Instruction Manual ZHK
V07-21.0
55/140
Figure 101:
Closing of the joints with sealant
5.1.6 Cable gland
For the connection of engines, pumps, electric heaters, sensors, etc., EUROCLIMA loosely sup-
plies material for cable glands (
), which must be installed efficiently and properly. The
following procedure is recommended:
1. Drilling through AHU casing (at right angles to the surface).
2. Enlarge drillings on external panel and internal panel according to
–
Size
(of the cable gland)
External drilling diameter
(for screwing)
Internal drilling diameter
(for sleeve)
M 16
17
19
M 20
21
23
M 25
26
28
M 32
33
35
M 40
41
43
M 50
51
55
M 63
64
71
Table 7:
Drilling diameters for cable glands
Figure 102:
Step drill
3. Insert sleeve (inside
–
) and screwing (outside
–
) into the drill-
ings and screw them together (see
Summary of Contents for ZHK