2525462-01-01/20 (Translation of the original operating instructions)
Operating Instructions
Transponder-Coded Safety Switch CTM-LBI-BR
EN
6.6.
Guard locking on version CTM-LBI
(guard locking actuated by spring force and released by power-ON)
Activating guard locking:
close guard; no voltage at control input IMP.
Releasing guard locking:
apply voltage to control input IMP.
The spring-operated guard locking functions in accordance with the closed-circuit current principle. If the voltage is interrupted
at the solenoid, the guard locking remains active and the guard cannot be opened directly.
If the guard is open when the power supply is interrupted and is then closed, guard locking remains released. This prevents
people from being locked in unintentionally.
Important!
Malfunctions due to incorrect use.
Ì
The actuator must not be under tensile stress during release.
Ì
Very strong jolts or vibration can cause the guard locking state to change unintentionally. This gen-
erally applies when the switch is electrically isolated.
-The switch must not be used as a mechanical end stop.
-In case of heavy doors, ensure that the impact energy is cushioned on closing.
6.7.
Switching states
The detailed switching states for your switch can be found in the system status table. All safety outputs, monitoring outputs
and display LEDs are described there.
Guard closed and locked
Guard closed and not locked
Guard open
Betätiger
Schalter
Betätiger
Schalter
Betätiger
Schalter
Control input IMP
off
on
off = Guard locking is activated imme-
diately on closing
on = Guard locking remains released
on closing
Safety outputs FO1A and FO1B
on
off
off
Guard locking monitoring output OL
on
off
off
Door monitoring output OD
on
on
off