EVCO S.p.A. | EVBOX Light JS200 | Instruction sheet ver. 1.0 | Code 104LJS200E103 | Page 3 of 3 | PT 48/17
N.
PAR.
DEF. ENERGY SAVING
MIN... MAX.
98
HE2
0
energy saving maximum duration 0... 999 min
N.
PAR.
DEF. REAL TIME ENERGY SAVING
MIN... MAX.
99
H01
0
energy saving time
0... 23 h
100 H02
0
energy saving maximum duration 0... 24 h
N.
PAR.
DEF. REAL TIME DEFROST (if d8 = 4)
MIN... MAX.
101 Hd1
h-
1st daily defrost time
h- = disabled
102 Hd2
h-
2nd daily defrost time
h- = disabled
103 Hd3
h-
3rd daily defrost time
h- = disabled
104 Hd4
h-
4th daily defrost time
h- = disabled
105 Hd5
h-
5th daily defrost time
h- = disabled
106 Hd6
h-
6th daily defrost time
h- = disabled
N.
PAR.
DEF. RESERVED
MIN... MAX.
107 Sd0
- - -
reserved
reserved
108 Sd1
- - -
reserved
reserved
109 Sd2
- - -
reserved
reserved
110 Sd3
- - -
reserved
reserved
111 Sd4
- - -
reserved
reserved
112 Sd5
- - -
reserved
reserved
N.
PAR.
DEF. SAFETIES
MIN... MAX.
113 POF
1
enable ON/STAND-BY key
0 = no
1 = yes
114
Loc
1
enable keypad lock
0 = no
1 = yes
115 PAS
-19
password
-99... 999
116 PA1
426
level 1 password
-99... 999
117 PA2
824
level 2 password
-99... 999
N.
PAR.
DEF. DATA-LOGGING EVLINK
MIN... MAX.
118
rE0
60
data-logger sampling interval
0... 240 min
119
rE1
4
recorded temperature
0 = none
1 = cabinet
2 = evaporator
3 = auxiliary
4 = cabinet and evaporator
5 = all
N.
PAR.
DEF. MODBUS
MIN... MAX.
120
LA
247
MODBUS address
1... 247
121
Lb
2
MODBUS baud rate
0 = 2,400 baud
1 = 4,800 baud
2 = 9,600 baud
3 = 19,200 baud
122
LP
2
parity
0 = none
1 = odd
2 = even
N.
PAR.
DEF. BLUETOOTH
MIN... MAX.
123
bLE
1
serial
port
configuration
for
connectivity
0 = free
1 = forced for EVconnect or
EPoCA
2-99 = EPoCA local network
address
8
ALARMS
COD.
DESCRIPTION
RESET
TO CORRECT
Pr1
cabinet probe alarm
automatic
- check P0
Pr2
evaporator probe alarm
automatic
- check probe integrity
Pr3
auxiliary probe alarm
automatic
- check electrical connection
rtc
clock alarm
manual
set date, time and day of the week
AL
low temperature alarm
automatic
check A0, A1 and A2
AH
high temperature alarm
automatic
check A4 and A5
id
open door alarm
automatic
check i0 and i1
PF
power failure alarm
manual
- touch a key
- check electrical connection
COH
high condensation warning
automatic
check C6
CSd
high condensation alarm
manual
- switch the device off and on
- check C7
iA
multi-purpose input alarm
automatic
check i5 and i6
iSd
high pressure alarm
manual
- switch the device off and on
- check i5, i6, i8, i9
LP
low pressure alarm
automatic
check i5 and i6
C1t
compressor thermal switch
alarm
automatic
check i5 and i6
C2t
second compressor thermal
switch alarm
automatic
check i5 and i6
dFd
defrost timeout alarm
manual
- touch a key
- check d2, d3 and d11
- - -
user
interface-control
module
communication
alarm
manual
check electrical connection
9
TECHNICAL SPECIFICATIONS
Purpose of the control device
Function controller
Construction of the control device
Built-in electronic device
Container
User interface
White, self-extinguishing
Control module
Open frame board on plastic
support.
Category of heat and fire resistance
D
Measurements
User interface
150.0 x 245.0 x 37.1 mm
(5 15/16 x 9 5/8 x 1 7/16 in)
Control module:
142.0 x 122.0 x 37.0 mm (5
9/16 x 4 13/16 x 1 7/16 in)
Mounting methods for the
control device
User interface
To be fitted on a DIN rail, in a
control panel
Control module
To
be
installed
on
an
electrical switchboard
Degree
of
protection
provided by the covering
User interface
IP65
Control module
IP00
Connection method
Plug-in screw terminal blocks
for wires up to 1 mm²
Fixed screw terminal blocks
for wires up to 2.5 mm²
Fixed screw terminal blocks
for wires up to 5 mm²
Faston, 6.3 mm
Pico-Blade connector
Maximum permitted length for connection cables
User-interface-control module: 10 m (32.8 ft)
Power supply: 10 m (32.8 ft)
Analogue inputs: 10 m (32.8 ft)
Digital inputs: 10 m (32.8 ft)
Digital outputs: 10 m (32.8 ft)
Operating temperature
From 0 to 55 °C (from 32 to 131 °F)
Storage temperature
From -25 to 70 °C (from -13 to 158 °F)
Operating humidity
Relative humidity without condensate from
10 to 90%
Pollution status of the control device
2
Conformity
RoHS 2011/65/CE
WEEE 2012/19/EU
REACH
(EC)
Regulation
1907/2006
EMC 2014/30/UE
LVD 2014/35/UE
Power supply
115... 230 VAC (+10% -15%), 50/60 Hz (±3
Hz), max. 6 VA insulated
Earthing methods for the control device
With earth terminal
Rated impulse-withstand voltage
2.5 KV
Over-voltage category
II
Software class and structure
A
Analogue inputs
2 for PTC or NTC probes (cabinet probe and
evaporator probe)
PTC probes
Sensor type
KTY 81-121 (990
@ 25 °C, 77 °F)
Measurement field
From -50 to 150 °C (from -58 to 302 °F)
Resolution
0.1 °C (1 °F)
NTC probes
Sensor type
ß3435 (10 K
@ 25 °C, 77 °F)
Measurement field
From -40 to 105 °C (from -40 to 221 °F)
Resolution
0.1 °C (1 °F)
Digital inputs
1 dry contact (door switch)
Dry contact
Contact type
5 VDC, 2 mA
Power supply
None
Protection
None
Other inputs
Input configurable for analogue input (auxiliary probe) or
digital input (multi-purpose input)
Digital outputs
5
(4
for
EVLJS224)
with
electro-mechanical
relay
(compressor, defrost, evaporator fan, auxiliary relay 1 and
auxiliary relay 2)
Compressor relay (K2)
SPST, 30 A res. @ 250 VAC
Defrost relay (K4)
SPST, 16 A res. @ 250 VAC
Evaporator fan relay (K5)
SPST, 8 A res. @ 250 VAC
Auxiliary relay 1 (K3)
SPST, 16 A res. @ 250 VAC
Auxiliary relay 2 (K1, not available in
EVLJS224)
SPST, 30 A res. @ 250 VAC
The device guarantees double insulation between each digital output connector and the rest
of the components of the device
Type 1 or Type 2 Actions
Type 1
Additional features of Type 1 or Type 2
actions
C
Displays
LED custom display, 3 digit, with function
icons
Alarm buzzer
Incorporated
Communications ports
1 TTL MODBUS slave port for EVconnect app,
EPoCA remote monitoring system or for BMS
N.B.
The device must be disposed of according to local regulations governing the collection
of electrical and electronic waste.
This document and the solutions contained therein are the intellectual property of EVCO and thus
protected by the Italian Intellectual Property Rights Code (CPI). EVCO imposes an absolute ban on the
full or partial reproduction and disclosure of the content other than with the express approval of EVCO.
The customer (manufacturer, installer or end-user) assumes all responsibility for the configuration of the
device. EVCO accepts no liability for any possible errors in this document and reserves the right to make
any changes, at any time without prejudice to the essential functional and safety features of the