uction sheet ver. 2.0 | Code 1048318E203 | Page 1 of 4 | PT 47/18 

EV8318 

Controller for bread and pizza deck ovens  

 

 

 

 

ENGLISH 

power supply 115... 230 VAC or 24 VAC (according to the model) 

built-in clock 

chamber probe or top and floor probes (J/K or Pt 100 2-wire) 

multi-purpose input 

steam generator relay, 16 A res. @ 250 VAC 

alarm buzzer 

TTL MODBUS slave port for programming key or for TTL/RS-485 (BMS) serial interface 

USB port (set up recipe book) 

on-off/PI control 

independent regulation of the power or the top and floor temperature. 

 

Models available 

Purchasing  

code 

 

Power supply 

 

 

Type of 

analogue inputs 

 

Number of 

digital outputs 

 

Type of digital 

outputs for  

top and floor 

EV8318J9 

 

 

 

115... 230 VAC 

 

 

 

for J/K thermo-

couples or  

Pt 100 2-wire 

probes 

 

 

electro-

mechanical 

relay 

 

EV8318J4 

 

 

 

24 VAC 

 

 

 

for Pt 100 2-wire 

probes and  

J/K thermocou-

ples 

 

 

electro-

mechanical 

relay 

 

 

MEASUREMENTS AND INSTALLATION 

Measurements in mm (inches). To be fitted to a panel, screwed-in brackets provided. 

 

 

 

INSTALLATION PRECAUTIONS 

the thickness of the panel must be between 0.8 and 5.0 mm (1/32 and 1/16 in) 

the maximum clamping torque applicable to the screwed-in brackets is 10 cNm 

ensure  that  the  working  conditions  are  within  the  limits  stated  in  the  TECHNICAL 

SPECIFICATIONS section 

do not install the device close to heat sources, equipment with a strong magnetic field, 

in places subject to direct sunlight, rain, damp, excessive dust, mechanical vibrations 

or shocks 

in compliance with safety regulations, the device must be installed properly to ensure 

adequate  protection  from  contact  with  electrical  parts.  All  protective  parts  must  be 

fixed in such a way as to need the aid of a tool to remove them. 

 

 

 

 

 

 

 

 

 

 

ELECTRICAL CONNECTION 

 

 

N.B. 

-  use cables of an adequate section for the current running through them 

-  ensure that the thermocouple is properly insulated from contact with metal parts or 

use already insulated thermocouples 

-  if necessary, extend the thermocouple cables using compensating cables 

-  where  they  are  two  multi-purpose  inputs,  multi-purpose  input  1 has  priority  over 

multi-purpose input 2 

-   the TTL MODBUS port can be used as an alternative to the USB port and vice versa 

-  to reduce any electromagnetic interference locate the power cables as far away as 

possible from the signal cables. 

 

 

 

PRECAUTIONS FOR ELECTRICAL CONNECTION 

if using an electrical or pneumatic screwdriver, adjust the tightening torque 

if the device is moved from a cold to a warm place, humidity may cause condensation 

to form inside. Wait for about an hour before switching on the power 

make  sure  that  the  supply  voltage, electrical  frequency  and  power are  within  the  set 

limits. See the section TECHNICAL SPECIFICATIONS 

disconnect the power supply before carrying out any type of maintenance 

do not use the device as a safety device 

for repairs and for further information, contact the EVCO sales network. 

 

FIRST-TIME USE 

1. 

Carry out the installation following the instructions given in the section MEASUREMENTS 

AND INSTALLATION

2. 

Power  up  the  device  as  set  out  in  the  section  ELECTRICAL  CONNECTION:  an  internal 

test will start up. 

 

The test normally takes a few seconds; when it is finished the display will switch off. 

3. 

Configure the device as shown in the section Setting configuration parameters

 

 

Recommended configuration parameters for first-time use: 

PAR. 

DEF. 

PARAMETER 

MIN... MAX. 

P0 

 

 

type of probe 

 

0  = J 

1  = K 

2  = Pt 100 2-wire 

P1 

unit of measurement 

0  = °C 

1  = °F 

P2 

 

 

 

 

 

 

operating logic 

 

 

 

0  = independent  regulation  of  the 

top and floor power 

1  = independent  regulation  of  the 

top and floor temperature 

r3 

 

130 

 

chamber setpoint 

 

r1... r2 

if P2 = 1, top setpoint  

r6 

130 

floor setpoint 

r4... r5 

 

 

Then  check  that  the  remaining  settings  are  appropriate;  see  the  section  CONFIGURA-

TION PARAMETERS

4. 

Disconnect the device from the mains. 

5. 

Make the electrical connection as shown in the section ELECTRICAL CONNECTION with-

out powering up the device. 

6. 

When connecting to an RS-485 network, connect the EVIF22TSX interface.  

7. 

Power up the device. 

 

 

 

 

 

 

 

 

 

 

 

USER INTERFACE AND MAIN FUNCTIONS 

 

 

 

4.1 

Switching the device on/off 

To switch the device on: 

1. 

 

Touch the ON/STAND-BY key. 

 

To switch the device off: 

1. 

 

Touch the ON/STAND-BY key for 3 s. 

 

If  the  device  is  on  and  the  operating  logic  has  independent  regulation  of  the  top  and  floor 

power (P2 = 0, default), the display will show: 

 

 

 

If the chamber setpoint has been reached, the status of the device will show “READY", if not, it 

will show "PRE-HEATING".  

 

If the device is on and the operating logic has independent regulation of the top and floor tem-

perature (P2 = 1), the display will show: 

 

 

 

If the top and floor setpoints have been reached, the status of the device will show "READY", if 

not, it will show "PRE-HEATING". 

 

If the device is switched off, the display will show the time. If the weekly programmed switch-

on function is activated, the display will also show the day and time of the next switch-on and 

the programme that will start. 

If the status of the device shows an alarm code, see the section ALARMS

 

4.2 

Starting up/interrupting the cooking cycle 

To start up a cooking cycle: 

-  

make sure that the device is switched on 

make sure that the cooking timer is set  

1. 

 

Touch  the START/STOP  key:  the  cooking  timer  will  start up  and 

the  status  of  the  device  will  show "COOKING".  When  the  timer 

stops, it will show "END". 

 

To interrupt the cooking cycle: 

1. 

 

Touch the START/STOP key for 1 s. 

 

4.3 

Setting the cooking timer  

Make sure that the device is switched on. 

1. 

 

Touch the INTERACTIVE 4 key: the display will show the minutes 

in yellow. 

2. 

 

Touch the INTERACTIVE 1 key or the INTERACTIVE 2 key within 

15 s to set the value. 

3. 

 

Touch the INTERACTIVE 3 key: the display will show the seconds 

in yellow. 

4. 

 

Touch the INTERACTIVE 1 key or the INTERACTIVE 2 key within 

15 s to set the value. 

5. 

 

Touch the INTERACTIVE 3 key (or take no action for 15 s). 

6. 

 

Touch the INTERACTIVE 4 key to exit the procedure beforehand 

(any changes made will not be saved). 

 

4.4.1  Setting the chamber setpoint (if P2 = 0) 

Make sure that the device is switched on. 

1. 

 

Touch the INTERACTIVE 2 key: the display will show the value in 

yellow. 

Summary of Contents for EV8318

Page 1: ...following the instructions given in the section MEASUREMENTS AND INSTALLATION 2 Power up the device as set out in the section ELECTRICAL CONNECTION an internal test will start up The test normally takes a few seconds when it is finished the display will switch off 3 Configure the device as shown in the section Setting configuration parameters Recommended configuration parameters for first time use...

Page 2: ...he ENERGY SAVING key for 3 s the display will show the value in yellow 2 Touch the INTERACTIVE 1 key or the INTERACTIVE 2 key within 15 s to set the value 3 Touch the INTERACTIVE 3 key or take no action for 15 s If the operating logic has independent regulation of the top and floor temperature P2 1 when the energy saving function is active the switch on time of the top and floor heaters is calcula...

Page 3: ...grammed switch on 0 no 1 yes 26 c6 0 activate overheating at power on 0 no 1 yes effective only if P2 0 27 c7 150 chamber temperature threshold for end of overheating 0 999 C F 0 on reaching the working setpoint effective only if P2 0 28 c8 60 maximum duration of energy saving 0 240 min 0 until manual deactiva tion not effective if activated by digital input 29 c9 50 percentage reduction time top ...

Page 4: ...ulse withstand voltage 2 5 KV Over voltage category II Software class and structure A Clock built in secondary lithium battery Clock drift 60 s month at 25 C 77 F Clock battery autonomy in the absence of a power supply 24 h at 25 C 77 F Clock battery charging time 24 h the battery is charged by the power supply of the device Analogue inputs 2 for J K thermocouples or Pt 100 2 wire probes chamber p...

Reviews: