GB
OPERATING INSTRUCTIONS
PD 360/8 KNX BASIC
(EB10430442)
www.esylux.com
6 /6
DESCRIPTION OF APPLICATION
6.2 Switching
Threshold 0 = disabled, motion detection only
Direct entry 0 – 2000 lux
Default setting: 500 lux
6.3 • Switch-off delay time (light)
• Switch-off delay time (light)
Options: 0 seconds, 30 seconds – 12 hours
Default setting: 5 min
6.4 Processing actuator feedback
Object 3 can be used to evaluate the status object of an actuator. In the
event that the actuator is not only controlled by the detector, the light channel
switches to standby mode if the status of the channel differs from that of the
actuator.
6.5 Behaviour at switching lock ON or OFF
Options for each include: "No reaction", "Switch off" or "Switch on" the light
channel.
ESYLUX GmbH
An der Strusbek 40, 22926 Ahrensburg/Germany
Website: www.esylux.com
e-mail: [email protected]
MA00550400
7. LIGhT VALUE
The current light value can be transmitted either in cycles or from a specified
offset to the last actual value sent. This value is calculated as follows:
Value = [light value from sensor x modifier x multiplier] + offset