Evco EV8318 Quick Start Manual Download Page 3

EVCO S.p.A. | EV8318 | Instr

 

uction sheet ver. 2.0 | Code 1048318E203 | Page 3 of 4 | PT 47/18 

SETTINGS 

8.1 Setting configuration parameters 

 

 

N.B. 

Changing parameter P2 causes the value of the parameters whose unit of measure-

ment is °C or °F to be changed automatically. 

 

Make sure that the device is switched off. 

1. 

 

Touch  the INTERACTIVE 4  key:  the  display  will  show  the “Con-

figuration” menu. 

2. 

 

Touch the INTERACTIVE 1 key or the INTERACTIVE 2 key to se-

lect “Service”

3. 

 

Touch the INTERACTIVE 3 key: the display will show “Password” 

in yellow. 

4. 

 

Touch the INTERACTIVE 1 key or the INTERACTIVE 2 key within 

15 s to set “-19”. 

5. 

 

Touch  the  INTERACTIVE 3  key:  the  display  will  show  the  “Ser-

vice” menu. 

6. 

 

Touch the INTERACTIVE 1 key or the INTERACTIVE 2 key to se-

lect a parameter. 

7. 

 

Touch the INTERACTIVE 3 key: the display will show the parame-

ter in yellow. 

8. 

 

Touch the INTERACTIVE 1 key or the INTERACTIVE 2 key within 

15 s to set the value. 

9. 

 

Touch the INTERACTIVE 3 key (or take no action for 15 s). 

10. 

 

Touch the INTERACTIVE 4 key to exit the procedure (or take no 

action for 60 s). 

 

8.2 

Setting the time and day of the week 

 

 

N.B. 

Do not disconnect the device from the mains in the two minutes after setting the time 

and day of the week. 

 

Make sure that the device is switched off. 

1. 

 

Touch  the INTERACTIVE 4  key:  the  display  will  show  the “Con-

figuration” menu. 

2. 

 

Touch the INTERACTIVE 1 key or the INTERACTIVE 2 key to se-

lect “Clock”

3. 

 

Touch the INTERACTIVE 3 key. 

4. 

 

Touch the INTERACTIVE 1 key or the INTERACTIVE 2 key to se-

lect “Time”

5. 

 

Touch the INTERACTIVE 3 key: the display will show the time in 

yellow. 

6. 

 

Touch the INTERACTIVE 1 key or the INTERACTIVE 2 key within 

15 s to set the value. 

7. 

 

Touch the INTERACTIVE 3 key: the display will show the minutes 

in yellow. 

8. 

 

Touch the INTERACTIVE 1 key or the INTERACTIVE 2 key within 

15 s to set the value. 

9. 

 

Touch the INTERACTIVE 3 key (or take no action for 15 s). 

10. 

 

Touch the INTERACTIVE 1 key or the INTERACTIVE 2 key to se-

lect “Day”

11. 

 

Touch  the INTERACTIVE 3 key:  the  display  will  show  the  day  in 

yellow. 

12. 

 

Touch the INTERACTIVE 1 key or the INTERACTIVE 2 key within 

15 s to set the value. 

13. 

 

Touch the INTERACTIVE 3 key (or take no action for 15 s). 

14. 

 

Touch the INTERACTIVE 4 key to exit the procedure (or take no 

action for 60 s). 

 

8.3 

Restoring factory settings (default) 

 

 

N.B. 

Check that the factory settings are appropriate; see the section CONFIGURATION PA-

RAMETERS

 

Make sure that the device is switched off. 

1. 

 

Touch  the INTERACTIVE 4  key:  the  display  will  show  the “Con-

figuration” menu. 

2. 

 

Touch the INTERACTIVE 1 key or the INTERACTIVE 2 key to se-

lect “Service”

3. 

 

Touch the INTERACTIVE 3 key: the display will show “Password” 

in yellow. 

4. 

 

Touch the INTERACTIVE 1 key or the INTERACTIVE 2 key within 

15 s to set “149”. 

5. 

 

Touch  the  INTERACTIVE  3  key:  the  display  will  show  the  “Ser-

vice” menu. 

6. 

 

Touch the INTERACTIVE 1 key or the INTERACTIVE 2 key to se-

lect “Restore default”. 

7. 

 

Touch  the  INTERACTIVE  3  key  for  3  s:  the  display  will  show  a 

tick. 

8. 

 

Touch the INTERACTIVE 4 key to exit the procedure beforehand 

(the reset will not be carried out). 

 

CONFIGURATION PARAMETERS 

 

 

NO.  PAR. 

DEF.  ANALOGUE INPUTS 

MIN... MAX.

 

 

P0 

 

 

type of probe 

 

0  = J 

1  = K 

2  = Pt 100 2-wire 

P1 

unit of measurement 

0  = °C 

1  = °F 

 

 

 

 

 

P2 

 

 

 

 

 

 

 

 

 

 

operating logic 

 

 

 

 

 

0  = independent  regulation 

of  the  top  and  floor 

power 

1   = independent  regulation 

of  the  top  and  floor 

temperature 

 

 

 

 

 

 

 

 

 

 

 

 

P3 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

type of steam injection 

 

 

 

 

 

 

 

 

 

 

 

 

0  = disabled 

1  = manual  and  automatic 

(with  t8,  t9  and  t10)  if 

generator is on 

2  = manual  and  automatic 

(with  t8,  t9  and  t10), 

with  digital  input  active 

and if generator is on 

3  = manual  and  automatic 

(with  t8,  t9  and  t10), 

thermoregulated 

(with 

t1,  t2  and  t3)  and  if 

generator is on 

 

CA1 

 

 

chamber probe offset 

 

-25... 25 °C/°F 

if P2 = 1, top probe offset 

CA2 

floor probe offset 

-25... 25 °C/°F 

CA3 

steam probe offset 

-25... 25 °C/°F 

 

NO.  PAR. 

DEF.  REGULATION 

MIN... MAX. 

 

 

 

r0 

 

 

 

 

 

 

setpoint chamber differential 

 

 

 

1... 99 °C/°F 

if  P2  =  1,  top  setpoint  and 

floor setpoint differential 

effective if r10 = 0 

 

 

r1 

 

 

 

 

minimum chamber setpoint  

 

 

0 °C/°F... r2 

if  P2  =  1,  minimum  top  set-

point  

10 

 

 

r2 

 

 

300 

 

 

maximum chamber setpoint  

 

 

r1... 999 °C/°F 

if  P2  = 1,  maximum  top  set-

point  

11 

 

r3 

 

130 

 

chamber setpoint  

 

r1... r2 

if P2 = 1, top setpoint 

12 

r4 

minimum floor setpoint  

0 °C/°F... r5 

13 

r5 

300 

maximum floor setpoint  

r4... 999 °C/°F 

14 

r6 

130 

floor setpoint 

r4... r5 

15 

 

 

 

 

 

r7 

 

 

 

 

 

 

 

 

 

 

constraint between top and floor 

powers 

 

 

 

 

0  = disabled 

1  = changing 

power 

causes  the  other  to  be 

changed 

automatically 

so  that  the  sum  of  the 

two is always 100 

16 

 

 

 

 

 

r8 

 

 

 

 

 

80 

 

 

 

 

 

cycle  time  for  top  and  floor 

heaters on 

 

 

 

 

1... 999 s 

if  P2  =  1,  cycle  time  for  top 

and  floors  heaters  on  in  en-

ergy saving mode 

if  P2  =  1  and  r10  > 0,  cycle 

time PI 

17 

 

r9 

 

 

minimum  time  top  and  floor 

heaters on and off 

0... 240 s 

we recommend > 10 s 

18 

 

 

r10 

 

 

50 

 

 

proportional band 

 

 

0... 99 °C/°F 

0  = on-off control 

effective only if P2 = 1 

19 

 

 

r11 

 

 

80 

 

 

integral action time 

 

 

0... 999 s 

0  = P control 

effective only if P2 = 1 

 

NO.  PAR. 

DEF.  GENERAL SETTINGS 

MIN... MAX. 

20 

 

c0 

 

15 

 

time  buzzer  on  from  end  of 

cooking cycle 

-1... 120 s 

-1 = until silencing 

21 

 

c1 

 

 

activate buzzer for 1 s at end of 

the cooking phase 

0  = no 

1  = yes 

 

22 

 

 

 

c2 

 

 

 

60 

 

 

 

keyboard 

inactivity 

time 

to 

switch  off  the  device  from 

weekly  programmed  switch-on 

activation 

0... 240 min 

0  = disabled 

 

 

23 

 

 

c3 

 

 

10 

 

 

high 

chamber 

temperature 

threshold  for  locked  display 

(relative to chamber setpoint) 

0... 99 °C/°F 

chamber se c3 

0  = disabled 

24 

 

 

c4 

 

 

10 

 

 

low 

chamber 

temperature 

threshold  for  locked  display 

(relative to chamber setpoint) 

0... 99 °C/°F 

chamber setpoint - c4 

0  = disabled 

25 

 

c5 

 

 

enable 

weekly 

programmed 

switch-on 

0  = no 

1  = yes 

 

26 

 

c6 

 

 

activate overheating at power-on 

 

0  = no 

1  = yes 

effective only if P2 = 0 

27 

 

 

 

c7 

 

 

 

150 

 

 

 

chamber  temperature  threshold 

for end of overheating 

 

 

0... 999 °C/°F 

0  = on  reaching  the  working 

setpoint  

effective only if P2 = 0 

28 

 

 

 

 

c8 

 

 

 

 

60 

 

 

 

 

maximum  duration  of  energy 

saving  

 

 

 

0... 240 min 

0  = until  manual  deactiva-

tion 

not  effective  if  activated  by 

digital input 

29 

 

 

c9 

 

 

50 

 

 

percentage  reduction  time  top 

and  floor  heaters  on  in  energy 

saving mode 

0... 100 % 

effective only if P2 = 0 

 

30 

c10 

10 

duration of controller cleaning 

1... 120 s 

 

NO.  PAR. 

DEF.  STEAM INJECTION 

MIN... MAX. 

31 

t1 

100 

steam setpoint 

0... 500 °C/°F 

32 

t2 

steam setpoint differential 

1... 99 °C/°F 

33 

 

 

 

t3 

 

 

 

50 

 

 

 

steam temperature threshold for 

injection  stoppage  (relative  to 

steam setpoint) 

 

0... 999 °C/°F 

steam setpoint - t3 

injection  available  on  reach-

ing steam setpoint  

34 

 

 

t4 

 

 

 

 

activate  automatic  steam  injec-

tion cycles at start-up of cooking 

cycle 

0  = no 

1  = yes 

 

 

35 

 

 

t5 

 

 

 

 

deactivate  automatic  steam  in-

jection  cycles  at  end  of  cooking 

cycle 

0  = no 

1  = yes 

 

 

36 

t6 

steam generator on at power-on 

0  = no 

1  = yes 

37 

 

 

 

 

 

 

 

 

t7 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

value available with quick setting 

of  automatic  steam  injection  cy-

cles 

 

 

 

 

 

 

0  = injection time on 

1  = injection time on and in-

jection time off 

2  = injection  time  on,  injec-

tion  time  off  and  num-

ber of automatic cycles 

3  = injection  time  on  and 

number of automatic cy-

cles 

38 

 

t8 

 

 

steam  injection  default  time  on 

with quick setting 

1... 99 s 

 

39 

 

 

t9 

 

 

10 

 

 

steam  injection  default  time  off 

with quick setting 

 

1... 999 s 

if  t7  =  1  or  2,  injection  time 

off 

40 

 

 

 

 

t10 

 

 

 

 

 

 

 

 

number  of  automatic  steam  in-

jection cycles default 

 

 

 

-1... 20 

-1 = until 

generator 

is 

switched off 

if  t7  =  0  or  1,  number  of 

automatic cycles 

 

NO.  PAR. 

DEF.  ALARMS 

MIN... MAX. 

41 

 

A0 

 

10 

 

temperature alarm switch off dif-

ferential 

1... 99 °C/°F 

 

42 

A1 

high  temperature  alarm  thresh-

old 

0... 500 °C/°F 

43 

 

 

A2 

 

 

 

 

high  temperature  alarm  delay 

and  delay  after  modifying  set-

point 

0... 240 min 

 

 

44 

 

 

A3 

 

 

 

 

high temperature alarm type 

 

 

0  = disabled 

1  = absolute 

2  = relative to setpoint 

45 

 

A4 

 

70 

 

high 

operating 

temperature 

alarm threshold 

0... 88 °C/175 °F 

0  = disabled 

46 

 

A5 

 

240 

 

power failure duration due to in-

terruption of cooking cycle 

0... 240 min 

0  = disabled 

 

NO.  PAR. 

DEF.  DIGITAL INPUTS 

MIN... MAX. 

47 

 

i0 

 

 

activation multi-purpose input 1 

  

0 = with contact closed 

1 = with contact open 

48 

 

 

 

 

 

 

 

 

 

 

 

 

 

i1 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

multi-purpose input 1 function  

(option 

effective 

only 

if 

P3 = 2) 

 

 

 

 

 

 

 

 

 

 

 

0  = disabled 

1  = suction  hood  on  (door 

open alarm) 

2  = steam  injection  off,  top 

and  floor  heaters  off, 

suction  hood  on  (door 

open alarm) 

3  = switches device on/off 

4  = steam generator off, top 

and  floor  heaters  off 

(thermal switch alarm) 

5  = energy  saving  activa-

tion/deactivation 

6  = enable steam injection 

49 

 

 

i2 

 

 

 

 

door  open  alarm  delay  and 

thermal switch alarm delay from 

multi-purpose input 1 

0... 120 s 

 

 

50 

 

i3 

 

 

multi-purpose input 2 activation 

 

0 = with contact closed 

1 = with contact open 

51 

 

 

 

 

 

 

 

 

 

 

 

 

 

i4 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

multi-purpose input 2 function  

(option 

effective 

only 

if 

P3 = 2) 

 

 

 

 

 

 

 

 

 

 

 

0  = disabled 

1  = suction  hood  on  (door 

open alarm) 

2  = steam  injection  off,  top 

and  floor  heaters  off, 

suction  hood  on  (door 

open alarm) 

3  = switches device on/off 

4  = steam generator off, top 

and  floor  heaters  off 

(thermal switch alarm) 

5  = energy  saving  activa-

tion/deactivation 

6  = enable steam injection 

52 

 
 

i5 

 

 

 

 

door  open  alarm  delay  and 

thermal switch alarm delay from 

multi-purpose input 2  

0... 120 s 

 

 

 

NO.  PAR. 

DEF.  DIGITAL OUTPUTS 

MIN... MAX. 

53 

 

u0 

 

 

opening vent 

 

0 = with contact closed 

1 = with contact open 

54 

 

 

u1 

 

 

10 

 

 

time  vent  open  from  end  of 

cooking cycle 

 

0... 600 s 

-1 = open  until  closed  by 

pressing key 

55 

 

u2 

 

10 

 

time suction hood on 

 

0... 999 s 

0  = switching on/off by key 

56 

 

 

 

u6 

 

 

 

60 

 

 

 

operating  temperature  threshold 

when  electronics  compartment 

fans on and device off 

 

20... 65 °C/65... 150 °F 

fans always on with device on 

and  device  sensor  in  alarm 

mode 

57 

u7 

10 

u6 differential 

1... 99 °C/°F 

58 

 

 

u8 

 

 

 

 

activate  chamber  light  flashing 

for  10  s  at  end  of  the  cooking 

cycle 

0  = no 

1  = yes 

 

 

59 

 

 

 

 

 

 

 

 

 

 

 

u1c 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

K1 output configuration 

 

 

 

 

 

 

 

 

 

 

 

0  = disabled 

1  = top heaters 

2  = floor heaters 

3  = chamber light 

4  = steam generator 

5  = steam injection 

6  = venting 

7  = suction hood 

8  = electronics compartment 

fans 

9  = on/stand-by 

10 = sound 

60 

 

 

 

 

 

 

 

 

 

 

 

u2c 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

K2 output configuration 

 

 

 

 

 

 

 

 

 

 

 

0  = disabled 

1  = top heaters 

2  = floor heaters 

3  = chamber light 

4  = steam generator 

5  = steam injection 

6  = venting 

7  = suction hood 

8  = electronics compartment 

fans 

9  = on/stand-by 

10 = sound 

61 

 

 

 

 

 

 

 

 

 

 

 

u3c 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

K3 output configuration 

 

 

 

 

 

 

 

 

 

 

 

0  = disabled 

1  = top heaters 

2  = floor heaters 

3  = chamber light 

4  = steam generator 

5  = steam injection 

6  = venting 

7  = suction hood 

8  = electronics compartment 

fans 

9  = on/stand-by 

10 = sound 

62 

 

 

 

 

 

 

 

 

 

 

 

u4c 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

K4 output configuration 

 

 

 

 

 

 

 

 

 

 

 

0  = disabled 

1  = top heaters 

2  = floor heaters 

3  = chamber light 

4  = steam generator 

5  = steam injection 

6  = venting 

7  = suction hood 

8  = electronics compartment 

fans 

9  = on/stand-by 

10 = sound 

63 

 

 

 

 

 

 

 

 

 

 

 

u5c 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

K5 output configuration 

 

 

 

 

 

 

 

 

 

 

 

0  = disabled 

1  = top heaters 

2  = floor heaters 

3  = chamber light 

4  = steam generator 

5  = steam injection 

6  = venting 

7  = suction hood 

8  = electronics compartment 

fans 

9  = on/stand-by 

10 = sound 

64 

 

 

 

 

 

 

 

 

 

 

 

u6c 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

K6 output configuration 

 

 

 

 

 

 

 

 

 

 

 

0  = disabled 

1  = top heaters 

2  = floor heaters 

3  = chamber light 

4  = steam generator 

5  = steam injection 

6  = venting 

7  = suction hood 

8  = electronics compartment 

fans 

9  = on/stand-by 

10 = sound 

65 

 

 

 

 

 

 

 

 

 

 

 

u7c 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

K7 output configuration 

 

 

 

 

 

 

 

 

 

 

 

0  = disabled 

1  = top heaters 

2  = floor heaters 

3  = chamber light 

4  = steam generator 

5  = steam injection 

6  = venting 

7  = suction hood 

8  = electronics compartment 

fans 

9  = on/stand-by 

10 = sound 

66 

 

 

 

 

 

 

 

 

 

 

 

u8c 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

K8 output configuration 

 

 

 

 

 

 

 

 

 

 

 

0  = disabled 

1  = top heaters 

2  = floor heaters 

3  = chamber light 

4  = steam generator 

5  = steam injection 

6  = venting 

7  = suction hood 

8  = electronics compartment 

fans 

9  = on/stand-by 

10 = sound 

 

NO.  PAR. 

DEF.  SECURITY 

MIN... MAX. 

67 

PA1 

426 

first level password 

-99... 999 

68 

PA2 

824 

second level password  

-99... 999 

 

NO.  PAR. 

DEF.  MODBUS 

MIN... MAX. 

69 

LA 

247 

MODBUS address 

1... 247 

Summary of Contents for EV8318

Page 1: ...following the instructions given in the section MEASUREMENTS AND INSTALLATION 2 Power up the device as set out in the section ELECTRICAL CONNECTION an internal test will start up The test normally takes a few seconds when it is finished the display will switch off 3 Configure the device as shown in the section Setting configuration parameters Recommended configuration parameters for first time use...

Page 2: ...he ENERGY SAVING key for 3 s the display will show the value in yellow 2 Touch the INTERACTIVE 1 key or the INTERACTIVE 2 key within 15 s to set the value 3 Touch the INTERACTIVE 3 key or take no action for 15 s If the operating logic has independent regulation of the top and floor temperature P2 1 when the energy saving function is active the switch on time of the top and floor heaters is calcula...

Page 3: ...grammed switch on 0 no 1 yes 26 c6 0 activate overheating at power on 0 no 1 yes effective only if P2 0 27 c7 150 chamber temperature threshold for end of overheating 0 999 C F 0 on reaching the working setpoint effective only if P2 0 28 c8 60 maximum duration of energy saving 0 240 min 0 until manual deactiva tion not effective if activated by digital input 29 c9 50 percentage reduction time top ...

Page 4: ...ulse withstand voltage 2 5 KV Over voltage category II Software class and structure A Clock built in secondary lithium battery Clock drift 60 s month at 25 C 77 F Clock battery autonomy in the absence of a power supply 24 h at 25 C 77 F Clock battery charging time 24 h the battery is charged by the power supply of the device Analogue inputs 2 for J K thermocouples or Pt 100 2 wire probes chamber p...