Operating Instructions
Transponder-Coded Safety Switch CTM-C2-BP/BR-FLX
26
(translation of the original operating instructions) MAN20001574-01-09/22
12.3.2. Acyclical data (device data and events)
After one of the commands listed below is sent, the requested data are provided via the IO-Link Gateway. The reply message
always consists of 8 bytes in big endian format.
Example 1
: Reply message in response to the command
Send device ID number/serial number
: 06
02 68 E0 00 01 17
00
In this example, the device’s ID number is
157920
and its serial number is
279
.
Byte number
Byte 0
Byte 1
Byte 2
Byte 3
Byte 4
Byte 5
Byte 6
Byte 7
Reply in hex
06
02
68
E0
00
01
17
00
Description
User data length
in bytes
Device ID number
Serial number
Padding data
Reply in dec.
6 bytes
157920
279
–
Example 2
: Reply message in response to the command
Send current actuator code
: 05 xx xx
00 5F
xx 00 00
In this example, the device’s actuator code is
95
.
Byte number
Byte 0
Byte 1
Byte 2
Byte 3
Byte 4
Byte 5
Byte 6
Byte 7
Reply in hex
05
00
5F
00
00
Description
User data length
in bytes
Current actuator code
Padding data
Reply in dec.
5 bytes
95
–
–
Command
Reply
HEX
Meaning
Number
of bytes
Bit sequences
(big endian format)
2
Send device ID number/serial number
6
Bytes 1 - 3
Device ID number
Bytes 4 - 6
Serial number
3
Send version number of the device
5
Byte 1
{V}
Bytes 2 - 4
Version number
5
Send number of devices in series connection
1
11
Send number of solenoid switching cycles
3
12
Send current error code
1
13
Send most recently saved error code
1
14
Send size of log file
1
15
Send entry from log file with index
1
16
Send current actuator code
5
17
Send taught-in actuator code
5
18
Send disabled actuator code
5
19
Send applied voltage in mV
2
0F
Send number of teach-in operations, factory resets and resets for
acknowledging error messages
3
Byte 1
Number of teach-in operations
Byte 2
Number of factory resets
Byte 3
Number of resets for acknowledging error messages
1A
Send current temperature in °C
1
1B
Send number of door position switching cycles
3
1D
Reset for acknowledging error messages
1)
-
1E
Factory reset
1
0x1E – Factory reset performed
1) Each BR device must be addressed individually in a chain.
For more information on these and other acyclical data, refer to the operating instructions for your BR/IO-Link Gateway.