Eubank TV36D Installation, Operation And Maintenance Manual Download Page 2

REV

 G 3/01/17

309001

6

.

Your  equipment  is  covered  by  a  LIMITED  WARRANTY  against 
defects in material and workmanship. 

This  is  a  vertical,  wallmount  unit  designed  for  many  different 
applications  in  both residential  and commercial settings.  It  is  self-
contained  and  arrives completely  assembled, factory-charged  and 
wired. The unit is 100% run-tested  at the factory to ensure proper 
operation. Your unit is supplied with high-quality copper tubing and 
enhanced  aluminum-finned  coils  for  high  heat  transfer  efficiency 
and  long  life.  The  unit  cabinet  is  constructed  of  G-90  galvanized 
steel.  All  exterior  surfaces  are  finished  with  a  baked-on  polyester 
coating.  This  will  provide  excellent  corrosion  protection  in  most 
applications.  However,  if  the  unit  is  installed  in  an  area  with  a 
corrosive  atmosphere,  such  as  near  an  industrial  plant  or  on  the 
seacoast,  additional  coating  should  be  considered  to  extend  the 
life of the coils and cabinet.  

This unit was designed for up to 105ºF of ambient temperature. 

INSPECTION AND UNPACKING 

A  thorough  inspection  of  the  shipping  container  should  be  made 
immediately  upon  receiving  your  unit.  Look  for  any  punctures  or 
openings.  If  it  appears  as  if  damage  has  occurred,  it  should  be 
noted  on  the  freight  bill  before  signing.  The  delivering  carrier 
should  be  contacted  immediately  to  inspect  damage,  and  no 
installation work should begin until this inspection is completed. 

DANGER:

 

BEFORE 

PERFORMING 

ANY

WORK  ON  THIS  EQUIPMENT,  POWER  SUPPLY 
MUST  BE  TURNED  OFF  AT  THE  HOUSEHOLD 
SERVICE  BOX  TO  AVOID  THE  POSSIBILITY  OF 

SHOCK, INJURY, DEATH, OR DAMAGE TO EQUIPMENT. 

SAFETY RULES 

WARNING:

  FAILURE  TO  FOLLOW  THESE

RULES  AND  INSTRUCTIONS  COULD  CAUSE  A 
MALFUNCION 

OR 

DESTRUCTION 

OF 

EQUIPMENT 

WHICH 

COULD 

RESULT 

IN 

PROPERTY  DAMAGE,  SERIOUS  BODILY  INJURY,  OR 
DEATH. 

1.

Installation and repair MUST be done by a qualified person.
The equipment should be inspected before use and at least
once annually by a professional service person.

2.

AVOID  ELECTRICAL  SHOCK! 

Turn  power  OFF  when

servicing.  There  may  be  more  than  one  disconnect  switch
to de-energize unit.

3.

Close cover(s) before returning breaker(s) to “ON” position.

4.

Please  observe  good safety  practices  by wearing personal
protective  equipment such  as gloves  and safety glasses to
avoid injury.

5.

Installation MUST conform to local codes. In the absence of
local  codes,  refer  to  the  National  Electrical  Code  (NEC),
ANS/NFPA  No.  70-1993  and  recommendations  made  by
the National Board of Fire Underwriters.

In  our continuing  effort to improve  our product, specifications may 
change  without  notice.  If  there  are  any  questions,  please  see  the 
contact information on the last page of this manual.  

In all cases, the equipment MUST be installed in accordance with 
the installation instructions described in this manual. 

WARNING:

 IMPROPER INSTALLATION MAY

DAMAGE  EQUIPMENT,  CAN  CREATE  A  HAZARD, 
AND WILL VOID THE WARRANTY 

OPERATING INSTRUCTIONS 

If  heating  and  cooling  functions  are  controlled  by  separate 
thermostats,  turn  the  furnace  thermostat  to  the  “OFF”  position 
during the cooling season to prevent simultaneous operation of the 
heating  and  cooling  systems.  Reverse  the  procedure  during  the 
heating season. 

 If  the  same  thermostat  controls  both  heating  and  cooling 
functions, set the thermostat to either HEAT or COOL as desired.  

Set  the  desired  temperature  on  your  thermostat  and  set  the  fan 
switch to “ON” (for continuous  air circulation)  or to  “AUTOMATIC” 
(for  air  circulation  only  when  the  air  conditioning  system  is 
operating). 

IMPORTANT: 

Wait  at  least  three  (3)  minutes  after  turning  the  air 

conditioner off before trying to restart. If an attempt is made to start 
the compressor before the refrigerant pressures are  equalized, the 
compressor  motor  may  trip  on  its  overload.  An  additional  waiting 
period will be required before restarting. 

MAINTENANCE 

1.

Always  install  and  keep  filters  clean.  Check  filters  every  2

weeks. Clean or replace if necessary.  The factory-installed filter is 
located behind the center front access panel. 

TO CHANGE SYSTEM FILTER: 

A.

 

Turn  the  power  to  the  unit  off  at  the  unit  disconnect.  The 
disconnect  is  located  on  the  front  of  the  T  Series  unit 
behind a small access door. 

B.

 

Remove the front center access door from the unit. 

C.

 

Remove  and  replace  the  filter  with  the  type  and  size 
indicated in the table below. 

D.

 

Replace the access door and turn on the power to the unit. 

NOTE: 

If  your  system  has  a  filter  grille  installed  in  the  return  air 

opening,  the  unit  filter  should  have  been  discarded  during 
installation. 

The  filter  installed  into  the  return  air  grille  assembly  should  be 
replaced with the same size and type provided with the grille. 

If your system  is  equipped with  a fresh  air  intake, the filter for the 
fresh air assembly is accessed through the front center panel. The 
filter is a permanent washable type. 

UNIT MODEL 

QTY. 

FILTER SIZE 

TYPE 

36 

16 x 30 x 1 

(standard) Disposable 

36 

16 x 30 x 2 

(optional) Pleated 

48, 60 

1

 

20 x 30 x 1 

(standard) Disposable 

48, 60 

1

 

20 x 30 x 2 

(optional) Pleated 

WARNING

:  SERIOUS  INJURY  MAY  RESULT  IF

WATER  SPRAY  IS  DIRECTED  TOWARD  LIVE 
ELECTRICAL 

CONNECTIONS 

OR 

POWER 

SOURCES.  

TO CLEAN FRESH AIR INTAKE FILTER: 
A. 

Follow steps A and B above.  

“TO CHANGE SYSTEM FILTER”.

 

 

B. 

Gently pull out the filter from the bottom. 

C. 

Wash the filter with water. 

D. 

Reinstall  the  filter,  by  sliding  it  into  the 

retaining rail. 

E. 

Replace  the  access  door  and  turn  the 

power on to the unit. 

2.

Keep  the  outdoor  coil  clean.  Wash  it

down with a garden hose if necessary. 

Summary of Contents for TV36D

Page 1: ...REV G 3 01 17 1 3090016 Installation Operation and Maintenance TV SERIES 10 EER Wallmount Air Conditioners ...

Page 2: ... the last page of this manual In all cases the equipment MUST be installed in accordance with the installation instructions described in this manual WARNING IMPROPER INSTALLATION MAY DAMAGE EQUIPMENT CAN CREATE A HAZARD AND WILL VOID THE WARRANTY OPERATING INSTRUCTIONS If heating and cooling functions are controlled by separate thermostats turn the furnace thermostat to the OFF position during the...

Page 3: ...ng to form return and supply air collars and install air gaskets 4 The supply and return air ducts should be checked to be sure they a Match the openings on the unit to be installed b Have the same distance between them vertically as the openings on the unit to be installed 5 Return and supply grilles must be used when the return and supply are not ducted When a supply grille is used in the instal...

Page 4: ...Wire the first stage heat to terminal W2 Wire the second stage heat to terminal E J UNIT INSTALLATION T SERIES UNITS ARE FOR USE IN SINGLE STORY BUILDINGS ONLY 1 As previously stated the wall that the unit is to be installed onto MUST be strong enough to support the unit under the condition for which it will be used For example a unit to be installed on a building that is intended to be transporte...

Page 5: ...REV G 3 01 17 5 3090016 D PARTS DRAWING 48 EXPLODED PARTS DRAWING 36 48 60 ...

Page 6: ... X 14D 454236 BLWR MTR BRKT WASHER X X X X X X X X X 14E 750058 BLWR MTR BRKT BOLT 1 4 20 X X X X X X X X X 15 T36 0000B ASSEMBLY LEFT SIDE PANEL TV36 X X X 15A T36 0135 OD GRILL INLET LEFT SIDE TV36 X X X 15 T60 0008 ASSEMBLY LEFT SIDE PANEL TV48 60 X X X X X X 15A T60 0091 OD GRILL INLET LEFT SIDE TV48 60 X X X X X X 15B T36 0126 ERV INTAKE AIR PANEL X X X X X X X X X 16 T36 0001B ASSEMBLY RIGHT...

Page 7: ... 31 T36 0009 CONTROL PANEL TV36 X X X 31A T36 0093 TERMINAL BOARD PANEL TV36 X X X 31 T60 0009 CONTROL PANEL TV48 60 X X X X X X 31A T60 0093 TERMINAL BOARD PANEL TV48 60 X X X X X 32 T36 0036 CONTROL PANEL COVER TV36 X X X 32 T60 0036 CONTROL PANEL COVER TV48 60 X X X X X X 33 T36 0015 HEAT SHIELD TV36 X X X 33 T60 0015 HEAT SHIELD TV48 60 X X X X X X 453150 COMP CONTACTOR 1 POLE 1P 25 AMP X X 45...

Page 8: ...4 6 1 10 15 14 14 9 1 16 20 14 12 15 1 25 30 10 10 TV48S00 208 230 1 1 33 50 10 10 5 1 33 50 10 10 10 1 58 60 6 10 15 2 27 52 30 60 10 6 10 10 TV48T00 208 230 3 1 24 30 12 10 6 1 24 30 12 10 9 1 33 40 10 10 15 1 50 60 6 10 18 1 OR 2 60 70 6 8 TV48D00 460 3 1 12 15 14 14 6 1 13 15 14 14 9 1 17 20 14 12 15 1 26 30 10 10 TV60S00 208 230 1 1 40 60 8 10 5 1 40 60 8 10 10 1 58 60 6 10 15 2 34 52 40 60 1...

Page 9: ......

Page 10: ......

Page 11: ......

Page 12: ......

Page 13: ......

Page 14: ......

Page 15: ......

Page 16: ...REV G 3 01 17 16 3090016 NOTES ...

Page 17: ......

Page 18: ...t products Illustrations part numbers and others cover the general appearance of the units at the time of publication and the Manufacturer reserves the right to make changes in design and construction at any time without notice For replacement parts contact National Coil Company 1998 FM 2011 Longview TX 75603 Phone 903 643 2261 Fax 903 643 2222 www EubankNCC com ...

Reviews: