Switching off the unused zone. 

 

Mixer 

 

Mixer dynamics

 

Determines  the  time  of  mixer  response  to  changes  in  the  zone  temperature.  An 
excessive  value  may  cause  frequent  cycling  of  the  mixer,  whereas  the  insufficient 
value may cause slowness in achieving the preset temperature.

 

 

Mixer hysteresis

 

If  the  measured  temperature  of  a  zone  differs  from  the  preset  one  by  half  of  the 
value of preset hysteresis, then the mixer position is not corrected.

 

 

Alarm temperature 

CAUTION!  Alarm  temperatures  for  all  zones  should  be  selected  carefully. 
Incorrect setting of temperature level may cause improper operation or major 
failure of the system components.

 

The  alarm  temperature  should  be  preset  as  the  maximum  safe  temperature  for  a 
particular zone.

 

 

Room thermostat

 

In this item, a user may switch off the inputs of room thermostats. In such a case the 
central heating will be switched on regardless of the requests of thermostats. 

 

Weather compensator

 

Weather  compensation  provides  a  possibility  to  achieve thermal comfort  regardless  of 
external  temperature.  The  only  requirement  is  to  connect  an  outdoor  temperature 
sensor. 
After switching the weather compensation on, temperatures of the CH zones for three 
outdoor  temperatures  should  be  set.  Based  on  those  the  controller  calculates  the 
currently required zone temperatures every 10 minutes.

 

 

CAUTION!  Temperatures  must  meet  the  condition  of 

T10ºC  ≤  T0ºC  ≤ 

T-

20ºC

 

otherwise, the control will not work properly. 

 

Maintenance  operation 

 

if  a  given  zone  does  not  require  heating  (the  schedule  is 

not  selected  or  room  thermostat  contact  is  open)  the  controller  will  respond  in  the 
following way: 

 

stop

 

 the pump will be switched off and the mixer closed,  

 

time-based

 

  the  zone  will  be  switched  on  for  a  preset  time  with  the  preset  idle 

time,  the  zone  temperature  will  be  decreased  by  the  value  of  the  "

Reduction

” 

setting, 

 

continuous

 

  the  pump  does  not  switch  off,  the  mixer  reduces  the  zone 

temperature by the value of the "

Reduction

” setting.

 

Settings for DHW circuit 

 

Switching the circuit on/off

 

In this item, a user may switch off the DHW circuit if not used.

 

 

Hysteresis

 

It is a difference between the temperature at which the tank feeding pump is switched 
off and on.

 

Summary of Contents for UNI4

Page 1: ...manual carefully Manual version 01 02 2021 1 APPLICATION UNI4 is a universal controller designed to control a heating system equipped with Two independent CH zones with mixing valves e g for floor hea...

Page 2: ...zone temperature sensor S5 CH2 zone temperature sensor R1 CH1 zone room thermostat R2 CH2 zone room thermostat P1 CH1 zone pump P2 CH2 zone pump P4 DHW circulation pump M1 230 V 3 point actuator of t...

Page 3: ...of a gas fired boiler or other heating devices with a voltage free output NO NC relay contacts Alarm output 230 V 50 Hz output Event log the controller stores 15 last alarms or irregular situations S...

Page 4: ...ation selecting between menu items up down next previous and a confirmation button located in the center of the knob which also clears the display of alarm warnings CAUTION When changing a setting the...

Page 5: ...cted days of the week DHW circulation circuit schedule With the use of schedule we may preset the time of DHW circulation circuit operation on selected days of the week Heating season Switching to the...

Page 6: ...ity to achieve thermal comfort regardless of external temperature The only requirement is to connect an outdoor temperature sensor After switching the weather compensation on temperatures of the CH zo...

Page 7: ...ection at 0 00 The proper cleansing consists in heating the DHW tank to the temperature of 70 C and flushing the pipes with hot water The disinfection icon active in the display may last for 2 hours m...

Page 8: ...proximate to alarm temperatures It is important to ensure a safe level of alarm temperature for each zone Pump starting temperature Above this temperature the pumps of CH 1 CH 2 zones and DHW circuit...

Page 9: ...uirements Do not install the controller in rooms of increased humidity protect it against water and other liquids The controller is designed to be mounted on a 35 mm DIN rail in a protective cabinet D...

Page 10: ...hermostat control may be switched on or off for each central heating zone It is only allowed to use thermostats with a voltage free normally open NO contact It is recommended to use Euroster devices T...

Page 11: ...EUROSTER UNI4 USER MANUAL 11 Connection diagram for the cooling mode...

Page 12: ...xceeds the required one CH circulation pump is switched on if heating is active and the mixer is not closed However if maintenance operation continuous operation was activated the pump operates withou...

Page 13: ...hen thermostat output is disconnected after reaching the preset temperature in rooms 5 7 Buffer Pump Output Feeding no 2 voltage type This output is used to control the buffer pump the pump of additio...

Page 14: ...nected inversely and whether it is not jammed 6 2 A selected zone is subject to overheating Check Whether the valve is not blocked Whether the mixer actuator is operating Whether the actuator cables a...

Page 15: ...the Directive 2006 66 EC of the European Parliament and the Council Such marking informs that the electrical and electronic equipment and batteries may not be disposed of together with other househol...

Page 16: ...on the day when the manufacturer received the claimed device 5 The device may be repaired exclusively by the manufacturer or by a party clearly authorized by the manufacturer 6 Warranty becomes void i...

Reviews: