Chapter 10 User Instructions
582/583/5831
10 - 1
Chapter 10
User Instructions
CURRENT LOOP AND ZERO SPEED OPTION CARD
INTRODUCTION
The current loop and zero speed option card is intended to provide a speed reference and a zero
speed indication for the Eurotherm Drives 582/3 series of inverters.
Current loop format is configurable via the switches provided.
OPTION SWITCHES
Four current loop formats are available with this option card and are selected in the following
way:-
SW1
SW2
SW3
SW4
0.20mA
OFF
OFF
ON
OFF
4-20mA
ON
ON
ON
OFF
20-0mA
OFF
OFF
OFF
ON
20-4mA
ON
ON
OFF
ON
The 0/4-20mA formats will give an increase in speed for an increase in mA.
The 20-4/0mA formats will give an increase in speed for a decrease in mA.
ELECTRICAL SPECIFICATION
Accuracy
± 2% of FS
Input Impedance
100
Ω
Common Mode Voltage
30V
Bandwidth
20Hz
Zero Speed
N/O Contact
24V 2A contact
De-energized at Zero Speed
FITTING INSTRUCTIONS
Configure option switches and insert the connector onto the option pins provided on the inverter.
When fitted the components should be on the bottom side of the board and secured by a push fit
of nylon supports. If fitted incorrectly possible damage may occur.
Wiring Diagram over page:-
Summary of Contents for 582
Page 7: ......
Page 8: ......
Page 9: ......
Page 10: ......
Page 11: ......
Page 20: ......
Page 21: ......
Page 22: ......
Page 23: ......
Page 24: ......
Page 25: ......
Page 38: ...Figure B Mounting Details for Filter Part Number CO389108 ...
Page 39: ...Figure C Mounting Details for Filter Part Number CO389110 ...