedures are running
• press
B12
for 5 s: display
DY1
will show "
Prt
"
• press
B12
To exit the procedure:
• press
B12
for 5 s.
7
MESSAGES AND INDICATIONS
7.1
Messages
LED
MEANING
L1
“on”/”stand-by” LED
if on, a chilling or freezing operation is ongoing
if flashing, a storage operation is ongoing
L2
needle probe LED
if on, the temperature measured by the needle probe is
being displayed
if flashing, then the result of the test to verify correct needle
probe insertion was negative; the cycle will be started in
timed mode and the buzzer will emit 5 beeps every 10 s
L3
timed operation cycle LED
if on, a timed operation cycle will have been selected (or
is ongoing
L7
hard chill LED
if on:
• a hard chill operation will have been selected
• the first step of a hard chill operation is ongoing
• modification of the hard chill first step operational setpoint
is underway
if flashing:
• modification of the hard chill second step operational
setpoint is underway
• the second step of a hard chill operation is in progress
L8
normal chilling LED
if on, a normal chill operation has been selected (or is
ongoing
L9
freezing LED
if on, a freezing operation has been selected (or is ongoing)
L10
UV light (cabinet sterilisation) LED
if on, the UV light is on (a cabinet sterilisation operation is
ongoing)
L11
defrosting LED
if on, defrosting is ongoing
L12
program LED
if on, program storing, selection or execution is ongoing
L13
HACCP LED
if on, program storing, selection or execution is ongoing
7.2
Indications
CODE MEANING
dEF
if on, defrosting is ongoing
if flashing, drip-draining is ongoing
8
ALARMS
8.1
Alarms
CODE MEANING
AL
Minimum cabinet temperature alarm
Remedies:
• check the cabinet temperature
• see parameters P64 and P66
Consequences:
• the alarm output will be activated
AH
Maximum cabinet temperature alarm
Remedies:
• check the cabinet temperature
• see parameters P65 and P67
Consequences:
• the alarm output will be activated
Ht
Condenser temperature alarm
Remedies:
• check the condenser temperature
• see parameter P62
Consequences:
• the operational cycle will be interrupted
• it will not be possible to start any operational cycles
• the condenser fan will be switched on
• the alarm output will be activated
d - r
Micro-port input alarm
Remedies:
• check the causes of the input activation
• see parameter P38
Consequences if the alarm occurs while in "on" mode:
• the compressor will be shut down
• if parameter P37 is set to 1, the evaporator fan will be
switched off
• if parameter P59 is set to 0, the cabinet light will be
switched on
• the condenser fan will be switched off
• if the UV light is on (i.e. if cabinet sterilisation is ongoing),
the UV light will be switched off
CODE ALARM TYPE (AND CRITICAL VALUE)
Er0
cabinet probe error (the temperature of the cabinet when
the alarm condition occurred)
Er1
evaporator probe alarm (the maximum cabinet temperature
during the alarm condition)
Er3
needle probe alarm (the maximum cabinet temperature
during the alarm condition)
Er4
condenser probe alarm (the maximum cabinet
temperature during the alarm condition)
AL
(minimum) cabinet temperature alarm (the minimum cabi-
net temperature during the alarm condition)
AH
(maximum) cabinet temperature alarm (the maximum
cabinet temperature during the alarm condition)
Ht
condenser temperature alarm (the maximum cabinet
temperature during the alarm condition)
d - r
micro port input alarm (the maximum cabinet temperature
during the alarm condition)
HP
high pressure input alarm (the maximum cabinet
temperature during the alarm condition)
LP
low pressure input alarm (the maximum cabinet
temperature during the alarm condition)
HA
compressor thermal protection input alarm (the maximum
cabinet temperature during the alarm condition)
PF
power failure alarm (the cabinet temperature on restoration
of power)
5.2
Viewing HACCP alarm information
Viewing HACCP alarm information:
• ensure the device is in "off" mode and no procedures are running
• press
B12
for 5 s: display
DY1
will show "
Prt
".
To select an alarm:
• press
B4
or
B6
display
DY1
will show the number of the alarm
(for example "n03") and display
DY2
will show the
relevant code (for example "
AH
", or one of the codes
reported in the table in section 5.1; the lower the number,
the older the alarm itself).
To display the information relating to the alarm:
• press
B3
repeatedly: the display will show the following information
in sequence (for example):
INFO
MEANING
St
on display
DY1
y07
on display
DY2
The alarm occurred in 2007 (continued ...)
M03
on display
DY1
d26
on display
DY2
The alarm occurred on 26 March 2007
h16
on display
DY1
d30
on display
DY2
The alarm occurred at 4:30pm
t
on display
DY1
8
on display
DY2
The critical value is 8
°
C/8
°
F
dur
on display
DY1
75
on display
DY2
The alarm has lasted for 75 minutes
n03
on display
DY1
AH
on display
DY2
The selected alarm
LED
L13
provides information relating to the status of the HACCP
alarm memory; please refer to section 7.1.
To exit the information series:
• press
B4
or
B6
display
DY1
will show the number of another
alarm and display
DY2
will show the corresponding
code.
To exit the procedure:
• press
B12
for 5 s.
5.3
Deleting the HACCP alarm list
• set parameter P73 to 1.
6
DATA PRINTING
6.1
Introductory information
The device has a serial port for communicating with the PM 100A
X9S001 print module.
6.2
Connecting the PM 100A X9S001 print module
Connecting the PM 100A X9S001 print module:
• ensure that parameter P71 is set to 1
• ensure that the print module baud rate is set to 9,600 baud
• ensure that the module parity is set to odd.
6.3
Printing operational cycle information
Printing operational cycle information:
• operational cycle start date
• operational cycle or program type (or one of the codes listed in the
table below)
CODE MEANING
T>>>*
hard set-temperature chilling and storage
T*
normal set-temperature chilling and storage
T***
set-temperature freezing and storage
t>>>*
hard timed chilling and storage
t*
timed normal chilling and storage
t***
timed freezing and storage
P01...99
program 01 ... 99
• printing time
• cabinet temperature (Pr1)
• temperature measured by the needle probe (Pr2, only if the
operational cycle is a set-temperature cycle)
• the alarm output will be activated
Consequences if the alarm occurs while in "stand-by" mode:
• if parameter P59 is set to 0, the cabinet light will be
switched on
HP
High pressure input alarm
Remedies:
• check the causes of the input activation
• see parameter P40
Consequences:
• the operational cycle will be interrupted
• the loads will be switched off
• it will not be possible to start any operational cycles
• the alarm output will be activated
LP
Low pressure input alarm
Remedies:
• check the causes of the input activation
• see parameter P42
Consequences:
• the operational cycle will be interrupted
• the loads will be switched off
• it will not be possible to start any operational cycles
• the alarm output will be activated
HA
Compressor thermal protection input alarm
Remedies:
• check the causes of the input activation
• see parameter P44
Consequences:
• the operational cycle will be interrupted
• the loads will be switched off
• it will not be possible to start any operational cycles
• the alarm output will be activated
rES
Power failure during an operational cycle
Remedies:
• check the causes of the input activation
Consequences:
• the operational cycle will be restored from the point
where the power failure occurred
When the cause that triggered the alarm has been resolved, the device
restores normal operation.
9
INTERNAL DIAGNOSTICS
9.1
Internal diagnostics
CODE MEANING
Er0
Cabinet probe error
Remedies:
• see parameter P60
• check probe integrity
• check probe-device connection
• check the cabinet temperature
Consequences:
• the operational cycle will be interrupted
• the loads will be switched off
• it will not be possible to start any operational cycles
• the alarm output will be activated
Er1
Evaporator probe error
Remedies:
• the same as for the previous case, but in relation to the
evaporator probe
Consequences:
• defrosting will last for the length of time set by parameter
P24
• the evaporator fan will be switched off during storage
• the alarm output will be activated
Er3
Needle probe error
Remedies:
• the same as for the previous case, but in relation to the
needle probe
Consequences:
• if a set-temperature chilling or freezing operation is
ongoing, the operational cycle will be interrupted
• it will not be possible to start any set-temperature
operational cycles
• the alarm output will be activated
Er4
Condenser probe error
Remedies:
• the same as for the previous case, but in relation to the
condenser probe
Consequences:
• the condenser fan will operate in parallel with the
compressor, except when set by parameter P54
• the alarm output will be activated
Err
User interface-module communication error
Remedies:
• check the user interface-module connection
Consequences:
• if an operational cycle is ongoing, the device will continue
to function normally
• it will not be possible to start any operational cycles
When the cause that triggered the alarm has been resolved, the device
restores normal operation.