Concluding activities
19
7
Concluding activities
Check the drive connection data in the control
system
Check the connection data of the drive based on the
settings in the control system. The connection data is
listed on the name plate of the motor.
The parameters for the drive of the boiler are shown in
the text menu of the respective function block [Boiler]:
The parameters for all further drive components are
shown in the text menu of the respective function block
[SpConv]:
Checking the drive's direction of rotation
Mark the drive by drawing a line over the screw,
washer and drive.
Fig. 7-1: Marking
In the function block of the boiler, switch to the inputs
and outputs menu. Select the stoker unit [Stoker unit]
and press the
button for manual operation. Only
start the discharge drive with the [Fwd] button.
Fig. 7-2: Menu for manual operation
Check the direction of rotation of the drive with the aid
of the marking. The correct rotation direction is shown
in the following diagram.
If the rotation direction is not correct, check the drive's
electrical connection.
Fig. 7-3: Correct direction of rotation
Checking the direction of rotation of all other
drives
In the same way (as described before), check the
correct direction of rotation for all other drives.
Switch to the special conveyor function block and start
manual operation in the inputs and outputs menu.
Outputs
Stoker unit
Intermediate conveyor screw
Current
Max. current
NominCurr
Outputs
Motor rated output
Outputs
Conveying system
Current
Max. current
NominCurr