PREPARING THE SETUP
Page 28
DOC_DEV_SIG_ User guide_A
4
Temporary return to the factory settings
If the IP address of the SIG could not be founded, or if it is impossible to access the administration server, for
example, following a configuration error, it is possible to restore the factory settings without losing the current
configuration.
•
Press the push-button B2 located on the back.
•
Keep the push-button pressed for about 3 seconds;
•
The LED blinks red rapidly
•
The administration server becomes accessible at the factory IP address (192.168.0.128), in HTTP without
a password. The factory configuration is temporarily running. However, the current configuration is not
lost and it is the one that is still displayed in the pages of the Administration Server.
•
After reading the IP address or changing some parameters, press again the push button (B2) or reboot the
product.
•
The product can be reached at the registered IP address.
Note:
If the IP address of the SIG is unknown, the software tool
EticFinder
can be used.
This software detects all ETIC branded products on a local network. After starting the software, click on the
"Search" button, and when the product list is displayed, double-click on the product address to access the html
server.
5
Restoring the factory settings
It is possible to restore the factory configuration permanently using the push button B2 on the rear panel, or
by using the administration server. In this case, the current configuration will be lost unless it has been saved
to a file.
To restore the factory settings using the push button,
•
Power off the SIG,
•
Press the push-button B2 located on the back.
•
Power on the SIG, while keeping the push-button pressed at least 10 s.
The LED turns red; the SIG boots and the factory configuration is restored.
Note: The factory configuration can also be restored via the menu
Maintenance > Configurations
management