13
2110182-09-12/18 (Translation of the original operating instructions)
Operating Instructions
Non-Contact Safety Switch CES-A-C5H-EX
EN
Note the following points:
Ì
Actuator and safety switch must be easily accessible for inspection and replacement.
Ì
Actuator and safety switch must be fitted so that
-the front faces are at the minimum switch-on distance 0.8 x S
ao
or closer when the guard is closed. To avoid entering
the area of possible side lobes, a minimum distance is to be maintained in case of a side approach direction. See
chapter 13. Technical data, section Typical operating distance for the related actuator.
-when the guard is open up to the distance S
ar
(assured switch-off distance), a hazard is excluded.
-the actuator is positively mounted on the guard, e.g. by using the safety screws included.
-they cannot be removed or tampered with using simple means.
Ì
Pay attention to the maximum tightening torque for the read head or safety switch and actuator fastenings of 1 Nm. For
read heads/actuators made of PE-HD, the maximum tightening torque is only 0.5 Nm.