ETC Installation Guide
D1 & D2 Series Drivers
D1 & D2 Series Drivers
Page 12 of 25
ETC
Electrical and Wiring Specifications
Install the driver on a power distribution system with reliably identified earthed neutral (ground) and
install a maximum 20 A circuit breaker on the line conductor. The D1and D2 Series drivers accept
100–277 VAC, 50/60 Hz. ETC recommends installing all wiring in grounded metal conduit.
WARNING:
Circuits that are installed without an accessible power disconnect
device cannot be serviced or operated safely.
AVERTISSEMENT :
Il est imprudent d'utiliser ou de réparer les circuits
installés sans qu'un dispositif de déconnexion de l'alimentation ne soit
accessible.
Wire and Terminal Specifications
Terminal/Connector
Conduit
Entry
Wire Range/Specifications
Strip
Length
Torque Rating
D1 power input
line/neutral/ground
½ in
conduit
Up to 6 mm
2
(10 AWG) solid or stranded
7 mm
(1/4 in)
0.8 Nm
(7 in-lb)
D1 HOand D2 power input
line/neutral
½ in
conduit
0.5–10 mm
2
(22–6 AWG)
7 mm
(1/4 in)
0.5 Nm
(4.4 in-lb)
D1 HO and D2 Power Input
ground
½ in
conduit
2.5–10 mm
2
(6–14 AWG)
10 mm
(3/8 in)
4.0 Nm
(35 in-lb)
DMX In/Thru
RJ45 Connectors
½ in
conduit
Cat5e (or better) minimum 0.2 mm
2
(24 AWG) conductors terminated to
T568B standard
N/A
N/A
D1 and D2 Series Drivers with
Molex connectors
½ in
conduit
Follow Class 2 wiring methods.
Note:
Maximum supported wire length between One-Cell luminaires and D1 Series and
D2 Series drivers is 15 m (49 ft, 3 in). Maximum supported wire length between a One-Cell
High Output luminaire and a D1 HO Series driver is 1 m (3 ft, 3 in).