7300A User Manual
6-5
Digital Communication
6.5. DIGITAL COMMUNICATION PARAMETERS
PARAMETERS
The following parameters are at fixed addresses allowing the Master Modbus in order to
obtain data from the slave whatever power units from the 7000 range is used with the
digital communication option.
Abbreviation
Parameters name Decimal Status Format / Measure
Address
SL
Setpoint Local
01
R/W
0-255 (0-100%)
FS
Fast Setpoint transfer
02
R/W
0-255 (0-100%)
HS
High Setpoint Limit
16
R/W/M
0-255 (0-100%)
CL
Current Limit
17
R/W/M
0-255 (0-100%)
OS
Optional Status Word
18
R/W/M
HEX
SW
Status Word
32
R
HEX
XS
eXtended Status Word
33
R
HEX
OP
Output Power
34
R
0-255 (0-100%)
PV
Process Value
35
R
0-255 (0-125%)
SP
Working Setpoint
36
R
0-255 (0-100%)
PW
Power
37
R
0-255 (0-125%)
VV
Voltage Value
38
R
0-255 (0-125%)
C1
Current value channel 1
39
R
0-255 (0-125%)
C2
Current value channel 2
40
R
0-255 (0-125%)
C3
Current value channel 3
41
R
0-255 (0-125%)
CV
Current Value
42
R
0-255 (0-100%)
RI
Remote Input
43
R
0-255 (0-100%)
LL
Local Limit
44
R
51-255 (0-100%)
LS
Limit Setpoint
45
R
0-255 (0-100%)
HL
High Local limit
46
R
0-255 (0-100%)
DT
Delay Triggerring
47
R
0-90 (0-100%)
MI
Manufacturer Identifier
65280
R
ASCII
CW
Command Word
65488
R/W
0 - 7
GSW
General Status Word
65504
R
HEX
SN
Serial Number
65520
R
HEX
V0
Version 0
65522
R
HEX
V1
Version 1
65526
R
HEX
DI
Device Identifier
65528
R
0-65535
MF
Modbus Function
65529
R
HEX
CTO
Comm Time Out
65531
R/W/M
0-65535
STO
Setpoint Time Out
65532
R/W/M
0-255