Operating Instructions
Non-Contact Safety Switch CES-A-C5H-EX
20
(Translation of the original operating instructions) 2110182-10-02/20
11.2.2. Carrying out teach-in for a new actuator
A maximum of 8 teach-in operations can be performed. The number of already completed teach-in operations is signaled
by the flashing sequence of the STATE LED each time the power supply is connected (see
12. System status table on page
, area
Status indication
).
Faulty actuators can be replaced. Then a complete teach-in operation must be performed as per this section.
To trigger a further teach-in operation, the user must perform the following actions in the stipulated order:
1. Start teach-in operation
-Switch on operating voltage
-Close door to be monitored (the new actuator must be in the actuating range of the read head)
-Teach-in operation starts (STATE LED flashes at approx. 1 Hz)
-Wait for acknowledgment of the teach-in operation (STATE LED goes out after approx. 60 seconds)
2. End teach-in operation
-Interrupt operating voltage for at least 3 seconds (code for the new actuator taught-in is activated)
The newly taught-in actuator is saved and the old actuator deactivated.
3. Check safeguard for effectiveness
11.3. Functional check
After installation and any fault, the safety function must be fully checked. Proceed as follows:
WARNING
Danger of fatal injury as a result of faults in installation and functional check.
Ì
Before carrying out the functional check, make sure that there are no persons in the danger zone.
Ì
Observe the valid accident prevention regulations.
1. Switch on operating voltage.
-The safety switch carries out a self-test.
The green STATE LED flashes up to 3 times.
The STATE LED then illuminates continuously.
The OUT and ERROR LEDs do not light up.
2. Close all guards.
-The machine must not start automatically.
-The green STATE LED and the yellow OUT LED light up continuously.
3. Enable operation in the control system.
4. Open the guard.
-The machine must switch off and it must not be possible to start it as long as the guard is open.
-The green STATE LED illuminates continuously; the OUT and ERROR LEDs do not illuminate.
Repeat steps 2 … 4 separately for each guard.