54
www.eta.co.at
[Heating circuit] function block
ETAtouch controller
Check operating mode and target room
temperature on the ETA room sensor
•
If a room is too cold, check the room sensor, or in
the control system set the operating mode and the
desired room temperature. It is possible that the
heating circuit has been switched off or the room
temperature is set too low.
Fig. 5-50: ETA room sensor
•
Check the settings of the following parameters in
the text menu of the heating circuits:
–[Room effect], see chapter
–[Switch-on diff. room] and [Switch-off diff.
room] see chapter
room and Switch-off diff. room"
•
If during heating mode the rooms are constantly
too cold (within the set heating times), the heating
curve must be adjusted. See chapter
"Adjust heating curve (at outdoor temperatures
above freezing)"
If the rooms are too cold in reduced-temperature
mode (outside the heating times), only the [Set-
back difference] parameter needs to be adjusted.
See chapter
Fig. 5-53: "Adjust reduced operation
Check the heating time settings
•
Check the heating time settings in the control
system, see chapter
5.6.2 "Setting the heating time
.
For
heating systems with buffer storage
, often
heating times that are too short are the reason for
insufficiently warm rooms. Short heating times
(less than 5 hours continuous heating) are particu-
larly ill-advised for underfloor heating because
such systems react very slowly.
Optimal operation is enabled with low feed tem-
peratures (=[Flow at +10 °C] and [Flow at -10 °C])
for the heating curve and long continuous heating
times (10-14 hours). Thus, the heat is transferred
evenly throughout the room. Therefore, it is
advisable (in heating systems with a buffer) to first
set a longer heating time and wait a few days. If the
rooms are then still too cold, the heating curve
must be adjusted. See chapter
.
If
no buffer storage tank
is available,
several short heating times must be set with
pauses in between. This increases the heat
absorbed by the heating circuit from the boiler in
the short heating times. Through this heating time
interruption, the screed becomes a "buffer" in case
of underfloor heating. Between the heating times,
the screed cools and then absorbs heat again. In a
well-insulated building, observe the following
guidelines:
–Radiator heating: several intervals with
3 hours of heating and 2 hours break
–Underfloor heating: several intervals with
4 hours of heating and 3 hours break
The optimum settings depend on the heat demand
of the building and each room. Explore this in con-
sultation with your heating contractor or ETA
customer service.
Summary of Contents for PelletsCompact33-50 kW
Page 1: ...2017 04 19 EN 0000000285 V 003 3 38 0 2703 93120 002 PelletsCompact 33 50 kW Operation...
Page 27: ...ETAtouch controller Getting to know the control system 27...
Page 31: ...ETAtouch controller Boiler function block PelletsCompact 33 50 kW 31...
Page 41: ...ETAtouch controller Buffer function block 41...
Page 45: ...ETAtouch controller Hot water tank function block 45...
Page 49: ...ETAtouch controller Fresh water module function block 49...
Page 63: ...ETAtouch controller Solar function block 63...
Page 67: ...ETAtouch controller Pellet store function block 67...
Page 74: ...www eta co at...
Page 75: ......
Page 76: ...www eta co at www eta co at downloads DOWNLOAD...