Selects the opening cycle of the purge SV.
SV PURGE MENU
Enables or disables the Flow sensor function (proximity probe). The
flow
Flow Sensor
sensor is useful in the event of water lack in the probe socket; the proximity
Enabled
probe disables all outputs ensuring no chemical substance is added
.
Overwrites the previous SV programming (timer or conductivity), selecting the maximum SV opening time and
manual start-up (next step). It is a safety measure in the case where the operator opens the SV via the Max
manual programming and forgets to close it.
SV PURGE MENU
Supersedes the previous Max Manual Time programming and SV
Manual Start-up
programming (timer or conductivity). The operator manually selects when
ON
the SV is ON / OFF. "Manual ON / OFF start-up" only works if the previous
function" Max Manual Time" has been programmed.
Press
to go back to
or press
MEASUREMENT DISPLAY
PURGE operations by means of CONDUCTIVITY measurement
Processes the conductivity level to control purge operations; the displays show the measured EC values and
drive the relay output connected to the SV solenoid valve.
SV PURGE MENU
The setpoints activate the output relay for the solenoid valve or other
Low Setpoint
devices once the setpoint level is selected. The display shows the value in
0 µ S
μS but if the value exceeds 1999 μS, it shows 2.00 mS (if the value
decreases the reading goes back in μS).
Selects the maximum opening time of the purge SV.
SV PURGE MENU
The MIN Alarm function selects a MINIMUM alarm level
MIN Alarm
after which the alarm relay is triggered on.
0 µ S*
The MAX Alarm function selects a MAXIMUM alarm level
beyond which the alarm relay is triggered on.
SV PURGE MENU
Cycle duration
000 : 00 ( m: s)
SV PURGE MENU
Flow Sensor
Disabled
SV PURGE MENU
Max Manual Time
000. 00 ( m: s)
SV PURGE MENU
Manual Start-up
OFF
Menu Selection
SV PURGE
SV PURGE MENU
Mode Selection
Conductivity
SV PURGE MENU
High Setpoint
0 µ S
SV PURGE MENU
Max SV time
000 : 00 ( m: s)
SV PURGE MENU
MAX Alarm
0 µ S*
M E N U S E L E C T I O N
ESC
ESC
ESC
to go b a c k
to