 value indication, if the decimal point on last digit (from left) is flashing, this is because the system working as 

Generator or the sense of current is inverted (verify correct CT connection or modify parameter 

.



). 

b)  Press 

 button to scroll on available measurements indicated by the related LED. 

c)  If a 

k

 is on the value must be multiplied x1000, instead If a 

M

 is on the value must be multiplied x1000000. 

d)  Press 



 both buttons to scroll measure automatically every 3s, press 

 button for stop scroll. 

e)  While viewing one of these measures: 

V

 -

 A

 - 

Cos

 - 

W

 - 

VAr

 - 

VA

 - 

%THDV

 - 

%THDI

 if press 

 button for 1s, all 

displays and shows the average value measured. 

f)  While viewing one of these measures: 

V

 - 

A

 - 

%THDV

 - 

%THDI

 - 

TEMP

 if press 



 both buttons for 1s, flashes 

the relative Led and display shows the maximum value measured. 

g)  While select 

Wh

 measure, the display shows the value for each Phases if 



 set in Three-Phase mode or one Phase if 



 set in Single-Phase mode, press 

 it shows the total 

Wh

 for 5s.  

 

Press 



 both buttons for 15s to reset all 

Wh

 values. 

h)  While select 

VArh

 measure, the display shows the value for each Phases if 



 set in Three-Phase mode or one Phase 

if 



 set in Single-Phase mode, press 

 it shows the total 

VArh

 for 5s. 

 

Press 



 both buttons for 15s to reset all 

VArh 

values. 

i)  Only if 



 set in Three-Phase mode, while select 

V

 measure, the display shows the value 



 for each Phase, press 

 it shows the phase voltages. 

 

Press for more than 5s 

 to switch from 



  to 



 and set this as default measure value and vice versa. 

l)  While select 

TEMP

 measure, the display shows the current working temperature, press and hold 

 it shows the total 

device worked hours. 

 
 

5.1  MEASURE DETAILS: 

MAX VALUE: 

The  data  recording  happens  every  2  seconds,  then  after  32 
seconds,  the  micro  calculates  the  average  of  the  16  different 
recording  and,  if  above  the  stored  max  value,  this  goes  to 
overwrite it and becomes effectively the new max value. 
This  is  to  avoid  that  a  single  abnormal  pike  can  false  the  real 
situation recording an extraordinary and occasional max value. 
For  the  max  Temperature  the  data  is  related  to  the  single 
reading not to the average. 

AVERAGE VALUE: 

The  data  capture  occurs  every  2  seconds,  for  example  if 

.



=10 the average value is calculated on 20 seconds. 

 
After power on, during the first 15 minutes, the recording of the max values is disabled. 

 

 

 

 

6 - TECHNICAL DATA:

 

Supply Circuit 

 

144x144 

9 Modules

 

Measuring Type: 

 

True RMS 

 Cos

 (L/L)

0.00 to 1.00  ±1% 

 Voltage (N/Lx) 

VA

 

100 to 280  ±1% 

 Voltage (L/L) 

VA

 

180 to 490  ±1% 

 Current (CT) 

0.05 to 5.5  ±0.5% 

 Active Power (Lx) 

Class 1 

 

 Reactive Power (Lx) 

VAr 

Class 1 

 

 Apparent Power (Lx) 

VA 

Class 1 

 

 THD of Volt or Current 

0 to 255 

 Work Hours 

0 to 9999 (with multiplier) 

 Ambient Temperature 

°C 

0/+60°C (or °F) 

Summary of Contents for 004656578

Page 1: ...Ds 2 2 ELECTRICAL DIAGRAM FOR INSTALLATION 2 3 SET UP MENU 3 4 ENTER THE ALARMS MENU 5 5 MEASUREMENTS FUNCTIONS 6 6 TECHNICAL DATA 7 7 TERMINAL CONNECTIONS 8 8 DIMENSIONS 9 REGISTERS MODBUS RTU TABLE...

Page 2: ...RMS A Current Hz Frequency Cos Cos W True Power VAr Volt Amp Reactive VA Volt Amp Apparent V THD Total Harmonic Distortion Voltage A THD Total Harmonic Distortion Current Wh Watt hours VArh Volt Amp...

Page 3: ...The installer has to provide an external disconnection device this breaker has to be easily reachable and identified as disconnection device Without transformer 1 For higher supply voltage than the su...

Page 4: ...er Reading Interval 60s 360s 90s 2 Average time filter Value 1 20 4 1 Parameter adjusts the time window width for the integration of current and power maximum demand 2 Parameter allows to modify the s...

Page 5: ...bus 19200 Bds NONE 1 Bit Stop 12 Modbus 9600 Bds NONE 1 Bit Stop 13 Modbus 4800 Bds NONE 1 Bit Stop 14 Modbus 2400 Bds NONE 1 Bit Stop 15 Modbus 1200 Bds NONE 1 Bit Stop 16 Proprietary 9600 Bds NONE 1...

Page 6: ...disable 1 2 3 1 0 ALL 0 1 L1 2 L2 3 L3 Over Temperature 0 disable 30 60 60 1 240 10 Min Sec Sec 0 disable 1 2 3 1 THD I 0 disable 5 200 120 1 240 10 Min Sec Sec 0 disable 1 2 3 1 Low Cos 0 disable 0...

Page 7: ...s Press both buttons for 15s to reset all VArh values i Only if set in Three Phase mode while select V measure the display shows the value for each Phase press it shows the phase voltages Press for mo...

Page 8: ...ry Rated Voltage VDE0110 C 250 B 400 Maximum Switching Voltage 250V Electrical Contact Life 20 x 100 6 ops Mechanical Contact Life 100 x 10 3 ops Enclosure and Connections Cable Type for connection On...

Page 9: ...IMENSIONS 144x144 MODEL FRONT VIEW SIDE VIEW PANEL HOLE 9 MODULE MODEL FRONT VIEW SIDE VIEW CLEANING OF THE UNIT If necessary clean the device with a soft cloth dampened with water This operation must...

Reviews: