  D A T A   S H E E T

 85005-0131

 

Not to be used for installation purposes.

  Issue 7

SA-232 RS-232 interface

The SA-232 card provides an RS-232 
interface with iO-Series panels. It can be 
used for connecting a printer to the control 
panel to print system events. The card also 
can be used for connecting a computer to 
download a configuration program from 
the iO-CU to the control panel.

The RS-232 card is installed on the plastic assembly and con-
nects to the main circuit board via a ribbon cable.

SA-232 specifications

Operating voltage

Standard EIA-232

Terminal rating

12 to18 AWG (0.75 to 2.5 sq mm)

Operating environment

Temperature

Humidity

32 to 120°F (0 to 49°C)
0 to 93% RH, noncondensing at 90°F (32°C)

SA-ETH Ethernet Interface Card 

Network cable

Ethernet card

To network
connection

SA-ETH wiring

   The SA-ETH card provides a 

standard 10/100 Base T Ethernet 
network connection for connect-
ing to an intranet, a local net-
work, or the Internet. The card 
can be used to download 
configuration programming from 
the iO-CU to the panel over the 
network.

The Ethernet card is installed on 
the plastic assembly and con-
nects to the main circuit board 

via a ribbon cable.

SA-ETH specifications

Ethernet

10/100 Base T

Operating environment

Temperature

Humidity

32 to 120°F (0 to 49°C)
0 to 93% RH, noncondensing at 90°F 
(32°C)

Option Cards

iO-Series panels are supported by a complete line of modules and 
related equipment that enhance performance and extend system 
capabilities. Option cards are easy to install and set up. They 
simply plug directly into the control panel main circuit board or are 
connected to it with a ribbon cable. After installation, terminals 
remain easily accessible for quick connection of field wiring. The 
cabinet provides ample room for wire routing, keeping wiring neat 
and easy to service at all times.

GND (black wire)

TXD (white wire)

RXD (red wire)

SA-232 wiring

SA-CLA Class A Module

The SA-CLA card 
provides Class A 
capability for NAC, 
loop, and an-
nunciator wiring. 
Its terminal block 
provides the wiring 
connection for NAC 
return wiring. The 
card is required for 
loop and annuncia-
tor Class A wiring 
even though this wiring does not return to the SA-CLA card. The 
SA-CLA is compatible with iO64 control panels only. iO500 panels 
are Class A ready. The SA-CLA is installed directly to the control 
panel circuit board using its plastic standoffs and plug connection.

SA-CLA specifications

Operating voltage

24 VFWR

Operating current

2.5 A/circuit, 3.75A total (115/230 60hz)
3.0A total (230v 50hz)  

Circuit impedance

26 Ω, 0.35 µF, max

Terminal rating

12 to18 AWG (0.75 to 2.5 sq mm)

Operating environment

Temperature

Humidity

32 to 120°F (0 to 49°C)
0 to 93% RH, noncondensing at 90°F 
(32°C)

SA-CLA wiring

Class A card installed
on main circuit board

NAC1

NAC2+

NAC2

NAC1+

+

+

+

+

+

+

TB2 on main
circuit board

1

1

1

2

2

2

3

3

3

4

4

4

5

5

5

6

6

6

7

7

7

8

8

8

11

11

12

12

16

16

15

15

14

14 13

13

9

9

10

10

3 2 1

3 2 1

+

_

24 VDC 

auxilliary

 power 

(not resettable)

+

+

+

+

+

+

+

Power in

Power out

SMK

JP1

JP1

 Data in

Data out

Terminate

or to next

UM

T

wo

-wire smoke

detector

s

T

wo

-wire smoke

detector

s

SMK Smoke Power Converter

The SMK Smoke Power 
Converter Module provides a 
regulated power source for two-
wire smoke circuits connected 
to a Signature data circuit. The 
SMK monitors the operating 
power from the power supply. 
When power begins to degrade, 
the SMK provides the necessary 
operating voltage to the two-
wire smoke detection circuits.

SMK specifications

Input voltage 

21.9 to 28.3 VDC (not resettable)

Output voltage 

24 VDC nom. at 200 mA, max., special 
applications

Ground fault 
impedance 

10 k ohm

Operating environment 
Temperature 
Humidity 

 
32 to 120°F (0 to 49°C)  
0 to 93% RH, noncondensing at 90°F (32°C)

Storage temperature 

–4 to 140°F (–20 to 60°C) 

Compatible electrical 
boxes 

North American 4 inch square x 2-1/2 in. 
(64 mm) deep 2 gang box  or Standard 4 in. 
square box 1-1/2 in. (38 mm) deep

Wire size 

14, 16, or 18 AWG wire (1.5, 1.0, or 0.75 sq. 
mm) (Sizes 16 and 18 AWG are preferred) 

Summary of Contents for iO64

Page 1: ...nd related equip ment including Signature Series intelligent modules detectors and bases R Series remote annunciators option cards that expand system capacity and extend system capabilities fully integrated CO detection using Signature Series 2 detec tors with or w o audible signaling Features Comes standard with one loop that supports up to 64 intelligent devices of any type and two Class B NACs ...

Page 2: ...plication The iO64 life safety system is a powerful intelligent solution for small to mid sized buildings Advanced analog technology delivers the benefits of flexible system installation while a clean and easy to operatate user interface makes panel operation and system mainte nance quick and intuitive The smart choice Signature Series electronic addressing eliminates the tedium of setting dipswit...

Page 3: ... walk test Steady indicates a silent test Monitor Yellow LED Flashes when there is an active monitor event on any loop On steady once acknowledged Service Detector Yellow LED Indicates that detector needs servicing Signal Silence Yellow LED On steady indicates that NAC circuits are turned off but the panel is still in alarm Remote Discon nect Yellow LED On steady indicates that the dialer is disab...

Page 4: ...1 SEC Loop 1 PRI Loop device Loop device Loop card Data Line Class B Wiring Class A Wiring Marking indicates output signal polarity when the circuit is active Polarity reverses when the circuit is not active Wire notification appliances accordingly Notification appliance polarity shown in active state Annunciator loop TB4 The control panel provides a connection for up to eight serially driven and ...

Page 5: ...32 wiring SA CLA Class A Module The SA CLA card provides Class A capability for NAC loop and an nunciator wiring Its terminal block provides the wiring connection for NAC return wiring The card is required for loop and annuncia tor Class A wiring even though this wiring does not return to the SA CLA card The SA CLA is compatible with iO64 control panels only iO500 panels are Class A ready The SA C...

Page 6: ...g agents such as CO2 Halon or foam The module is easily configured in the field and of fers a wide range of options that ensure dependable service while preventing the unnecessary release of extinguishing agent SIGA REL specifications Power riser Input voltage Supervisory current Riser input current Alarm 24 Vdc power limited 25 mA max 4 amps maximum 170 mA min 4 A max Release circuits Output rati...

Page 7: ...e mount enclosure 230 Vac Spanish iO64G PG Note 2 1 Loop System 64 point capacity 2 NACs gray door surface mount enclosure 115 Vac Portuguese iO64G 2 PG Note 2 1 Loop System 64 point capacity 2 NACs gray door surface mount enclosure 230 Vac Portuguese iO64GL Note 1 1 Loop System 64 point capacity 2 Class B NACs 16 zone LED display gray door surface mount enclosure 115 Vac English iO64GL F Note 1 1...

Page 8: ...4 0 15 SIGA MCRR Polarity Reversal Relay Module UIO Mount 0 18 0 08 SIGA RM1 Riser Monitor Module Standard Mount 0 5 0 23 SIGA MRM1 Riser Monitor Module Plug in 0 18 0 08 SIGA IO Input Output Module Standard Mount 0 34 0 15 SIGA MIO Input Output Module Plug in 0 22 0 10 SIGA MAB Universal Class A B Module Plug in 0 18 0 08 SIGA CT1 Single Input Module 0 4 0 15 SIGA CT2 Dual Input Module 0 4 0 15 S...

Page 9: ... EOL Polarized end of line relay English markings on stainless steel cover 0 2 0 1 SIGA UIO2R Universal Module Board w Riser Inputs Two Module Positions 0 32 0 15 SIGA UIO6R Universal Module Board w Riser Inputs Six Module Positions 0 62 0 28 SIGA UIO6 Universal Module Board Six Module Positions 0 56 0 25 Accessories GCI Graphic Annunciator Driver provides outputs for common indicators and 32 alar...

Page 10: ... EST is an EDWARDS brand 1016 Corporate Park Drive Mebane NC 27302 In Canada contact Chubb Edwards Email inquiries chubbedwards com Web www chubbedwards com 2013 UTC Fire Security Americas Corporation Inc All rights reserved Specifications subject to change without notice Edwards is part of UTC Climate Controls Security a unit of United Technologies Corporation ...

Reviews: