33
MAN20001574-01-09/22 (translation of the original operating instructions)
Operating Instructions
Transponder-Coded Safety Switch CTM-C2-BP/BR-FLX
EN
Err
or code via IO-Link
LED indicator
Error
Troubleshooting
Ac-
knowl-
edging
errors
STATE
green
DIA
red
LOCK
yellow
Open/close door
Reset
Plausibility error
0x89
1 x
Transponder is no longer detected when guard lock-
ing is active. Actuator defective or malfunctioning.
Check actuator and replace it if necessary.
Guard locking was opened without active control:
Ì
Auxiliary release was actuated.
Ì
Internal error
Ì
Reset auxiliary release and restart the device.
Ì
On repeated occurrence, contact the manufacturer.
0x8c
15.4. Acknowledging error messages
If the DIA LED flashes inversely once, the error message can be acknowledged by opening and closing the guard. If the
error is still displayed afterward, a reset must be performed.
If the LED DIA is permanently illuminated, the error message can be acknowledged only by a reset.
The reset can be performed as follows.
Reset
Centrally for
all devices in a
chain
Each device
must be ad-
dressed individ-
ually
Further information
By briefly disconnecting the power supply
(at least 3 s)
-
-
Via the cyclical data of IO-Link communication
-
See operating instructions for the IO-Link Gateway
Via the acyclical data of IO-Link communication
-
See chapter
12.3.2. Acyclical data (device data and events) on
Resetting to acknowledge error messages does not delete the configuration.
Important!
Contact the manufacturer if the fault display is not reset after briefly disconnecting the power supply.