BE SURE THE UNIT DISCONNECT IS IN THE

 

“OFF” POSITION 

AND  THAT  ALL  ELECTRICAL  POWER  TO

 

THE  UNIT  IS 

TURNED OFF BEFORE CLEANING THE

 

SYSTEM. 

Remove  any  loose  grass,  leaves,  papers,  etc.,  from  the  area 
around the condenser coil. These could reduce the air supply 
through the coil and reduce the amount of cooling capacity. 

3.

Since the air conditioner is located outdoors, it is exposed to all

weather elements. Treat it with a good automobile paste wax 
twice a year (in the spring and fall). 

Check with your contractor if you have any questions regarding 
the maintenance or operation of your unit. 

INSTALLATION 
A. CODES

 

The installer SHALL comply with all local, state, and federal codes 
and/or  regulations  pertaining  to  this  type  of  equipment  and  its 
installation. 

Such  codes 

and/or  regulations  should  take 

precedence over any recommendations contained herein. 

Installations SHALL be made in accordance with the National 
Electrical  Code,  local  codes,  and  recommendations  made  by  the 
National Board of Fire Underwriters. 

B. UNIT SITE SELECTION 

1.

To  eliminate  noise  from  being  transmitted  into  noise
sensitive  areas,  the  unit  should 

NOT 

be  installed  on  walls

adjoining  bedrooms,  sleeping  quarters,  or  adjacent  to
windows.

2.

Locating  the  unit  as  close  as  possible  to  the  main  duct
system  or  area to  be conditioned, will prevent lengthy duct
runs and unnecessary thermal and air-pressure losses.

3.

The  clearance  to  combustibles  is  0"  on  all  sides,  and  1/4"
for the first three (3) feet of supply duct.

4.

The  condenser  air  inlets  (left,  right  and  bottom  inlets)
SHALL  be  located  at  least  8"  away  from  walls  or  other
obstructions for unrestricted airflow.

5.

The condenser air outlet should be located at least 6’ away
from any obstructions to prevent recirculation of condenser
air.

6.

Bottom of the unit SHALL be located at least 12" away from
the ground or other obstructions for unrestricted airflow.

7.

Service  clearance  is  28"  from  the  electrical  box  access
panel  located  on  the  front  of  the  unit  and  28"  from  the
center, upper, and lower front access panels.

8.

The wall selected for unit installation MUST be able to or be
made to safely support the weight of the unit.

9.

Do 

NOT 

locate  where  heat,  lint  or  exhaust  fumes  will  be

discharged on the unit (as from dryer vents).

C. UNIT PREPARATION 

1.

The  T  Series  model  units  have  top  rain  flashing  built  onto
the  unit.  The  bottom-mounting  flange  for  all  models  is
shipped 

separately  and  in place. (Refer to “Section J.  Unit

Installation”  for  the  recommended  use  of  the  bottom
flange.)

2.

Electrical  entrances  are  located  on  the  right  side  and  left
side  of  all  T 

Series  units.  Refer  to  “Section  H.  Electrical

Hook-

up” for details.

3.

Bend  the  lids  of  return  and  supply  opening  to  form  return
and supply air collars and install air gaskets.

4.

The  supply  and  return  air  ducts  should  be  checked  to  be
sure they:
a.

Match the openings on the unit to be installed.

b.

Have  the  same  distance  between  them  vertically  as
the openings on the unit to be installed.

5.

Return  and  supply  grilles must  be  used  when  the  return
and supply are not ducted. When a supply grille is  used
in the installation, the louver spacing must be no greater
than 5/8 inch.

6.

If  the  factory-installed  filter  is  used  on  your  installation,
access to the filter is made through the center panel on the
front of the unit.

IF  A  REMOTE  FILTER  IS  USED,  SUCH  AS

 

A  FILTER  GRILLE, 

THE FACTORY-INSTALLED FILTER

 

MUST BE REMOVED AND 

DISCARDED.

 

D. DUCTWORK 

1.

Properly-sized  duct  systems  are  critical  for  satisfactory
operation  of  any  air  conditioning  system.  All  ductwork
MUST be correctly sized for the design air flow requirement
of the equipment.

2.

The  recommended  operation  duct  static  is  to  deduct  0.07"
W.C.  for  any  size  of  heater  5  kW  to  20  kW  on  factory  or
field-installed heaters.

3.

Ductwork routed through  wall cavities,  as well  as  any  duct
not  in  conditioned  space,  MUST  be  insulated.  Supply
ducting  routed  through  exterior  walls  MUST  be  insulated
with 1" insulation to the back of the unit.

4.

Supply and return air ducts should be flush with the exterior
wall  and  sized  to  fit  over  the  unit  duct  collars  in  order  to
compress the collar air gasket.

5.

If  supply  duct  is  flashed  to  the  exterior  of  a  building
constructed  with  combustible  material, the flashing MUST
be  insulated  in  order  to  maintain  the  required  clearances
to  combustible  materials.  Required  clearance  is  1/4"  for
the first three (3) feet of supply duct.

E. FILTERS 

1.

One-inch  disposable  filters  are  supplied  standard  in  each
unit.  Two-inch  disposable  filters  can  also  be  used  and  are
available  as  an  option.  The  filter  rack  is  adjustable  to
accommodate  2"  filters.  The  filter  rack  on  this  series  is
adapted  by 

removing  the  1”  filter  brackets.  Refer  to  the

Maintenance  section  for  the  procedures  for  changing  the
filters.

2.

If a filter grille is used in the installation, the filter should be
properly sized to allow a maximum velocity of 400 FPM.

WHEN  USING  A  FILTER  GRILLE,  THE  FACTORY-INSTALLED 
FILTER MUST BE REMOVED. 

F. ELECTRICAL POWER 

The  installer  MUST  check  available  power  to  make  certain  it 
matches  the  unit  nameplate  rating  and  that  constant  voltage  can 
be  maintained to the  unit. Unsatisfactory  and  unsafe  performance 
could  otherwise  result.  The  local  power  company  should  be 
contacted about questions concerning power supply. 

G. BREAKER/DISCONNECT ASSEMBLY 

These  units  are  standard  equipped  from  the  factory  with  a  unit 
disconnect. This  is  in the form  of  a circuit  breaker (230V models) 
or disconnect (460V models). If an optional electric heat kit is to be 
installed, follow the instructions included with the heater assembly. 
See Figure 1 for reference. 

Summary of Contents for TV36D

Page 1: ...REV G 3 01 17 1 3090016 Installation Operation and Maintenance TV SERIES 10 EER Wallmount Air Conditioners ...

Page 2: ... the last page of this manual In all cases the equipment MUST be installed in accordance with the installation instructions described in this manual WARNING IMPROPER INSTALLATION MAY DAMAGE EQUIPMENT CAN CREATE A HAZARD AND WILL VOID THE WARRANTY OPERATING INSTRUCTIONS If heating and cooling functions are controlled by separate thermostats turn the furnace thermostat to the OFF position during the...

Page 3: ...ng to form return and supply air collars and install air gaskets 4 The supply and return air ducts should be checked to be sure they a Match the openings on the unit to be installed b Have the same distance between them vertically as the openings on the unit to be installed 5 Return and supply grilles must be used when the return and supply are not ducted When a supply grille is used in the instal...

Page 4: ...Wire the first stage heat to terminal W2 Wire the second stage heat to terminal E J UNIT INSTALLATION T SERIES UNITS ARE FOR USE IN SINGLE STORY BUILDINGS ONLY 1 As previously stated the wall that the unit is to be installed onto MUST be strong enough to support the unit under the condition for which it will be used For example a unit to be installed on a building that is intended to be transporte...

Page 5: ...REV G 3 01 17 5 3090016 D PARTS DRAWING 48 EXPLODED PARTS DRAWING 36 48 60 ...

Page 6: ... X 14D 454236 BLWR MTR BRKT WASHER X X X X X X X X X 14E 750058 BLWR MTR BRKT BOLT 1 4 20 X X X X X X X X X 15 T36 0000B ASSEMBLY LEFT SIDE PANEL TV36 X X X 15A T36 0135 OD GRILL INLET LEFT SIDE TV36 X X X 15 T60 0008 ASSEMBLY LEFT SIDE PANEL TV48 60 X X X X X X 15A T60 0091 OD GRILL INLET LEFT SIDE TV48 60 X X X X X X 15B T36 0126 ERV INTAKE AIR PANEL X X X X X X X X X 16 T36 0001B ASSEMBLY RIGHT...

Page 7: ... 31 T36 0009 CONTROL PANEL TV36 X X X 31A T36 0093 TERMINAL BOARD PANEL TV36 X X X 31 T60 0009 CONTROL PANEL TV48 60 X X X X X X 31A T60 0093 TERMINAL BOARD PANEL TV48 60 X X X X X 32 T36 0036 CONTROL PANEL COVER TV36 X X X 32 T60 0036 CONTROL PANEL COVER TV48 60 X X X X X X 33 T36 0015 HEAT SHIELD TV36 X X X 33 T60 0015 HEAT SHIELD TV48 60 X X X X X X 453150 COMP CONTACTOR 1 POLE 1P 25 AMP X X 45...

Page 8: ...4 6 1 10 15 14 14 9 1 16 20 14 12 15 1 25 30 10 10 TV48S00 208 230 1 1 33 50 10 10 5 1 33 50 10 10 10 1 58 60 6 10 15 2 27 52 30 60 10 6 10 10 TV48T00 208 230 3 1 24 30 12 10 6 1 24 30 12 10 9 1 33 40 10 10 15 1 50 60 6 10 18 1 OR 2 60 70 6 8 TV48D00 460 3 1 12 15 14 14 6 1 13 15 14 14 9 1 17 20 14 12 15 1 26 30 10 10 TV60S00 208 230 1 1 40 60 8 10 5 1 40 60 8 10 10 1 58 60 6 10 15 2 34 52 40 60 1...

Page 9: ......

Page 10: ......

Page 11: ......

Page 12: ......

Page 13: ......

Page 14: ......

Page 15: ......

Page 16: ...REV G 3 01 17 16 3090016 NOTES ...

Page 17: ......

Page 18: ...t products Illustrations part numbers and others cover the general appearance of the units at the time of publication and the Manufacturer reserves the right to make changes in design and construction at any time without notice For replacement parts contact National Coil Company 1998 FM 2011 Longview TX 75603 Phone 903 643 2261 Fax 903 643 2222 www EubankNCC com ...

Reviews: