 General:

 ControlPlex

®

 

Rack, E/A  external alarm interface EAI300

The EAI300 has particularly been designed for use with the 

Power-D-Box

®

 type PDB-N-CP in connection 

with the remote control interface RCI10. It can be installed and de-installed in the 

Power-D-Box

®

 later with 

the system live without having to disconnect the application from the mains. The EAI300 only requires a free 
ESX300 slot (slot for circuit protectors) in the 

Power-D-Box

®

7.1 

Operating mode and application EAI300

The EAI300 has been conceived for connection and free text indication of alarm messages from “external” 
alarm contacts and sensors in the plant room by means of a control computer. This could include door  
contacts, temperature sensors or alarm contacts of the air conditioning system. The EAI300 interface  
communicates with the RCI10 Remote Control Interface installed in the 

Power-D-Box

®

 via an internal bus. 

The RCI10 sub-assembly communicates with a management system or a control computer by means of an 
Ethernet interface. With the help of an integral LED an “external” alarm can also be indicated locally on the 
EAI300. An integral 24V voltage output can be used directly for reading the alarm contacts. Equally, there are 
two potential-free outputs available for activating e.g. a door lock or for realising an additional group signalling 
of the ESX300 circuit protectors. Within a 

Power-D-Box

®

 you can install up to 20 EAI300 sub-assemblies.

7.2 

Technical data of EAI300

Interface card for forwarding additional alarms in the engineering room, so-called “external alarms”. 

Technical data of EAI300

Operating voltage

DC 20 V … DC 75 V

Dielectric strength

DC 100 V for 1 ms

Power consumption

Typically 1.9 W

Internal interfaces

EL-Bus

®

 and supply via blade terminals

External connection

Two plug-in type 8-pole connection sleeves with 
spring-loaded connectors on the front side Cross-section 
0.14 mm² … 1.5 mm²

Number of digital inputs:

Eight physically isolated inputs

Current consumption

1 mA at 24 V

Input resistance:

22.1 kOhm

Voltage potential “HIGH” level

DC 12 V … DC 72 V

Voltage potential “LOW” level

DC 0 V … DC 4 V

Number of analog inputs:

One physically isolated input

Measuring input

4 mA … 20 mA

Number of digital outputs (relay outputs)

Two physically isolated relay outputs (break contacts)

Max. load current of contact

2 A

Voltage range – contact

DC 12 V … DC 72 V

Internal supply voltage for I/O connection

Typically DC 24 V 
(at Power-D-Box supply voltage ≥ DC 30 V)

Max. load current:

100 mA

Summary of Contents for Control Plex

Page 1: ...Rack Installation Instruction...

Page 2: ...be reproduced or distributed without prior written consent of E T A GmbH Any person acting illegally with regard to this publication can be prosecuted Limitation of liability Although all provisions w...

Page 3: ...Here you will find an instruction for configuration and for integration of the module Remote Control Interface RCI10 into your network In addition this document holds a user description of the web bro...

Page 4: ...on cabling for Power D Box 18 3 8 3 Mounting and start up of Power D Box 19 4 General ControlPlex Rack electronic circuit protector ESX300 S 21 4 1 Application ESX300 S 21 4 2 Technical data of the P...

Page 5: ...ure of slot for RCI10 or RSI10 35 6 5 2 Picture of an example for network connection 35 6 6 Configuration and start up RCI10 35 7 General ControlPlex Rack E A external alarm interface EAI300 36 7 1 Op...

Page 6: ...s of the product or the system E T A does not accept any liability for problems caused by improper installation or handling by the customer or a third person Symbols You will find the following symbol...

Page 7: ...7...

Page 8: ...its system properties the ControlPlex Rack is the perfect solution for smart protection control and energy measurement for DC supplied minus switching system cabinets Typical applications include Sys...

Page 9: ...lation the system has to be disconnected from the mains A cable connection must only be established if the supply voltage is OFF Danger Possible ignition hazard The device must NOT be used in inflamma...

Page 10: ...n designed for the quick and easy installation into 19 or ETSI racks which is ensured by a rotating mounting flange Depending on the required termination technology front or rear the corresponding Pow...

Page 11: ...als 16 50 mm AWG 5 AWG 1 16 50 mm AWG 5 AWG 1 4 25 mm AWG 11 AWG 3 16 50 mm AWG 5 AWG 1 16 50 mm AWG 5 AWG 1 Tightening torque 6 8 Nm 6 8 Nm 4 4 5 Nm 6 8 Nm 6 8 Nm Loads PDB N CP09A RR A PDB N CP09A R...

Page 12: ...D for load terminal on the front part no X223 189 01 marking frame with labels 0 5U for customised marking of circuit protectors part no X22357501 marking frame with labels 1U with cable gland on the...

Page 13: ...HE fig 4 front view PDB N CP09A FF Ax 1 x 9 slots terminals on the front with high current SUB D connectors fig 5 rear view PDB N CP09A FF Ax 1 x 9 slots with rear cable grip rail 482 6 88 9 fig 6 fro...

Page 14: ...TS 88 9 2HE fig 8 front view PDB N CP18R RR Ax 2 x 9 slots fig 9 front view PDB N CP18R RR Ax 2 x 9 slots 450 171 5 160 14 201 5 271 5 cable grip set optional cable guide supply fig 10 top view PDB N...

Page 15: ...S E T A ESX300 S E T A ESX300 S E T A ESX300 S E T A ESX300 S E T A ESX300 S E T A ESX300 S E T A fig 11 Schematic diagram PDB N CP19A RR Ax 1 x 19 slots with signalling ESX300 S E T A RCI RSI A7 A4...

Page 16: ...tion max 50 mm loads B B loads A A plus 48 V DC B minus 48 V DC A minus 48 V DC B plus 48 V DC A fig 13 version PDB N CP18R RR A pin assignment cable grip removed Pin assignment PDB N CP09A FF Ax Fron...

Page 17: ...60 V max 200 A with supply via two supply terminals internally bridged Max 150 A per supply terminal at 50 mm cable cross section cable cross section max 50 mm per supply line cable cross section max...

Page 18: ...ce and ensure that the vent holes are not blocked Leave enough space between the devices Cable management Ensure installation at a site where the cables can be laid and connected properly Ensure ease...

Page 19: ...oduct connecting cables for power supply and ground not delivered with product connecting cables for load terminals not part of the delivery scope 4 mounting screws M6 x 16mm with plastic sleeve 2 x M...

Page 20: ...ignment Depending on the version tightening torque of supply terminals see table 2 Technical data supply Important Do not yet connect any load lines 9 Switch on the power supply Check correct polarity...

Page 21: ...erface RCI10 see chapter 6 allows failure indication as well as an automatic remote control of the ESX300 S via a controlling computer 4 2 Technical data of ESX300 S Electronic circuit protectors with...

Page 22: ...contact N C optional no error OFF locked flashing slowly OFF open normal operation connected ON OFF open error undervoltage with device in OFF condition 15 V U 37 V locked OFF ON closed error undervol...

Page 23: ...ing ESD protection means Failure to comply can cause damages on the ControlPlex Rack system or the corresponding components Warning Mounting position The ESX300 S sub assembly has to be pushed in vert...

Page 24: ...momentary switch once until it blinks Important The red status LED Fault must be off If this is not the case please go chapter 4 7 ESX300 S trouble shooting and remedy the failure Do not continue wit...

Page 25: ...efore being removed Push the momentary switch On Off until the green LED blinks slowly or disconnect the Power D Box dead voltage both LEDs off 2 When removing the electronic circuit protector the int...

Page 26: ...Directive 98 37 EG and EN 60204 1 Safety of Machinery Note ESX300 S time after short circuit or overcurrent trip After tripping due to a short circuit the circuit protector ESX300 S can only be reset...

Page 27: ...ta logging and extended alarm monitoring by means of replacing the RCI10 sub assembly by RSI10 without a failure of the connected loads 5 2 Technical data of RSI10 Interface card for group alarm signa...

Page 28: ...error overcurrent or short circuit discon nection locked green closed normal operation error undervoltage U 15 V 37 V connected green closed normal operation error overvoltage 72 V U 75 V connected gr...

Page 29: ...protectionTo protect electronic components against electrostatic voltage any work must only be carried out with corresponding ESD protection means Failure to comply can cause damages on the ControlPle...

Page 30: ...d remedy the failure Do not continue with step 6 before the green LED is lighted continuously 6 Connection of an external alarm indication Connect a prepared external alarm indication via the 3 pole a...

Page 31: ...r query can be forwarded to a connected control computer 6 2 Technical data of RCI10 Interface card for measuring data recording automation and remote control of all circuit protectors installed in th...

Page 32: ...ternal failure BUS EL BUS The red LED indicates an EL BUS failure The communication with the circuit protector ESX300 S and the RCI10 is disrupted This problem can be caused by a defective circuit pro...

Page 33: ...I10 IP Reset 6 3 Delivery scope RCI10 The following parts are part of the delivery scope of the RCI10 Remote control interface type RCI10 xxx A with front plate 6 4 Picture of RCI10 fig 21 RCI10 sub a...

Page 34: ...terminal length 2 Important Please ensure that all steps in chapter 3 for starting up the Power D Box and in chapter 4 Start up ESX300 S were carried out correctly 3 Important Please make sure that an...

Page 35: ...nagement system main computer intranet ControlPlex Rack RCI10 ESX300 S EAI300 Fig 23 connection example network 6 6 Configuration and start up RCI10 For configuring the RCI10 sub assembly you need the...

Page 36: ...utput can be used directly for reading the alarm contacts Equally there are two potential free outputs available for activating e g a door lock or for realising an additional group signalling of the E...

Page 37: ...e blinking EAI300 normal duty identified new circuit protector ESX300 relay output configured as group signal 5 seconds blue EAI300 fault condition no control interface RCI10 available red blinking EA...

Page 38: ...EAI300 should always be plugged into the highest slot of the Power D Box e g with Power D Box type PDB N CP19A into slot 19 the following EAI300 into slot 18 etc 4 Installation of the EAI300 sub assem...

Page 39: ...connection example connector X5 alarm output sensor 4 20 mA connector X6 Label LED retaining clip alternative supply external power supply for the inputs and outputs Extern DC 12 V DC 72 V max 100 mA...

Page 40: ...ktrotechnische Apparate GmbH Industriestra e 2 8 90518 ALTDORF GERMANY Tel 49 9187 10 0 Fax 49 9187 10 397 E Mail info e t a de www e t a de Installation manual I_19BGTCP_d_200617 Issue 03 All rights...

Reviews: