background image

ETC Installation Guide

Echo-Echoflex Interface

Echo-Echoflex Interface

Page 9 of 15

ETC

Manual Control of Wireless Outputs

When a wireless output is selected, the Manual Control [ON] and [OFF] buttons allow manual level control 
of the selected wireless output and its linked Echoflex devices.

Manual control of wireless outputs simulate the event action only on the linked Echoflex control system, 
and only for the zone that is associated with the selected wireless output and the linked Echoflex wireless 
device(s).

For example:

If wireless output 1 is selected, pressing the [ON] button will set the levels for all of the Echoflex power 
controllers that are linked to Echoflex Output 1 to 100%.

Manual control events for the selected wireless outputs will not be shared to the Unison Echo control 
system.

Push

Press and release the button.
- On - sets the selected output to 100% using a two second fade time.
- Off – sets the selected output to 0% using a two second fade time

Hold

Press and hold the button.
- Hold On – selected output level raise
- Hold Off – selected output level lower

Double-tap

Double-tap On and Off events perform the same action as the “Push” action for the linked output, 
except the event will execute in a 500 ms time frame.
- Double-tap On – sets the selected output to 100%, executed in a 500 ms fade time.
- Double-tap Off – sets the selected output to 0%, executed in a 500 ms fade time.

Configuration

Linking Echoflex Devices to Wireless Inputs and Outputs

With a wireless input or output selected, and the EEI in Learn/Teach Mode, the selected wireless input or 
output LED lights and the OUTPUT STATUS LEDs indicate the number of Echoflex controls that are linked 
to the selected input or output.

A selected wireless input or output that is not associated with (linked) Echoflex controls will not display 
indication on the Output Status LED's.

To link an Echoflex device to an EEI wireless input, you must have access to the EEI to place the unit in Learn 
mode and access to the Echoflex device to place it into Teach mode.

Follow these instructions to link an Echoflex device to the EEI wireless input.

1:

Select the wireless input. Press the [SELECT] button to cycle through the available wireless inputs and 
outputs, until the desired input is selected. The selected input LED will indicate in amber. If the input 
already has a linked device, the INPUT STATUS LED will indicate. Reference 

Input Status

 on 

page 5

 

for LED indication details.

2:

Press the [LEARN/TEACH] button. The LEARN/TEACH LED will blink alternating red and green to 
indicate it is in Learn mode. Learn mode will expire after 30 seconds of inactivity, if no Teach 
messages are received from Echoflex devices or interaction with the [SELECT] button is made.

Summary of Contents for Echo-Echoflex Interface

Page 1: ...llation of an external antenna Contact ETC for ordering details Specification For use with ETC dimming and relay products 902 MHz radio products only Ambient Environment For indoor use only Supports plenum rating Operating temperature 0 50 C 5 95 non condensing humidity Electrical Specification The EEI requires 24 Vdc Class 2 power supplied by an external 24 Vdc power supply Termination for this c...

Page 2: ...that the total combined length of an EchoConnect data run using Belden 8471 or equivalent must not exceed 1 640 feet 500 m This requirement should be considered when determining the location of the Echo Echoflex Interface for installation Range Planning Guidelines for Wireless When an event is triggered by a button station or sensor a wireless message is sent between the EEI and the linked Echofle...

Page 3: ...al 3 identified with a symbol insert the data wire black is typical into terminal 2 identified with a symbol and insert the ground wire green yellow is typical into terminal 1 identified with a ground symbol 4 Secure the screws firmly onto each wire Connect 24 Vdc An external 24 Vdc Class 2 power supply is required to power the EEI Terminate to the interface terminals labeled 24 Vdc Terminals acce...

Page 4: ...control Unison Echo Control System The interface participates in a Unison Echo control system using the configured Unison Echo Space selected using the rotary switch on the front of the unit Control of presets and zones are shared over EchoConnect with other connected Unison Echo devices By default Wireless Inputs 1 through 4 are configured to control Echo Presets 1 through 4 and Wireless Outputs ...

Page 5: ... to be snapshot recorded See Record on page 10 LEDs Input Status The INPUT STATUS LED displays the state of the currently selected wireless input When an Echoflex device is linked to the Echoflex Input and the Echoflex Input is selected the LED reflects the current control status of the linked device Generally speaking lights on events are shown with a green LED lights off events are shown with a ...

Page 6: ...ndicate the current output level is 50 10 green LED s indicate the current output level is 100 System Wireless Inputs The four wireless inputs on the EEI convert Echoflex control inputs into Unison Echo control system actions Linking of Echoflex controls such as stations and sensors allows control of Echo presets Wireless inputs can be configured to recall a specific preset which is configured usi...

Page 7: ...n to both the Wave and Decorator Style switches Push Press and release the button On Preset activation Off Space Off Hold Press and hold the button Hold On Space raise Hold Off Space lower Double tap Double tap On and Off events perform the same action as the Push action for the linked Echoflex device type except the event will execute in a 500 ms time frame Double tap On Preset activation execute...

Page 8: ...action Off Space Off and Station Lockout for the removed card action Double tap Double tap On and Off events perform the same action as the Push action for the linked Echoflex device type except the event will execute in a 500 ms time frame Double tap On Preset activation and Station Unlock for the inserted card action executed in a 500 ms fade time Double tap Off Space Off and Station Lockout for...

Page 9: ...lected output to 100 executed in a 500 ms fade time Double tap Off sets the selected output to 0 executed in a 500 ms fade time Configuration Linking Echoflex Devices to Wireless Inputs and Outputs With a wireless input or output selected and the EEI in Learn Teach Mode the selected wireless input or output LED lights and the OUTPUT STATUS LEDs indicate the number of Echoflex controls that are lin...

Page 10: ...a red LED for four seconds If nothing has been linked unlinked the EEI Output LED shall remain off Press the LEARN TEACH button again to exit Learn mode or press the SELECT button to cycle through the inputs and outputs Clearing the Linked Devices from Wireless Inputs and Outputs To clear all Echoflex devices from the selected Echoflex input or output on the EEI press and hold the CLEAR button for...

Page 11: ...set actions By factory default the four Echoflex Inputs are configured to Preset 1 through Preset 4 respectively Presets 1 16 may be individually assigned to the wireless inputs Configure Preset 1 Place the EEI in Program Mode 2 Press the SELECT button until the wireless input to be configured is selected The current preset number configured to the selection displays on the OUTPUT STATUS LED s 3 P...

Page 12: ...ditional Zone number will indicate additively in a cycle First all LED s will indicate 10 then the remaining LED s will indicate up to 6 followed by a long pause Configure Zone 1 Place the EEI in Program Mode 2 Press the SELECT button until the wireless output to be configured is selected The current zone number configured to the selection displays on the OUTPUT STATUS LED s 3 Press the ON button ...

Page 13: ...e ON and OFF buttons for five seconds until the Echo input status LED starts blinking RED 3 Tap the OFF button until the input status LED blinks the either red green or amber according to the setting you will edit The output status LED indicates the current setting 4 Tap the ON button to edit the current setting displayed on the output status bar 5 Press and hold the ON and OFF buttons for five se...

Page 14: ...defaults to the Echo Echoflex Interface follow these instructions 1 Set the Space rotary dial to 16 2 Hold the RECORD PROGRAM and CLEAR buttons for 10 seconds Remove the Interface from DIN If for any reason you need to remove the Echo Echoflex Interface from the DIN rail follow these instructions 1 Disconnect all wiring 2 Insert a flat head screwdriver into the clip on top of the interface slide i...

Page 15: ...ater functionality one tap Repeater disabled two taps Repeater 1 hop three taps Repeater 2 hops The Learn Teach LED will blink the number of times to confirm To send a manufacturer specific message press and hold the LEARN TEACH button while tapping the CLEAR button two times This will send the radio ID of the EEI in order to configure it with remote management tools The learn teach LED will blink...