Operating Instructions
Non-Contact Safety Switch CES-A-C5H-EX
26
(Translation of the original operating instructions) 2110182-10-02/20
13.2.2. Typical actuating range
Only in conjunction with actuator CES-A-BPA-EX on surface mounting.
45
40
35
30
25
20
15
10
-45
5
Z
Y
X
5
10
15
20
25
30
35
40
45
45
40
-45
35
30
25
20
15
10
5
For a side approach direction for the actuator and read head, a minimum distance of s = 6 mm must be maintained so that the
actuating range of the side lobes is not entered.
13.2.3. Actuating range for center offset m = 0
1)
Parameter
Value
Unit
min.
typ.
max.
Operating distance
-
22
1)
-
mm
Assured operating distance S
ao
15
-
-
Switching hysteresis
1
2
-
Assured release distance S
ar
-
-
58
1) On surface mounting on aluminum; the typical operating distances increase to 30 mm in a non-metallic environment.