18
8.2.3 Cyclical output data of circuit protectors
Each channel can be switched on or off or reset via the cyclical output data. A subindex (1 to 32) is reserved per channel in register
0x7000. The subindex again represents the channel number.
Design of the output bytes per circuit protector is as follows:
byte
type
range
description
Control
channel 1
0
byte
0 ... 255
bit 0 = load output ON/OFF
bit 1 = reset load output (only responds to rising edge 0 -> 1)
bit 2 = reserve
bit 3 = reserve
bit 4 = reserve
bit 5 = reserve
bit 6 = reserve
bit 7 = reserve
»True« means the status is active.
Control
channel 2
1
byte
0 ... 255
bit 0 = load output ON/OFF
bit 1 = reset load output (only responds to rising edge 0 -> 1)
bit 2 = reserve
bit 3 = reserve
bit 4 = reserve
bit 5 = reserve
bit 6 = reserve
bit 7 = reserve
»True« means the status is active.
fig. 11: Output data circuit protector