3. Leds and Buttons on Front Panel

•  General Fault Led: 

This led is ON together with written fault code on 7 segment display 

when low current, high current, low voltage and high voltage protections are active.

•  Up / Down Buttons: 

These buttons enable to surf within menus on 7 segment display and 

they are used to set values of numerical parameters. In addition to this, the fault occured on 

the system can be reset whşle pressing these buttons together for 5 seconds.

•  Approval Button:

 This button enables to enter submenus and save the parameter already 

set values.

•  Switch Led: 

This led is ON when the pressure switch on the system is active. 

•  ON/OFF Button: 

 This button is used to start-up and switch-off the panel OFF is written on 7 

segment display when the panel is switched-off and there is power supply on the system.

Voltage value between L1-L2-L3 and neutral is 

displayed in sequence as seen on the right hand 

side when there is no signal from pressure switch. 

In case there is signal from pressure switch and 

system starts operating, pump current is displayed.

When display is on main screen and “Approval” 

button is pressed, High Voltage Protection Setting 

Menu is displayed. It is possible to enter the 

submenu by re-pressing the “Approval” button and 

high voltage protection value can be set by using 

“Up/Down” buttons

Low Voltage Protection Setting Menu can be 

reached by pressing “Approval” button first and 

then “Down” button for once when display is on 

main screen. It is possible to enter the submenu by 

re-pressing the “Approval” button and low voltage 

protection value can be set by using “Up/Down” 

buttons.

4. Menus

a.  High Voltage Protection Setting Menu 

b.  Low Voltage Protection Setting Menu 

Figure 4. Panel Main Operating Screen

Figure 5. High Voltage Setting Menu

Figure 6. Low Voltage Setting Menu

Summary of Contents for Hydropan

Page 1: ...Hydropan Single with Alarm Kit Operation and Maintenance Manual...

Page 2: ...witch Fault warning leds as well as Up Down buttons used to surf in menus Approval button to confirm parameter changes and ON OFF button System parameters can be set easily by using Up Down Approval b...

Page 3: ...3 www etna com tr Connectors Cable Glands Voltage Transformer 7 Segment Display Connection Cable Current Transformers Power Relays Earth Connection Bar Figure 2 Hydropan Single Internal View...

Page 4: ...rrent Protection Setting High Current Protection Setting Current and Voltage fault delay time setting General Fault Dry Running and Pressure Switch signal warning leds Pump running currents display on...

Page 5: ...wer supply on the system Voltage value between L1 L2 L3 and neutral is displayed in sequence as seen on the right hand side when there is no signal from pressure switch In case there is signal from pr...

Page 6: ...in screen It is possible to enter the submenu by re pressing the Approval button and fault display delay duration value can be set by using Up Down buttons Pump Operation Mode Selection Menu as P6 see...

Page 7: ...s active when Pump Operation Mode parameter set to 1 or 2 requested time duration for well filling or discharging can be set in minutes If this parameter is set to 0 it becomes out of use Figure 11 We...

Page 8: ...otor label Check motor cable and connector connections ERROR 5 LOW CURRENT FAULT Before performing any measurement make sure there is no mechanical congestion in pump Make sure that pump suction valve...

Page 9: ...N 1 30A Relay TR U N MOTOR POWER POWER SUPPLY N L1 30A Relay U V W MOTOR POWER POWER INPUT PRESSURE SWITCH COM RUN FAULT WELL L1 L2 L3 Pe 30A Relay TRANSFORMER HYDROPAN 1 30A Relay TR 30A Relay PRESSU...

Page 10: ...Dudullu Organize Sanayi B lgesi 2 Cadde No 14 34775 mraniye stanbul Turkey Tel 90 216 561 47 74 Pbx Fax 90 216 561 47 50 www etna com tr en info etna com tr customer service...