EUROSTER UNI4 User Manual Download Page 5

EUROSTER UNI4 

 USER MANUAL

 

5

 

3.5. List screens

 

The controller settings are arranged hierarchically, according to the zone -> parameters order.  
Only the basic settings are available for the user. Advanced options are i

ncluded in “Settings” 

and are protected with an access code.

 

3.6. Setting screens

 

Adjustable parameters with comments are listed below.

 

3.6.1. User settings 
CH1 zone 

 

The preset temperature of the zone

 

It is the zone temperature maintained with the use of the mixer. When operating with 
the  weather  sensor,  there  are  three  settings  (based  on  which  the  heating  curve  is 
established). When operating without the weather sensor, one setting is available.

 

 

Schedule

 

With the use of schedule a zone may be switched off for the selected time on selected 
days of the week. 

CH2 zone

 

 

Parameters identical to the CH1 zone

 

DHW circuit 

 

DHW temperature

 

It is the tank temperature to be maintained by the controller.

 

 

DHW schedule

 

With the use of schedule, we may preset time to feed the DHW tank on selected days of 
the week. 

DHW circulation circuit 

 

schedule 

 

With the use of schedule, we may preset the time of DHW circulation circuit operation 
on selected days of the week.

 

Heating season 

 

Switching  to  the 

“SUMMER”  season  results

  in  switching  off  the  CH 1  and  CH 2  zones,  DHW 

circuits operate normally. 
Switching to the 

“WINTER” season results in switching on the CH zones and DHW circuits. 

 

Date and time

 

In  this  window,  a  user  may  enter  the  current  date  and  time.  Please  remember  that  the 
operation of the schedules, control algorithms, and events log is only correct with the correct 
settings.

 

Output testing

 

Testing all outputs by switching them on and off. Provides the possibility to check the correct 
operation  of  all  devices  connected  to  the  controller.  After  2  minutes  the  controller  exits  the 
testing mode and switches to automatic operation.

 

Settings

 

Entering advanced settings (installer settings).

 

3.6.2. Technician’s settings

 

The technician’s settings are available after entering th

e access code. 

The d

efault code is “1, 

2, 3”.

 

CAUTION! It is recommended to restore factory settings before configuring a new 
controller. 
Settings for CH 1 zone (identical ones for CH 2 zone) 

 

Switching the zone on/off

 

Summary of Contents for UNI4

Page 1: ...manual carefully Manual version 01 02 2021 1 APPLICATION UNI4 is a universal controller designed to control a heating system equipped with Two independent CH zones with mixing valves e g for floor hea...

Page 2: ...zone temperature sensor S5 CH2 zone temperature sensor R1 CH1 zone room thermostat R2 CH2 zone room thermostat P1 CH1 zone pump P2 CH2 zone pump P4 DHW circulation pump M1 230 V 3 point actuator of t...

Page 3: ...of a gas fired boiler or other heating devices with a voltage free output NO NC relay contacts Alarm output 230 V 50 Hz output Event log the controller stores 15 last alarms or irregular situations S...

Page 4: ...ation selecting between menu items up down next previous and a confirmation button located in the center of the knob which also clears the display of alarm warnings CAUTION When changing a setting the...

Page 5: ...cted days of the week DHW circulation circuit schedule With the use of schedule we may preset the time of DHW circulation circuit operation on selected days of the week Heating season Switching to the...

Page 6: ...ity to achieve thermal comfort regardless of external temperature The only requirement is to connect an outdoor temperature sensor After switching the weather compensation on temperatures of the CH zo...

Page 7: ...ection at 0 00 The proper cleansing consists in heating the DHW tank to the temperature of 70 C and flushing the pipes with hot water The disinfection icon active in the display may last for 2 hours m...

Page 8: ...proximate to alarm temperatures It is important to ensure a safe level of alarm temperature for each zone Pump starting temperature Above this temperature the pumps of CH 1 CH 2 zones and DHW circuit...

Page 9: ...uirements Do not install the controller in rooms of increased humidity protect it against water and other liquids The controller is designed to be mounted on a 35 mm DIN rail in a protective cabinet D...

Page 10: ...hermostat control may be switched on or off for each central heating zone It is only allowed to use thermostats with a voltage free normally open NO contact It is recommended to use Euroster devices T...

Page 11: ...EUROSTER UNI4 USER MANUAL 11 Connection diagram for the cooling mode...

Page 12: ...xceeds the required one CH circulation pump is switched on if heating is active and the mixer is not closed However if maintenance operation continuous operation was activated the pump operates withou...

Page 13: ...hen thermostat output is disconnected after reaching the preset temperature in rooms 5 7 Buffer Pump Output Feeding no 2 voltage type This output is used to control the buffer pump the pump of additio...

Page 14: ...nected inversely and whether it is not jammed 6 2 A selected zone is subject to overheating Check Whether the valve is not blocked Whether the mixer actuator is operating Whether the actuator cables a...

Page 15: ...the Directive 2006 66 EC of the European Parliament and the Council Such marking informs that the electrical and electronic equipment and batteries may not be disposed of together with other househol...

Page 16: ...on the day when the manufacturer received the claimed device 5 The device may be repaired exclusively by the manufacturer or by a party clearly authorized by the manufacturer 6 Warranty becomes void i...