Wall-Mount Driver Installation
15
Chapter 3
Wall-Mount Driver Installation
This chapter provides instructions for installing the standard wall-mount models of ArcLamp
driver. Instructions for standard rack-mount or emergency wall-mount and emergency rack-
mount drivers are in these chapters:
•
Rack-Mount Driver Installation on page 25
•
Wall-Mount Emergency Drivers on page 48
Electrical and Wiring Specification
WARNING:
Circuits that are installed without an accessible power
disconnect device cannot be serviced or operated safely.
AVERTISSEMENT :
Il est imprudent d'utiliser ou de réparer les circuits
installés sans qu'un dispositif de déconnexion de l'alimentation ne soit
accessible.
Install the ArcLamp Driver on a power distribution system with reliably identified earthed neutral
and install a maximum 15 A circuit breaker on the line conductor.
ETC recommends installing all wiring to and from wall-mount drivers in grounded metal conduit.
The wall-mount ArcLamp Driver accepts 100–277 VAC (150 models) or 100–240 VAC (350 and
700 models), 50/60 Hz. Emergency models only: requires normal sense and maintained
(emergency) input power.