C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
Page
63
Hd42
Comp. 2 thermal
DI pos.
Sets the position of the
compressor 2 thermal alarm
digital input
2
0
12 (22)
CO-Hw
Max
=10(18) on
C-PRO
MEGA
RACK;
Visibility *¹
Hd43
Comp. 3 thermal
DI pos.
Sets the position of the
compressor 3 thermal alarm
digital input
3
0
12 (22)
CO-Hw
Max
=10(18) on
C-PRO
MEGA
RACK;
Visibility *¹
Hd44
Comp. 4 thermal
DI pos.
Sets the position of the
compressor 4 thermal alarm
digital input
4
0
12 (22)
CO-Hw
Max
=10(18) on
C-PRO
MEGA
RACK;
Visibility *¹
Hd45
Comp. 5 thermal
DI pos.
Sets the position of the
compressor 5 thermal alarm
digital input
0
0
12 (22)
CO-Hw
Max
=10(18) on
C-PRO
MEGA
RACK;
Visibility *¹
Hd46
Comp. 6 thermal
DI pos.
Sets the position of the
compressor 6 thermal alarm
digital input
0
0
12 (22)
CO-Hw
Max
=10(18) on
C-PRO
MEGA
RACK;
Visibility *¹
Hd47
Comp. 7 thermal
DI pos.
Sets the position of the
compressor 7 thermal alarm
digital input
0
0
12 (22)
CO-Hw
Max
=10(18) on
C-PRO
MEGA
RACK;
Visibility *¹
Hd48
Comp. 8 thermal
DI pos.
Sets the position of the
compressor 8 thermal alarm
digital input
0
0
12 (22)
CO-Hw
Max
=10(18) on
C-PRO
MEGA
RACK;
Visibility *¹
Hd49
Comp. 9 thermal
DI pos.
Sets the position of the
compressor 9 thermal alarm
digital input
0
0
12 (22)
CO-Hw
Max
=10(18) on
C-PRO
MEGA
RACK;
Visibility *¹
Hd50
Comp. 10
thermal DI pos.
Sets the position of the
compressor 10 thermal
0
0
12 (22)
CO-Hw
Max
=10(18) on