114CP3OEE104
c-pro 3 OEM -
Hardware manual
Housing and blind version configuration
Through a controller with user interface
Configuration
The following procedures show an example of how to configure a blind programmable controller through a programmable
controller with user interface (in the example c-pro 3 OEM LCD):
1. Disconnect the controllers power supply
2. Connect the blind controller to the controller with user interface through the CAN CANBUS port
3. Connect the controllers power supply
Switching ON/OFF the device
Progression Description
1
Connect the blind controller to the controller
with user interface through the CAN CANBUS
port
2
Touch
UP
and
DOWN
keys for 2 seconds:
the display will show the main menu
3
To switch OFF the device switch OFF the power
supply
Accessing the procedure from c-pro 3 OEM LCD
Key
Instructions
Touch
UP
and
DOWN
keys for 2 seconds:
the display will show the main menu
Touch
ESC
key few times to return to the previous
displays
c-pro 3 OEM blind
c-pro 3 OEM blind
c-pro 3 OEM LCD
c-pro 3 OEM LCD
CAN node address setting
Key
Instructions
Touch
UP
and
DOWN
keys for 2 seconds:
the display will show the main menu
Touch
UP
or
DOWN
keys to see the “
Network
” menu
Touch
ENTER
key to select the menu
Touch
ENTER
key to enter the password
Touch
UP
or
DOWN
keys to set-up the password
“-19”
Touch
ENTER
key to confirm the password
Touch
UP
or
DOWN
keys to see the “
CAN Bus
” menu
Touch
ENTER
key to select the menu
Touch
UP
or
DOWN
keys to see the “
NetworkNode
”
menu
Touch
ENTER
key to select the menu
Touch
UP
or
DOWN
keys to set-up the node [1]
Touch
ENTER
key to confirm the node
Touch
UP
and
DOWN
keys
to select the right arrow
“>”
Touch
ENTER
key
Touch
ESC
key few times to return to the previous
displays
The default setting of the CAN node is 1.
Operate on the controller with user interface to set the
“NetworkNode” parameter to [ 1 ].