6

• 

Place the MMMH Type cubicle on a channel inside 

the building in accordance with the dimensions 

indicated in the right picture.

• 

• 

A 5cm gap should be left between the placed 

cubicles on the right or the left side inside the 

building and the wall.

• 

• 

Close the channel gaps.

• 

• 

Do not go below the dimensions indicated in the 

right picture.

3.3.1 Placement inside the Building:

3.3 - CUBICLE’S PLACEMENT

• 

Base holes that enable the cubicles to be fixed to the ground are provided as shown in the below picture.

• 

Fix the cubicles to the ground by using M10 steel peg or iron dowel.

•  The dispatched cubicles should 

be placed on the side and 
according to the illustrated 

figure.

• 

Do  not  go  below  the  provided 

dimensions.

•  The building dimensions  can be 

determined accordingly.

•  The gaps between the cubicles 

from one side and the ceiling 

and the back wall from the other 
side  should  be  at  least  300mm 
and 100mm respectively.

IMPORTANT WARNING:

All manuals and user guides at all-guides.com

Summary of Contents for 36-CR

Page 1: ...www evaelektromekanik com CABLE CONNECTION CUBICLE 36kV METAL ENCLOSED MODULAR SWITCHGEARS MMMH USER GUIDE Assembly Operating and Maintenance Instructions All manuals and user guides at all guides com...

Page 2: ...312 811 27 28 www evaelektromekanik com All rights reserved Any part of this catalogue can not be copied without the permission of the right holder It can only be copied and augmented with the writte...

Page 3: ...TEM OF THE FACILITY 9 3 8 PASSAGES OF AUXILIARY SERVICE AND CONTROL CABLES FROM CUBICLE TO ANOTHER 10 3 9 CONNECTION OF MV CABLES 11 3 10 MATTERS TO BE CONSIDERED AGAINST INTERNAL ARC WHEN THE CUBICLE...

Page 4: ...ol processes to all the modulars the products will be ready for delivery and installation 1 1 GENERAL SECTIONS eva 36 CR SWITCHING SYSTEM IS FULLY COMPLIANT WITH TS EN IEC 62271 1 TS EN IEC 62271 200...

Page 5: ...Main Busbar IAC A FL 16kA 1sec Protection Level TS 3033 EN 60529 IP3X Applied Standard TS EN IEC 62271 1 TS EN IEC 62271 200 Height mm 2250 Width mm 750 Depth mm 1400 1 3 KARAKTER ST K ZELL KLER LSC...

Page 6: ...er way as shown in the the pictures below In addition forklift is usually used to unload the cubicles from the truck and transport them to the assembly site 2 1 TRANSPORTATING WITH FORKLIFT Pipe Trans...

Page 7: ...ENT WITH THE CUBICLE Tools Dimensions Quantity Open End Wrench 10 2 Pcs Open End Wrench 13 2 Pcs Open End Wrench 15 1 Pcs Open End Wrench 17 1 Pcs Open End Wrench 19 1 Pcs Open End Wrench 24 1 Pcs Tor...

Page 8: ...3 CUBICLE S PLACEMENT Base holes that enable the cubicles to be fixed to the ground are provided as shown in the below picture Fix the cubicles to the ground by using M10 steel peg or iron dowel The...

Page 9: ...should be used Then the holes to be fixed with M10x50 bolts MV Cable Entry Point Pull the lifting hooks upwards See below pictures Bring the cubicles to the settlement area by using the relevant tran...

Page 10: ...0Nm torque 3 Wipe the insulators and solid insulation materials with a dry clean cloth 4 Assemble the upper cover plate IMPORTANT WARNING If the surface on which the cubicles will be mounted is not fl...

Page 11: ...m use the grounding busbar located in the cable connection compartment of the cubicles See Picture 4 Any of the cubicles at the beginning or at the end of the cubicle s array can be used for this purp...

Page 12: ...picture 6 NOTE The connection between cubicle to another is made by combining the cable entry sockets that contain the electrical interlock and AC DC cables to each other NOTE The cable passage hole...

Page 13: ...h them See picture 8 1 Open the cubicle s cable connection compartment door 2 Mount the cable terminal caps internal type on the MV cable terminals in accordance with the related instructions 3 Connec...

Page 14: ...inside the cubicle and take it out 3 Check that there is at least 100 mm gap between the cubicles back and the building s wall and that there is no objects in between 4 Check whether the side cover pl...

Page 15: ...TION Tools Dimensions Quantity Dirt Chemical Solution Clean Cloth Open End Wrench 10 13 15 17 19 24 2 Pcs Torque Wrench 1 Pcs Socket Wrench 1 Pcs Socket 10 13 15 17 19 24 1 Pcs The manufacturer compan...