Echoflex Installation Guide
Phase Adaptive Dimmer
Phase Adaptive Dimmer (ER6CD/ER12CD)
Page 5 of 12
Echoflex
Learn Button
The
[Learn]
button initiates Link mode for linking compatible Echoflex
devices to the controller. See the relevant switch or sensor documentation
for information on linking. Link mode times out after 30 seconds of
inactivity.
Devices can be linked to a controller during the Echoflex pre-commissioning
process, or linked manually. Repeating the linking process for a device that
is already linked to a controller will unlink it from that controller.
Clear Button
The
[Clear]
button resets the controller either to its pre-commissioned state
or to its factory default state.
To reset to pre-commissioned state:
1. Press the
[Clear]
button until the red Power and green Learn LEDs are
both solid ON.
2. Release the
[Clear]
button. The red Power LED blink code indicates the
type and count of devices linked at pre-commissioning.
To reset to factory default state:
1. Press and hold the
[Clear]
button until the red Power and green Learn
LEDs start blinking (about 15 seconds).
2. Release the
[Clear]
button. The Power LED displays solid red to indicate
factory default state. All links are removed.
Test the Controller
Echoflex provides the controller in either a pre-commissioned state or a
factory default state.
• Pre-commissioned devices are linked, configured, and labeled
according to customer specifications. When powered up, the red
Power LED repeats a blink code to indicate the type and number of
devices currently linked to the controller. See
. To test the dimmer, press the
[Learn]
button
or use a linked switch.
• In factory default state, when powered up, the Power LED displays
solid red to indicate the controller has no linked devices. To test the
dimmer, press the
[Learn]
button or link a switch. See the relevant
switch documentation.
A maximum of 20 switches or sensors can be linked to one controller.