3
TABLE 1-ELECTRICAL LOADING TABLE
HEATER UNIT INSTALLATION
1) Installation instruction f
1.1) Install the Undersink Heater as close as possible to the main hot water dra
points.
1.2) Leave a minimum of 5’’ of clearance on all sides for servicing.
1.3) Remove plastic cover. (Fig. 3 )
1.4) Mount unit securely to wall by putting two screws through mounting holes.
Screws and plastic wall plugs for mounting are provided. (Fig. 4)
2) The unit is to be installed in a closed, frost-free room. The unit is to be installed vertically
(Hot water connection downwards).
3) The unit can be installed in any location, conceal in the ceiling, below washbasin or even wall mounted.
HEATER UNIT INSTALLATION DIAGRAM
Mounting hole (A)
Fig. 4
Fig. 1
Fig. 2
248mm
155mm
Fig. 3
83mm
Mounting hole (B)
Voltage Power Current
(AC) (kW) (A)
Conductor Size (csa)
mm Conduit Cable Flexible Cable
On/ O
Fuse /
Switch (A) MCB (A)
240V
50/60 Hz
2.4 10.0 2.5 7 / 0.67mm 50 / 0.25mm 20 20
3.6
4.9 20.4 4.0 7 / 0.67mm 56 / 0.25mm 32 32
230V
50/60 Hz
3.3 14.4 2.5 7 / 0.67mm 50 / 0.25mm 20 20
4.5 19.6 2.5 7 / 0.67mm 50 / 0.25mm 32 32
6.0 25.0 4.0 7 / 0.85mm 56 / 0.30mm 32 32
220V
50/60 Hz
2.4 10.9 2.5 7 / 0.67mm 50 / 0.25mm 20 20
3.5 15.9 2.5 7 / 0.67mm 50 / 0.25mm 20 20
4.5 20.5 2.5 7 / 0.67mm 56 / 0.25mm 32 32
6.0 27.3 4.0 7 / 0.85mm 50 / 0.30mm 32 32
5.5 25.0 4.0 7 / 0.85mm 56 / 0.30mm 32 32
(Malaysia Modal)
15.0 4.0 7 / 0.85mm 50 / 0.30mm 20 20
3
TABLE 1-ELECTRICAL LOADING TABLE
HEATER UNIT INSTALLATION
1) Installation instruction f
1.1) Install the Undersink Heater as close as possible to the main hot water dra
points.
1.2) Leave a minimum of 5’’ of clearance on all sides for servicing.
1.3) Remove plastic cover. (Fig. 3 )
1.4) Mount unit securely to wall by putting two screws through mounting holes.
Screws and plastic wall plugs for mounting are provided. (Fig. 4)
2) The unit is to be installed in a closed, frost-free room. The unit is to be installed vertically
(Hot water connection downwards).
3) The unit can be installed in any location, conceal in the ceiling, below washbasin or even wall mounted.
HEATER UNIT INSTALLATION DIAGRAM
Mounting hole (A)
Fig. 4
Fig. 1
Fig. 2
248mm
155mm
Fig. 3
83mm
Mounting hole (B)
Voltage Power Current
(AC) (kW) (A)
Conductor Size (csa)
mm Conduit Cable Flexible Cable
On/ O
Fuse /
Switch (A) MCB (A)
240V
50/60 Hz
2.4 10.0 2.5 7 / 0.67mm 50 / 0.25mm 20 20
3.6
4.9 20.4 4.0 7 / 0.67mm 56 / 0.25mm 32 32
230V
50/60 Hz
3.3 14.4 2.5 7 / 0.67mm 50 / 0.25mm 20 20
4.5 19.6 2.5 7 / 0.67mm 50 / 0.25mm 32 32
6.0 25.0 4.0 7 / 0.85mm 56 / 0.30mm 32 32
220V
50/60 Hz
2.4 10.9 2.5 7 / 0.67mm 50 / 0.25mm 20 20
3.5 15.9 2.5 7 / 0.67mm 50 / 0.25mm 20 20
4.5 20.5 2.5 7 / 0.67mm 56 / 0.25mm 32 32
6.0 27.3 4.0 7 / 0.85mm 50 / 0.30mm 32 32
5.5 25.0 4.0 7 / 0.85mm 56 / 0.30mm 32 32
(Malaysia Modal)
15.0 4.0 7 / 0.85mm 50 / 0.30mm 20 20