6. Control of guard locking
By changing the parameters in the configuration tool of your control system, it can be set whether bit
O 0.0
(in the safe
data block for the MGB locking module) is evaluated as well (see chapter
13.7.4. Data block for MGB locking module L2
).
The guard locking solenoid is controlled if
Ì
bit O 0.0
OR
bit SO 0.0 = 1
Truth table:
PROFINET bit
PROFIsafe bit
Guard locking with
O 0.0
SO 0.0
MGB-L2…
0
0
inactive
0
1
active
1
0
active
1
1
active