P 27 Total duration on power (h)

Indicates inverter total duration on power (just readable)

 

P 29 Number of Start

Indicates inverter total number of start-up information (just readable)

P 31 Inverter Operation Condition

 Indicates inverter operation condition (Master- Slave)

Inverter Operation Condition Indicator on Internal Communication Line

SETTING PARAMETERS

Summary of Contents for Hydrokon

Page 1: ...Hydrokon Pump Booster Frequency Control Unit User Manuel...

Page 2: ...that you read this manual carefully and keep the manual safe together with the warranty card Warning Specifications 03 Driver Terminal Connection 05 Control Connections 08 Setting Parameters 09 Troubl...

Page 3: ...it to frequent shock Operate the device in a non vibrating environment Do not assemble the device near an electromagnetic radiation source Ensure the cable connections of the device are correct and co...

Page 4: ...thickness and fuse capacities should be selected according to the device input and output current values Power supply line cables and cables that control inductive load such as relay windings must be...

Page 5: ...assembly clamps of the inverter 5 Disassemble the upper cover by unbolting the 4 bolts located on the corner of the cover 6 Locate M5 x 50 mm sized screws on the inverter aluminium body 7 Fix assembl...

Page 6: ...ONS POWER INPUT MASTER SLAVE SELECTION SWITCH T W V U S R 12 BMS Connection 11 BMS Connection 2 Internal Communication 3 Floater 4 Floater 5 Transmitter 1 9 Transmitter 2 6 Transmitter 1 10 Transmitte...

Page 7: ...7 www etna com tr 220 V AC MONOPHASE POWER SUPPLIED INVERTER CONNECTION CHART V U MOTOR CONNECTION GROUNDING INPUT 220 V 0 NEUTRAL W...

Page 8: ...or No 7 2 External contact tip 0v GND Connector No 8 2 External contact tip Connector No 9 2 Pressure sensor 4 20 mA Connector No 10 2 Pressure sensor 4 20 mA Connector No 11 BMS Communication RS485 C...

Page 9: ...the valve and the pump set the autoset parameter The device calculates this pressure automatically There is no need to set the parameter for Slave devices It would be enough to correctly position the...

Page 10: ...Motor current A 2 DC bar voltage V Dc 3 Device temperature C Press P button and enter correct password Afterwards change P0000_ value to P0001_ by pressing up and down buttons Move the cursor to right...

Page 11: ...0_ value to P0003_ by using Up and Down buttons Move the cursor to right by using right button and increase or decrease the parameter value by using Up and Down buttons set the parameter by using left...

Page 12: ...to motor label value On other conditions not necessary Press P button and enter the correct password Change P0000_ value to P0006_ by using Up and Down buttons Move the cursor to right by using right...

Page 13: ...t pressure for operation and stop System operating pressure value bar in Automatic Mode Differential pressure p in Circulation Systems Press P button and enter the correct password Change P0000_ value...

Page 14: ...requency output of the inverter Hz Press P button and enter the correct password Change P0000_ value to P0012_ by using Up and Down buttons Move the cursor to right by using right button and adjust th...

Page 15: ...ration 2 Pump operation Press P button and enter the correct password Change P0000_ value to P0015_ by using Up and Down buttons Move the cursor to right by using right button and adjust maximum pump...

Page 16: ...ations Press P button and enter the correct password Change P0000_ value to P0018_ by using Up and Down buttons Move the cursor to right by using right button and adjust parameter to 1 Set the paramet...

Page 17: ...system reaches set pressure Min frequency Hysteresis P 22 Pump Type 1 2 2 1 Booster 2 Circulation Press P button and enter the correct password Change P0000_ value to P0021_ by using Up and Down butto...

Page 18: ...tton P 24 Phase fault 0 1 1 Phase protection is ON in case there is phase loss on input the inverter protects itself and motor and phase fault written on display P 25 Operating Hours h Indicates inver...

Page 19: ...power just readable P 29 Number of Start Indicates inverter total number of start up information just readable P 31 Inverter Operation Condition Indicates inverter operation condition Master Slave In...

Page 20: ...set as Master 100 Only Slave1 Enabled 020 Only Slave2 Enabled 004 Only Slave3 Enabled 120 Slave1 and Slave2 Enabled 104 Slave1 and Slave3 Enabled 024 Slave2 and Slave3 Enabled 124 Slave1 Slave2 and Sl...

Page 21: ...80V or 220V depending on the device model Regeneration effect Ensure the inverter supply voltage is within the operating range Increase the inverter stop ramp P3 Phase Error Valid for triphase devices...

Page 22: ...rter Operating hours 1250 i e 0x2015 Slave_1 Inverter Operating days 650 i e 0x2020 Slave_2 Inverter connected to System 1 Connected 0 Not connected 0x2021 Slave_2 Inverter Operation 1 Operating 0 Not...

Page 23: ...2 7 48 10 12 12 98 18 5 Input current A 3 7 4 9 5 9 10 12 5 16 25 Recommended Input Fuse A 10 16 20 32 Recommended Cable Diameter mm Input 1 5 2 5 4 Output 1 5 2 5 4 Dimensions mm w x l x d 200 X 200...

Page 24: ...Dudullu Organize Sanayi B lgesi 2 Cadde No 14 34775 mraniye stanbul Turkey Tel 90 216 561 47 74 Pbx Fax 90 216 561 47 50 www etna com tr en info etna com tr customer service...

Reviews: