7300A user Manual
2-9
Installation
Table 2-3 Description of control terminal blocks
Version
Terminal
Terminal description
Terminal
Torque
block name
No.
Name
Purpose
capacity
mm
2
AWG
Nm
Basic
ANA
31
0VA
0 V for analogue signals
or
32
RI
‘+’ for analogue signals
1.5
16
0.5
Options
33
5VA
5 V user output
A/F
16
230
230 V aux. supply
(except
17
115
115 V aux. supply
2.5
14
0.7
SELF)
18
0V
Neutral or second phase
Option
DIG
61
0VD
0 V logic signal
ICO
62
ACK
Alarm acknowledgement
1.5
16
0.5
63
5VD
5 V user output
Options
ALR
71
1a
Alarm relay
2.5
14
0.7
Alarms
72
1b
contact (code NC)
73
1a
Alarm relay
74
1b
contact (code NO)
Option:
EXT
21
N
Supply Neutral for 4S
DLF,
22
Not connected
VICL
Option
ADJ.CAL
66
0VC
0 V calibration
1.5
16
0.5
VICL
67
HRC
Calibration control
Digital
Comms
AUX2
19
24V
Auxiliary power supply
2,5
14
0,7
Option
20
0VS
29
GND
COM
91
B
Comme connector
2,5
14
0,5
92
A
2.5. CONTROL CONNECTIONS
Terminal blocks on the underside of the 7300A power thyristor unit are used to connect:
• the control signals (analogue and logic)
• the auxiliary or electronics supply and the neutral
• alarm relay and acknowledgement contacts
The wires used should be stripped for a length of 6 to 7 mm.
2.5.1. Control terminal blocks
The control terminal blocks are plug-in screw connectors.
The terminal blocks available depend on the power thyristor unit version and the selected
options in the product code.
The terminal names and numbers are marked on the front panel for available terminal
blocks. The table below gives details of all terminals and terminal blocks.