background image

11. Maintenance

Eternity Technologies OPzV are sealed-maintenance free lead-acid 
batteries and need no water addition. 

Cleanliness

The containers and lids must be kept dry and free from dust.
Cleaning must be done only with a damp cotton cloth.
Avoid static discharges generated during cleaning.

Voltages

Individual cell voltages will vary greatly when the cells are first put 
into operation. This is expected and variation will start to decrease 
within the first 12 months. Monitor these as per below. If there isn’t 
any significant change in the voltages after 12 months, an additional 
equalisation charge should be performed. 

Please see graph below for expected voltage variation vs time.

Every 6 months

:

- Check for evidence of damage on the battery and equipment.
- Check and record the total battery float voltage, the voltage on pilot 
cells* and temperature.
 

Once a year:

- Check and record individual cell voltages.
- Perform a discharge test according to IEC 60896-21 standard until 
the battery shows signs of degradation and then every six months 
thereafter.

Keep a log book to record all maintenance and inspection operations, 
which will be helpful to monitor long-term changes of the battery 
condition.

Do not attempt to open the safety valve. Opening could cause 
damage to the battery.

*Pilot Cell

For regular monitoring of the battery condition, select one cell near 
the middle of the battery string as a “pilot” cell (for battery consisting 
of more than 60 cells, it is advisable to select one pilot cell out of 60).

Additional Information 

For any further information on Eternity OPzV VRLA Standby & Solar 
batteries, please contact:

Eternity Technologies FZ-LLC

Al Hamra / Al Jazeera
PO Box 35102
Ras Al Khaimah
U.A.E

Phone

 + 971 72 433 535

Fax

 + 971 72 433 536

Web

 www.eternitytechnologies.com

Summary of Contents for OPzV Series

Page 1: ...dby Solar Batteries are designed to be used as back up power to support users that need reliable service continuity in case of power blackouts and outages of the electricity distribution network They can also be used in off grid and hybrid installations Installation Operation and Maintenance Solar Batteries ET IOM005 0520 ...

Page 2: ...nel Observe the following precautions at all times Observe the operating instructions work on the battery should be carried out by qualified personnel only Exposed metal parts of the battery carry a voltage and are electrically live with the risk of short circuits Avoid any electrostatic charge before starting work on the battery first discharge any possible electricity from yourself by touching a...

Page 3: ... and performance 3 Delivery Unpacking and storage Unpack the batteries as soon as they are delivered Verify that the equipment has been delivered in good condition Any damage must be reported immediately to the carrier and the damaged items retained for inspection by the carrier s representative The details on the label should be read carefully and the following points to be observed Cell Type Cel...

Page 4: ...ernity Technologies When storing horizontally ensure that the internal plates are vertical to check this is the correct the positive and negative terminals should be above or below each other ie not on the same level as per the diagram below 5 Charging a Commissioning Charge Batteries lose charge while in transit or during storage For this reason a refresh charge should be given before putting the...

Page 5: ...age value requires a thermal compensation of 3 5mV cell C for temperature increases For temperature decreases in the cell the voltage should be increased by 3 5mV Cell C See graph below Failure to change these values will lead to capacity problems and reduction in operational life c Equalizing Boost charge 2 35 2 4V Chargers usually have two adjustable charging voltages one for the floating charge...

Page 6: ...ifferent number of cycles 9 Hybrid Applications Eternity Technologies Solar OPzV batteries can be used in a hybrid system alongside a diesel generator where the batteries are used to decrease the run time of the generator Charging is critical in this application and the user must ensure that the charging time is sufficient to fully charge the battery between cycles Failure to do this will result i...

Page 7: ...l battery float voltage the voltage on pilot cells and temperature Once a year Check and record individual cell voltages Perform a discharge test according to IEC 60896 21 standard until the battery shows signs of degradation and then every six months thereafter Keep a log book to record all maintenance and inspection operations which will be helpful to monitor long term changes of the battery con...

Page 8: ...tytechnologies com The Eternity Technologies range is built using only the highest quality and most efficient production processes at our state of the art manufacturing centre in the UAE It is this innovation modern design criteria and industry leading machinery that allows Eternity Technologies to not only meet the needs of the global industrial market with increased reliability but define it for...

Reviews: