www.eta.co.at
Safety devices
Safety
is reached, the power supply to the draught fan and the
fuel intake is interrupted. If the boiler temperature
decreases below 70°C again, the safety temperature
limiter can be manually released for a restart of the
boiler.
Safety valve against overpressure
A safety valve with 3 bar opening pressure has already
been installed on the boiler at the factory. If solar or
other heat sources provide energy to the buffer
storage tank via a heat exchanger, a safety valve
(3 bar maximum) is also required on the buffer storage
tank.
Fig. 3-3: Safety valve
Normally an expansion tank that is too small or
defective, or blocked heating lines, are the cause for
activation of the safety valve. The safety valve should
be
installed at the highest point of the heat producer or i
n the flow pipe close to the heat producer.
DANGER!
Safety valve outlet
The safety valve outlet must be directed to the ground
in a pipe so nobody is endangered by hot water or
steam.
The safety valve outlet must be directed to the
sewer via a clearly visible, open route (siphon
funnel), so that malfunctions, especially a failure of
the safety valve to close, can be detected. If no
sewer connection is available, the outlet must be
directed to the ground in a pipe.
Summary of Contents for PelletsCompact33-50 kW
Page 1: ...2017 04 19 EN 0000000285 V 003 3 38 0 2703 93120 002 PelletsCompact 33 50 kW Operation...
Page 27: ...ETAtouch controller Getting to know the control system 27...
Page 31: ...ETAtouch controller Boiler function block PelletsCompact 33 50 kW 31...
Page 41: ...ETAtouch controller Buffer function block 41...
Page 45: ...ETAtouch controller Hot water tank function block 45...
Page 49: ...ETAtouch controller Fresh water module function block 49...
Page 63: ...ETAtouch controller Solar function block 63...
Page 67: ...ETAtouch controller Pellet store function block 67...
Page 74: ...www eta co at...
Page 75: ......
Page 76: ...www eta co at www eta co at downloads DOWNLOAD...