INSTALLATION
DOC_DEV_SIG_ User guide_A
Page 19
2
Safety instructions
The product shall be installed in a fire electrical resistant cabinet by a qualified operator.
The product shall be connected only to equipment that complies with the IEC60950-1 or IEC62368-1 standards
and that meets the following classifications:
•
IEC60950-1 : Limited power circuits and SELV type
–
§2.2 and 2.5
•
IEC62368-1 : ES1 & PS2
To avoid any risk of burns, it is strongly recommended to wear gloves to handle the product in
operation when the ambient temperature exceeds 30 °C.
Cellular models:
•
The antenna should be installed and operated with minimum distance of 20 cm between the radiator
and your body.
•
The antenna must not be co-located or operating in conjunction with any other antenna or transmitter.
3
Cooling
The product is designed to be mounted into a server cabinet.
To avoid obstructing the airflow around the unit, the spacing must be at least 25 mm above and below, and 10
mm left and right.
4
Earthing
For safety and EMC reasons, the product must be connected to the protective earth of the installation by its
power cord.