Evco S.p.A. • Code 1049376E00 • page 2/8
3.7
Learning of the quantity shown by the lower part
of the display during the on status
• make sure no procedure is in progress
• press
and
: the lower part of the display will show one of
the labels given in the following table for 2 secs:
LABEL
MEANING
Pbr
chamber temperature
SPr
work set-point of the phase in progress
tinE
count of the duration of the cooking phase in progress
rtc
day and real time
PbC
core temperature
SPC
core set-point
If the core probe is not enabled (parameter P4 = 0), the “
PbC
” and
“
SPC
” labels will not be displayed.
3.8
Chamber light switch-on/off
• make sure no procedure is in progress
• press
The chamber light can be on during the pre-heating phase and during
any cooking phase.
Via the multifunction input it is also possible to cause the same effect
by pressing the
key in remote mode.
If the chamber light is not managed by any digital output, pressing the
key will cause the “
no
” indication to be shown in the lower part
of the display for 1 s.
3.9
Silencing the buzzer
• make sure no procedure is in progress
• press a key (the first time the key is pressed, the associated effect is
not caused).
Pressing the key also causes the acoustic output and the buzzer output
to switch off.
Via the multifunction input it is also possible to switch the buzzer, the
acoustic output and the buzzer output off in remote mode.
4
FUNCTIONING
4.1
Preliminary considerations
The following types of cooking can be managed (successively also
called cooking phases):
• timed
• core
• steam
• grill
• continuous.
If no cooking phase is selected, a continuous cooking phase will be
started on instrument switch-on.
If the parameter r11 is set at 1, every cooking phase is preceded by a
pre-heating phase.
4.2
Pre-heating phase
To start the phase:
• make sure that the instrument is in stand-by status and that no
procedure is in progress
• press
for 1 s:
During the phase:
• the upper part of the display shows the established quantity with
parameter P5 (for predefined setting of the chamber temperature)
• the lower part of the display will show the “
PrEH
” indication
• the work set-point is the “work set-point of the cooking phase
successive to the pre-heating phase + temperature established using
parameter r4” value (successively called work set-point of the pre-
heating phase)
- press
and
for 1 s to pass to the cooking phase.
When the temperature of the chamber reaches the work set-point of
the pre-heating phase, the phase is concluded.
On conclusion of the phase:
- the lower part of the display will show the flashing “
rdY
” indication
- the buzzer and the acoustic output are switched-on for the time
established using parameter c4
- press a key to silence the buzzer and to switch the acoustic output off
- the activity of the output for continuous temperature regulation
depends on the chamber temperature (chamber probe), the work
set-point of the pre-heating phase and the parameter r0
- the fan remains on
- press
for 1 s to pass to the cooking phase.
Via the multifunction input it is also possible to pass from the conclusion
of the pre-heating phase to the next cooking phase in remote mode.
If on start-up of the pre-heating phase, the chamber temperature is
above the work set-point of the pre-heating phase, this will not be
performed.
To modify the work set-point of the pre-heating phase:
• press
during the phase or the conclusion of the phase: the upper
part of the display will show the work set-point of the pre-
heating phase and the
LED will flash
• press
or
within 15 s; see also parameters r1 and r2
• press
or do not operate for 15 s: the
LED will switch-off,
after which the instrument will exit the procedure.
To exit the procedure in advance:
• do not operate for 15 s (any modifications will be saved).
The modification of the work set-point of the pre-heating phase causes
automatic adaptation of the work set-point of the next cooking phase
at the pre-heating phase such to guarantee that the “work set-point of
the next cooking phase at the pre-heating phase + temperature
established using parameter r4” is always the work set-point of the pre-
heating phase.
To interrupt the phase and pass to the next one:
• press
and
for 1 s:
To interrupt the phase:
• press
for 1 s:
4.3
Timed cooking phase
To select the phase:
• make sure that the instrument is in the stand-by status, that no
procedure is in progress and the chamber probe error is not in progress
• press
: the lower part of the display will show flashing “
tinE
”.
To exit the procedure in advance:
• press
do not operate for 15 s.
To start the phase:
• press
for 1 s:
To modify the work set-point:
• press
before starting the phase: the upper part of the display
will show the work set-point and the
LED will flash
• press
or
within 15 s; see also parameters r1 and r2
• press
or do not operate for 15 s: the
LED will switch-off,
after which the instrument will exit the procedure.
To exit the procedure in advance:
• do not operate for 15 s (any modifications will be saved).
It is also possible to set the work set-point of the timed cooking phase
via parameter SP1 (for predefined setting 150
°
C/
°
F).
To modify the duration of the phase:
• press
and
before starting the phase: the lower part of the
display will show phase duration, the left part
and the “
timer
” LED will flash.
The duration of the phase is visualised in the hours:minutes format.
To modify the hour:
• press
or
within 15 s
• press
: the right part will flash.
To modify the minutes:
• press
or
within 15 s.
The duration of the phase can be set between 00:00 and 24:00 h:min.
• press
: the “
timer
” LED will switch-off, after which the instrument
will exit the procedure.
To go back to the previous level:
• press
during the procedure.
To exit the procedure in advance:
• do not operate for 15 s (any modifications will be saved).
It is also possible to set the duration of the timed cooking phase via
parameter d1 (for pre-defined setting 00:30 h:min).
The work set-point and the duration of the phase can also be modified
when the phase is in progress (these modifications are temporary, i.e.,
on the contrary to any power supply cut-off, the selection of a different
type of cooking phase causes the reset of the same values set, however
with the procedure indicated in paragraph 5.3).
If the duration of the phase is set at 00:00 h:min, the count will be
interrupted, the “
timer
” LED will switch-off, the buzzer and the acoustic
output will be on for 3 s.
During the phase:
• the upper part of the display shows the established quantity with
parameter P5 (for predefined setting of the chamber temperature)
• the lower part of the display shows the quantity established using
parameter P6 (for predefined setting of the count of the phase
duration; the count is displayed in the hours:minutes format (residual
time))
• press
and
to display the indication relative to the cooking
phase in progress for 2 sec in the lower part of
the display (“
tinE
”).
When the count of the duration of the phase is completed, the phase
is concluded.
Before the conclusion of the phase (of the time established with
parameter c9):
- the buzzer and the acoustic output are switched-on for the time
established using parameter c4.
On conclusion of the phase:
- the lower part of the display will show the flashing “
End
” indication
- press a key to silence the buzzer and to switch the acoustic output
off; press it again to delete the “
End
” indication
- the temperature regulation output is switched-off
- the fan is switched-off.
To interrupt the phase:
• press
for 1 s:
To memorise the phase and its settings in a program:
• make sure the phase has ended
• press
and
for 4 s: the lower part of the display will show
“
PrOG
” and a flashing label relative to the first
program
• repeat the procedure stated in paragraph 11.2.
The instrument memorises the phase and its settings on condition that
another phase is not selected on conclusion of the phase.
4.4
Core cooking phase
To select the phase:
• make sure that the instrument is in the stand-by status, that no
procedure is in progress and the chamber probe error is not in progress
• press
: the lower part of the display will show flashing “
tinE
”
• press
or
within 15 s to select “
COrE
”.
To exit the procedure in advance:
• press
do not operate for 15 s.
To start the phase:
• press
for 1 s:
If the core probe is not enabled (parameter P4 = 0) or if a core probe
error is in progress, the “
COrE
” label will not be displayed.
To modify the work set-point:
• press
before starting the phase: the upper part of the display will
show the work set-point, the
LEDs and “
1
” will flash
• press
or
within 15 s; see also parameters r1 and r2
- if P5 = 2, the display will show the core temperature
- if P5 = 3, the display will show the core set-point
• the lower part of the display will show the quantity established with
parameter P6:
- if P6 = 0, the display will show the chamber temperature
- if P6 = 1, the display will show the work set-point of the phase in
progress (in this case the “
set
” LED and the “
1
” LED will be on)
- if P6 = 2, the display the count of the duration of the cooking phase
in progress (in this case the “
timer
” LED will be on). The count is
displayed in the hours:minutes format (residual time)
- if P6 = 3, the display shows the day and the real time (in this case the
“
clock
” LED will be on). The day will be displayed in the 1 ... 7
format (number 1 corresponds to Monday), the real time in the 24 h
format
- if P6 = 4, the display will show the core temperature
- if P6 = 5, the display will show the core set-point (in this case the
“
set
” LED and the “
2
” LED will be on)
- if P6 = 6, the display will show the significant quantity for the event in
progress:
- “
PrEH
” during the pre-heating phase
- “
rdY
” flashing on conclusion of the pre-heating phase
- “
End
” flashing on conclusion of the cooking phase
- “
EndP
” flashing on conclusion of the program
- “
PAUS
” flashes during the suspension of the cooking phase
- count of the duration of the cooking phase, during the timed
cooking phase, during the steam cooking phase and during the
grill cooking phase
- core temperature during the core cooking phase
- “
- - - -
” during the continuous cooking phase.
If parameter P6 is set at values different to 6, these will have no effect
in the following conditions:
• during the pre-heating phase (the lower part of the display will
show “
PrEH
”)
• on the conclusion of the pre-heating phase, in stand-by for start-up of
the cooking phase (the lower part of the display shows flashing “
rdY
”)
• during the pre-heating phase (the lower part of the display will show
flashing “
PAUS
”)
• on conclusion of the cooking phase (the lower part of the display will
show flashing “
End
”)
• on conclusion of the program (the lower part of the display will show
flashing “
EndP
”)
• during the core cooking phase (if P6 = 2) and during the continuous
cooking phase (the lower part of the display will show “
- - - -
”).
See also paragraphs 3.5 and 3.7.
If the instrument is in the programmed switch-on status:
• the upper part of the display will show the program label which will
be started on programmed switch-on of the instrument (if the start-
up of any program is not envisioned, the upper part of the display
will show “
P -
”)
• the lower part of the display will show the day of the time of the next
switch-on; the day is visualised in 1 ... 7 format (number 1 corresponds
to Monday), the real time in the 24 h format (if no switch-on is
programmed, the lower part of the display will show “
- - : - -
”)
• the “
delay
” LED will be on
• the LED will be on.
If the instrument is in the stand-by status:
• the upper part of the display will be off
• the lower part of the display:
- will be off if parameter c8 is set at 0
- it will display the real time if parameter c8 is set at 1 (in this case the
“
clock
” LED will be on); the real time is displayed in the
24 h format
• the LED will be on.
3.4
Temporary setting of the quantity shown by the
upper part of the display during the on status
• make sure no procedure is in progress
• press
and
for 1 s several times: the highest display will show
one of the labels stated in the table in
paragraph 3.5 for 2 s, after which it will show
the corresponding value.
A power cut causes the restore of the display of the quantity established
with parameter P5.
3.5
Learning of the quantity shown by the upper
part of the display during the on status
• make sure no procedure is in progress
• press
and
: the upper part of the display will show one of
the labels given in the following table for 2 secs:
LABEL
MEANING
Pbr
chamber temperature
SPr
work set-point of the phase in progress
PbC
core temperature
SPC
core set-point
If the core probe is not enabled (parameter P4 = 0), the “
PbC
” and
“
SPC
” labels will not be displayed.
3.6
Temporary setting of the quantity shown by the
lower part of the display during the on status
• make sure no procedure is in progress
• press
and
for 1 s several times: the lowest display will show
one of the labels stated in the table in
paragraph 3.7 for 2 s, after which it will show
the corresponding value.
A power cut causes the restore of the display of the quantity established
with parameter P6.