Temperature effect on cycle life

Eternity Technologies recommends that the operating temperature 
range for OPzV batteries be within the region of +10°C to + 30°C. 
Operating in higher temperatures will lead to decreased operational 
life, operating in lower temperatures will lead to a reduction in 
available capacity. 

Air flow for cooling

 When batteries are cycled, they generate heat. Eternity Technologies 
recommend a minimum gap of at least 10.0mm between cells to 
allow for the heat to disperse from around the cells. Where natural 
cooling is not enough to keep the temperature of the battery to a 
recommended level, a cooling system may be required. We can work 
out the size of the required cooling by calculation, please see below:

A 48V battery is discharged twice daily, delivering 3 hours back-up 
and 3kW of power

Heat loss from the battery = 2 (2 discharges/day) x 3kW x 3 hours x 
0.15 (15%) = 2.7kWh = 2700Wh per day.

If we calculate the cooling power required to keep the room at a 
consistent temperature then we take 2700Wh and divide by 24 hours 
= 112.5W

Air exchange to exhaust Hydrogen
Due to the chemistries involved within Eternity Technologies OPzV 
battery range, hydrogen evolution and emittance is unavoidable. 
Although the levels are minimal, if they are allowed to accumulate 
or there is a fault within the system and hydrogen gas increases 
to a dangerous level, there is a risk of explosion if a spark or flame 
becomes present.

8. Cycle Life

Please see the graph below showing our maximum number of cycles 
vs the depth of discharge. There are two lines on the graph. One 
line states the charging profile with IU charging profile. The other 
line shows the cycle life with an IUI charging profile. The graph is 
referenced to 20°C, operating at temperatures either side of this 
figure will result in a different number of cycles. 

9. Hybrid Applications

Eternity Technologies Solar OPzV batteries can be used in a hybrid 
system alongside a diesel generator where the batteries are used 
to decrease the run time of the generator. Charging is critical in 
this application and the user must ensure that the charging time is 
sufficient to fully charge the battery between cycles. Failure to do this 
will result in reduced cycle life.

The charging criteria must comply with the figures set out in section 5 
of this document. 

10. Solar Applications

Batteries used without a generator and no mains power are classified 
as solar batteries. The important thing here is to limit the charge and 
discharge currents.

When there is an abundance of sunlight, it is necessary to limit the 
charge and not overcharge the battery. When there are times of 
continuous darkness, it is important not to discharge the battery too 
much. Please use the end of discharge voltage recommendations in 
this brochure for guidance.

Failure to comply with this will result in reduced capacity and cycle life.

It is recommended to perform a boost charge every 1-3 months in 
solar applications. 

In order to avoid a build-up of hydrogen to dangerous levels, the 
battery room or area needs to be ventilated. We can calculate the 
required ventilation based on the number of cells and their capacity. 
Eternity Technologies recommends the international standard for the 
safety stationary batteries, IEC 62485-2 be consulted.

7. Temperature and Air flow

Temperature effect on float life

Increased temperatures have a great effect on the life of a battery. 
When the battery is operated at increased temperatures, the 
corrosion of the positive terminal is accelerated which leads to early 
failure. When operated at 20°C, Eternity technologies OPzV range of 
batteries will last for 20 years. For every 10°C increase in the average 
operating temperature, the battery’s life is halved.

The graph below shows the effect of temperature on the float life of 
the battery.

Summary of Contents for OPzV Series

Page 1: ...dby Solar Batteries are designed to be used as back up power to support users that need reliable service continuity in case of power blackouts and outages of the electricity distribution network They can also be used in off grid and hybrid installations Installation Operation and Maintenance Solar Batteries ET IOM005 0520 ...

Page 2: ...nel Observe the following precautions at all times Observe the operating instructions work on the battery should be carried out by qualified personnel only Exposed metal parts of the battery carry a voltage and are electrically live with the risk of short circuits Avoid any electrostatic charge before starting work on the battery first discharge any possible electricity from yourself by touching a...

Page 3: ... and performance 3 Delivery Unpacking and storage Unpack the batteries as soon as they are delivered Verify that the equipment has been delivered in good condition Any damage must be reported immediately to the carrier and the damaged items retained for inspection by the carrier s representative The details on the label should be read carefully and the following points to be observed Cell Type Cel...

Page 4: ...ernity Technologies When storing horizontally ensure that the internal plates are vertical to check this is the correct the positive and negative terminals should be above or below each other ie not on the same level as per the diagram below 5 Charging a Commissioning Charge Batteries lose charge while in transit or during storage For this reason a refresh charge should be given before putting the...

Page 5: ...age value requires a thermal compensation of 3 5mV cell C for temperature increases For temperature decreases in the cell the voltage should be increased by 3 5mV Cell C See graph below Failure to change these values will lead to capacity problems and reduction in operational life c Equalizing Boost charge 2 35 2 4V Chargers usually have two adjustable charging voltages one for the floating charge...

Page 6: ...ifferent number of cycles 9 Hybrid Applications Eternity Technologies Solar OPzV batteries can be used in a hybrid system alongside a diesel generator where the batteries are used to decrease the run time of the generator Charging is critical in this application and the user must ensure that the charging time is sufficient to fully charge the battery between cycles Failure to do this will result i...

Page 7: ...l battery float voltage the voltage on pilot cells and temperature Once a year Check and record individual cell voltages Perform a discharge test according to IEC 60896 21 standard until the battery shows signs of degradation and then every six months thereafter Keep a log book to record all maintenance and inspection operations which will be helpful to monitor long term changes of the battery con...

Page 8: ...tytechnologies com The Eternity Technologies range is built using only the highest quality and most efficient production processes at our state of the art manufacturing centre in the UAE It is this innovation modern design criteria and industry leading machinery that allows Eternity Technologies to not only meet the needs of the global industrial market with increased reliability but define it for...

Reviews: