  D A T A   S H E E T

 85005-0131

 

Not to be used for installation purposes.

  Issue 7

Panel Operation Options

Language

English or French

Marketplace

U.S. or Canada

AC fail delay

Off: 

Off-premise notification of an AC power failure 

is immediate.

1 to 15 hours: 

Delays the off-premise notification of 

an AC power failure by the time period selected.

Zone resound

On: 

NACs resound each time a device in the zone 

goes into alarm even if they were silenced
Off: Inhibits the NACs from turning on again (after 
they were silenced) when a second device in the 
zone goes into alarm.

Reset inhibit after 
NACs turn on

Off: 

Panel reset is operational immediately.

1 minute: 

Panel reset is inhibited for one minute.

Auto signal 
silence

Off: 

Allows immediate silencing of signals from an 

off-normal condition using the Signal Silence button

5 to 30 minutes:

 Delays the silencing of signals 

from an off-normal condition by disabling the Signal 
Silence button for the time period selected.

Day start

Start time for daytime sensitivity

Night start

Start time for nighttime sensitivity

Date

U.S.: 

MM/DD/YYYY, 

Canada: 

DD/MM/YYYY

Sounder Base

Six configuration settings

Mapping

Disabled: 

Device mapping is not available

Enabled: 

Device mapping is available

LCD banner

Banner text for line one and line two. Each line is 
capable of up to 20 characters.

Event notification

Zone: 

When a device is a member of a zone, only 

the zone information is sent to the LCD display, 
LEDs, printer, and dialer. 

Zone/device: 

Zone information is sent to the LCD 

display and LEDs. Device information is sent to the 
printer and dialer. 

Device: 

Only device information is reported.

System LEDs

LED

Description

Alarm

Red LED. Flashes when there is an active alarm 
event on any loop. On steady once acknowledged.

Trouble

Yellow LED. Flashes when there’s a fault with a 
monitored circuit or system component or when a 
circuit is disabled. On steady once acknowledged.

Sup

Yellow LED. Flashes when there is an active super-
visory event on any loop. On steady once acknowl-
edged.

Ac Power

Green LED. On when the panel has AC power.

Disable

Yellow LED. Double-flashes when there is a dis-
abled circuit, alarm relay, or remote annunciator.

Ground 
Fault

Yellow LED. On steady during an active ground 
fault.

Test

Yellow LED. Flashes when performing an audible 
walk test. Steady indicates a silent test.

Monitor

Yellow LED. Flashes when there is an active monitor 
event on any loop. On steady once acknowledged.

Service 
Detector

Yellow LED. Indicates that detector needs servicing.

Signal 
Silence

Yellow LED. On steady indicates that NAC circuits 
are turned off but the panel is still in alarm.

Remote 
Discon-
nect

Yellow LED. On steady indicates that the dialer is 
disabled or that the alarm relay is enabled or dis-
abled when the dialer is set to modem only.

Drill

Yellow LED. Indicates that the panel is in drill.

Reset

Yellow LED. Indicates that the panel is resetting.

Panel  
Silence

Yellow LED. Indicates that the panel has been 
silenced during an active trouble, supervisory, or 
alarm event and indicates that new event activa-
tions have been acknowledged.

User Keys Yellow LED. Indicates the programmed key function is active.

Dimensions

D1

D2

D3

D4

D5

D6

Surface mounting holes

Semi-flush

mounting

h

o

le

s

Surface mounting holes

Panel dimensions, in (cm)

Model

D1*

D2

D3

D4

D5*

D6

iO64

21.50

(54.6)

3.85

(9.8)

7.5

(19.0)

15.5

(39.4)

14.25

(36.2)

10.25

(26.0)

* Add 1-1/2 in. (3.81 cm) to D1 and D5 dimensions for trim kit.

Programming

iO-Series life safety systems are simple to set up, yet also offer ad-
vanced programming features that put these small building panels 
into a class of their own. The auto programming feature quickly 
gets the panel operational using factory default settings. Basic 
zone and point settings can be programmed easily through the 
front panel interface, so the system is up and running in no time.

For more advanced system configuration and correlation groups 
programming, iO-Series systems interface to a PC running com-
patible iO-CU software. This option offers full system configuration 
in the familiar Windows

®

 operating environment. Connection is 

typically made to a laptop through the panel’s optional RS-232 
communications port, which can also be used to connect a sys-
tem printer.

Among the many advanced features of iO-Series control panels 
is the optional network card. This module provides a standard 
10/100 Base T Ethernet

®

 network connection that permits access 

to the control panel from any remote location with the correct 
communications protocols. The connection can be used to 
download to the panel from the iO-CU, or upload and view system 
reports using the iO-CU.
Available system reports include:

•  Correlation groups 

•  Device details

•  Device maintenance 

•  History

•  Internal status 

•  System configuration

•  System status 

•  Walk test

•  Dialer 

•  CO runtime

Summary of Contents for iO64

Page 1: ...nd related equip ment including Signature Series intelligent modules detectors and bases R Series remote annunciators option cards that expand system capacity and extend system capabilities fully integrated CO detection using Signature Series 2 detec tors with or w o audible signaling Features Comes standard with one loop that supports up to 64 intelligent devices of any type and two Class B NACs ...

Page 2: ...plication The iO64 life safety system is a powerful intelligent solution for small to mid sized buildings Advanced analog technology delivers the benefits of flexible system installation while a clean and easy to operatate user interface makes panel operation and system mainte nance quick and intuitive The smart choice Signature Series electronic addressing eliminates the tedium of setting dipswit...

Page 3: ... walk test Steady indicates a silent test Monitor Yellow LED Flashes when there is an active monitor event on any loop On steady once acknowledged Service Detector Yellow LED Indicates that detector needs servicing Signal Silence Yellow LED On steady indicates that NAC circuits are turned off but the panel is still in alarm Remote Discon nect Yellow LED On steady indicates that the dialer is disab...

Page 4: ...1 SEC Loop 1 PRI Loop device Loop device Loop card Data Line Class B Wiring Class A Wiring Marking indicates output signal polarity when the circuit is active Polarity reverses when the circuit is not active Wire notification appliances accordingly Notification appliance polarity shown in active state Annunciator loop TB4 The control panel provides a connection for up to eight serially driven and ...

Page 5: ...32 wiring SA CLA Class A Module The SA CLA card provides Class A capability for NAC loop and an nunciator wiring Its terminal block provides the wiring connection for NAC return wiring The card is required for loop and annuncia tor Class A wiring even though this wiring does not return to the SA CLA card The SA CLA is compatible with iO64 control panels only iO500 panels are Class A ready The SA C...

Page 6: ...g agents such as CO2 Halon or foam The module is easily configured in the field and of fers a wide range of options that ensure dependable service while preventing the unnecessary release of extinguishing agent SIGA REL specifications Power riser Input voltage Supervisory current Riser input current Alarm 24 Vdc power limited 25 mA max 4 amps maximum 170 mA min 4 A max Release circuits Output rati...

Page 7: ...e mount enclosure 230 Vac Spanish iO64G PG Note 2 1 Loop System 64 point capacity 2 NACs gray door surface mount enclosure 115 Vac Portuguese iO64G 2 PG Note 2 1 Loop System 64 point capacity 2 NACs gray door surface mount enclosure 230 Vac Portuguese iO64GL Note 1 1 Loop System 64 point capacity 2 Class B NACs 16 zone LED display gray door surface mount enclosure 115 Vac English iO64GL F Note 1 1...

Page 8: ...4 0 15 SIGA MCRR Polarity Reversal Relay Module UIO Mount 0 18 0 08 SIGA RM1 Riser Monitor Module Standard Mount 0 5 0 23 SIGA MRM1 Riser Monitor Module Plug in 0 18 0 08 SIGA IO Input Output Module Standard Mount 0 34 0 15 SIGA MIO Input Output Module Plug in 0 22 0 10 SIGA MAB Universal Class A B Module Plug in 0 18 0 08 SIGA CT1 Single Input Module 0 4 0 15 SIGA CT2 Dual Input Module 0 4 0 15 S...

Page 9: ... EOL Polarized end of line relay English markings on stainless steel cover 0 2 0 1 SIGA UIO2R Universal Module Board w Riser Inputs Two Module Positions 0 32 0 15 SIGA UIO6R Universal Module Board w Riser Inputs Six Module Positions 0 62 0 28 SIGA UIO6 Universal Module Board Six Module Positions 0 56 0 25 Accessories GCI Graphic Annunciator Driver provides outputs for common indicators and 32 alar...

Page 10: ... EST is an EDWARDS brand 1016 Corporate Park Drive Mebane NC 27302 In Canada contact Chubb Edwards Email inquiries chubbedwards com Web www chubbedwards com 2013 UTC Fire Security Americas Corporation Inc All rights reserved Specifications subject to change without notice Edwards is part of UTC Climate Controls Security a unit of United Technologies Corporation ...