14
2. Install
wall dock
x mm
2.7
Measure the power cable’s diameter and cut out the
correct diameter of the rubber seal in order to allow the
power cable and optional data cables to get through.
Note:
Strain relief and rubber seal are supplied in a
separate bag in the box.
2.8
Feed the power line and optional data wiring through the
rubber seal.
The total length of the power line fed through the rubber
seal must be 180 mm.
Strip the power line over a length of 130 mm.
In case of stranded (flexible) wiring, use wire end sleeves
with a ferrule length of 12-15 mm and apply a square
crimp for optimal fit into the connection terminals.
2.9
Assemble the strain relief.
Depending on the feed wire’s thickness, use either the
small or large diameter on the strain relief. Simply flip
the symmetrical parts to obtain a different strain relief
diameter.
The strain relief also accommodates
for extra data cables on two sides
(e.g. UTP/CAT5E/CAT6).
Small
Large
Optional data cable
Optional data cable
Power line cable
EN