3.9 - CONNECTION OF MV CABLES
3.10- MATTERS TO BE CONSIDERED AGAINST INTERNAL ARC WHEN THE CUBICLE IS
MOUNTED
MV CABLES CONNECTION
MV Cables are made according to the cable terminal cap instructions.
The plastic plugs found at the cubicle’s bottom surface should be
adjusted in accordance with the cables diameter so to enable the cables
from passing through them. See picture (8).
1. Open the cubicle’s cable connection compartment door.
2. Mount the cable terminal caps ( internal type ) on the MV cable
terminals in accordance with the related instructions.
3.
Connect the mounted terminals to the cubicles’s output terminals.
See picture (7).
4.
Connect the metallic screen of the MV cables to the cubicle’s
earthing busbar.
5. Fix the MV cables by using the cable supporting points located on
the MV cables’ entrance of the cubicle. See pictutre (8).
Close the cubicle’s side by cover plates before the operating.