Simultaneity (ms): Is always selected. Defines the maximum permissible time (ms) between the switching of the different
signals received from the external contacts on the device.
Filter (ms): This parameter makes it possible to filter the signals from the device. This filter can be set to between 3 and
250 ms and removes any contact bounce. The time set for the filter affects the calculation of the total response time of
the module.
9.2.2.16. Table – Mode 1 (device with 2 NO + 1 NC)
POSITION 1: Enabling switch fully released
POSITION 2: Enabling switch pressed to center position
POSITION 3: Enabling switch pressed all the way down
Position
Input
1
2
3
IN1
0
1
0
IN2
0
1
0
IN3
1
1
0
OUT
0
1
0
Table 59: Only with 2 normally open co 1 normally closed contact
9.2.2.17. Table – Mode 2 (device with 2 NO + 1 NC)
POSITION 1: Enabling switch fully released
POSITION 2: Enabling switch pressed to center position
POSITION 3: Enabling switch pressed all the way down
Position
Input
1
2
3
IN1
0
1
0
IN2
0
1
0
IN3
1
0
0
OUT
0
1
0
Table 60: Only with 2NO + 1NC
Enable Error Out: If selected, an error detected by the function block is displayed.
Item Description: Here you can enter a functional description for the component. This text is displayed in the upper part of