Automatic fire detectors series IQ8Quad Ex (i) 

 

30 

TI 798920 / 01.13

 

Ex barriers for fire detectors series IQ8Quad Ex (i) 

Purpose 

The Ex barrier (Part No. 764744-Zener barriers, not dry contact) and (Part No. 804744 dry 
contact) is used for installation of Ex (i) zones in combination with fire detectors series 
IQ8Quad Ex (i). The barrier separates inherently safe from non inherently safe circuits outside 
the explosive hazard area (Ex zone).  
 
 

Part No. 

Accessories

 

764752 

Housing (IP 66) for max. 10 barriers (Part No. 764744) or 8 barriers  
(Part No. 804744) incl. equipotential bonding system connection clips 

764754 

Cable gland (blue) for housing (Part No. 764752) 

764745 

Isolation- and mounting terminal, 
required, if the potential equalisation must not be done via the C-profile rack 

 

 

 

Depending on the used cables and the conditions in the Ex area of 
zone 1, zones with fire detectors series IQ8Quad Ex (i) may be connected to 
this barrier. 

 

Max. number of detectors on the FACP IQ8Control / FlexES control 

Î

 max. 8 

fire detectors per zone with barrier (Part No. 764744). 

 

Max. number of detectors on the FACP IQ8Control / FlexES control 

Î

 max. 10 

fire detectors per spur with barrier (Part No. 804744). 

 

9.1 Mounting 

information 

 

Observe category, area and temperature classifications. 

 

Observe the system limits for the maximum permitted number of detectors and the cable 
specifications. 

 

Study and follow the installation and operating instructions for the automatic fire detector 
and the fire detector base. 

 

Observe ambient temperature or temperature range of used detector types. 

 

Use cable I-Y (St) Y n x 2 x 0,8 mm with special designation or fire detection cable!  
The shielding must be connected for EMI protection of the communication cable! 

 

The automatic fire detectors and fire detector bases may not be installed in areas with 
atmospheres containing benzene, acetic acid or esters as the ABS plastic of the housing is 
not resistant to these chemicals. 

 

Secure and intrinsically safe areas are electrically isolated from each other by the  
Ex barrier (Part No. 804744); Therefore a connection to the equipotential bonding is not 
required. 

 

The cable shieldings of the intrinsically safe areas must be connected to the equipotential 
bonding of the corresponding Ex area. 

 

Summary of Contents for IQ8Quad Ex (i)

Page 1: ...Technische nderungen vorbehalten Technical changes reserved 2013 Honeywell International Inc Technische Information Automatische Brandmelder Serie IQ8Quad Ex i und Ex Barrieren Technical Information A...

Page 2: ...n der Brandmelde und L schanlagen bef higende Ausbildung besitzen bzw die Berechtigung haben Stromkreise und Ger te Systeme gem den Standards der Sicherheitstechnik in Betrieb zu nehmen zu erden und z...

Page 3: ...Serie IQ8Quad Ex i EC Type Examination Certificate T V Fire detector series IQ8Quad Ex i EC Type Examination Certificate Baseefa Ex barrier Part No 764744 EC Type Examination Certificate EECS Baseefa...

Page 4: ...000 Volt DIN VDE 100 718 Errichten von Niederspannungsanlagen Anforderung f r Betriebsst tten R ume und Anlagen besonderer Art Bauliche Anlagen f r Menschenansammlungen und DIN VDE 0105 100 Betrieb vo...

Page 5: ...hrdeten Bereichen DIN EN 1127 1 Explosionsf hige Atmosph ren Explosionsschutz DIN EN 60079 0 VDE 0170 1 Elektrische Betriebsmittel f r gasexplosionsgef hrdete Bereiche Allgemeine Anforderungen DIN EN...

Page 6: ...Installation ist sicherheitsrelevant Daher ist unbedingt darauf zu achten dass eine auf den Einsatzort Umgebungsbedingungen abgestimmte IP Schutzart realisiert wird 2 Die in den technischen Daten aufg...

Page 7: ...eigensichere Leitung anschalten Zus tzlich Systemgrenzen in Kapitel 5 beachten Elektrische Kennwerte von Kabeln und Leitungen Die elektrischen Kennwerte CC und LC oder CC und LC RC m ssen f r alle ve...

Page 8: ...r t Art Nr 060429 805550 805551 testen Zur Verwendung der Testger te unbedingt eine Erlaubnisbescheinigung Feuererlaubnisschein des Betreibers einholen F r den Zeitraum der Wartung sicherstellen dass...

Page 9: ...744 und 804744 Ex Schutz Ex ib IIC T4 Gb Melderkennzeichnung gem ATEX Abb 1 Kennzeichnungsbeispiel IQ8Quad Ex i 803371 EX Allgemeine Melderdaten Betriebsspannung 8 V DC bis 42 V DC Sensortyp Thermo 1...

Page 10: ...06 VdS Anerkennung G 209224 CE Zertifikat 0786 CPD 20914 O 2 T Multisensormelder 803374 EX 2 803374 EX F0 2 803374 EX NU 2 Ruhestrom 19 V DC 60 A Ruhestrom BMZAkku 0 23 mA 27 5 V 0 33 mA 42 V Anwendun...

Page 11: ...uP Geh use f r IQ8Quad Meldersockel 805572 IP 43 Feuchtraum Sockeladapter aP f r IQ8Quad Meldersockel inkl drei einsetzbaren Kabelverschraubungen 805573 IP 43 Schutz f r IQ8Quad Meldersockel tiefe Bau...

Page 12: ...trol FlexES control max 8 Brand melder pro Gruppe an einer Ex Barriere Art Nr 764744 Max Melderanzahl an der BMZ IQ8Control FlexES control max 10 Brand melder pro Ex Stichleitung an einer Ex Barriere...

Page 13: ...ssigkeit so angeschlossen werden dass die Impedanz vom Anschlusspunkt bis zum Erdpunkt des Starkstromsystems weniger als 1 betr gt Das kann durch Anschluss an eine Schaltraum Erdungsschiene oder durch...

Page 14: ...uktivit t im Ex i Stromkreis II C L0 650 H IIC L0 560 H Max Kapazit t im Ex i Stromkreis IIB C0 1 264 F Max Induktivit t im Ex i Stromkreis IIB L0 2 24 mH Max Kapazit t im Ex i Stromkreis IIA C0 4 774...

Page 15: ...werden Systemgrenzen Leitungsl nge einer Gruppe max 300 m Gesamtleitungsl nge ab den Anschlussklemmen der Meldergruppe M glichst nah vor dem zu berwachenden Ex Bereich Zone 1 die Barriere Art Nr 76474...

Page 16: ...lussleitung Potentialalausgleichsschiene PAS min 2 x 1 5 mm Cu oder 1 x 4 mm Cu 1 4 2 8 5 7 Ex Barriere Art Nr 764744 Geh use Art Nr 764752 Abb 3 Anschaltung der Ex Barriere Art Nr 764744 Zubeh r Je n...

Page 17: ...Geh use Art Nr 764752 montieren Melderanzahl max 10 Brandmelder pro Ex Barriere Max 4 Ex Barrieren pro Ringleitung Zwischen zwei Ex Barrieren mindestens einen esserbus Teilnehmer mit Trenner installi...

Page 18: ...Automatische Brandmelder Serie IQ8Quad Ex i 18 TI 798920 01 13 Abb 5 System bersicht mit Ex Barriere Art Nr 804744 Beispiel Abb 6 Anschaltung der Ex Barriere Art Nr 804744...

Page 19: ...798920 01 2013 AA G 209223 G 209224 G 209225 G 210047 GB Technical changes reserved 2013 Honeywell International Inc Technical Information Automatic fire detectors series IQ8Quad Ex i and Ex barriers...

Page 20: ...l trained installation or service personnel with the necessary qualification for carrying out repairs on fire alarm and extinguishing systems or who are authorised to operate ground and label electric...

Page 21: ...nigung T V Brandmelder Serie IQ8Quad Ex i EC Type Examination Certificate T V Fire detector series IQ8Quad Ex i EC Type Examination Certificate Baseefa Ex barrier Part No 764744 EC Type Examination Ce...

Page 22: ...ytems with rated voltage up to 1000 V DIN VDE 100 718 Install low voltage systems Requirements for sites rooms and special systems and DIN VDE 0105 100 Operation of electrical system General commitmen...

Page 23: ...EN 1127 1 Explosive atmospheres Explosion prevention and protection DIN EN 60079 0 VDE 0170 1 Electrical apparatus for explosive gas atmospheres General requirements DIN EN 60079 10 VDE 0165 101 Elect...

Page 24: ...ion is relevant to safety It is thus very important to ensure that the IP rating necessary for the installation location environmental conditions is achieved 2 The information on IP ratings in the spe...

Page 25: ...nnection cables between barrier and the specified detectors Pay attention to the detailed information for system limits in chapter 10 Electrical specifications of cables and conductors The electrical...

Page 26: ...test head for heat detector Part No 060429 805550 805551 to test heat detector operation To use the test equipment the a permit fire permission certificate must be signed by the operator of the fire a...

Page 27: ...ion Ex ib IIC T4 Gb Detector identification according to ATEX Fig 1 Identification example IQ8Quad Ex i 803371 EX General Specifications Operating voltage 8 V DC to 42 V DC Type of sensor Heat 1 Smoke...

Page 28: ...proval G 209224 CE certificate 0786 CPD 20914 O2T multisensor detector 803374 EX 2 803374 EX F0 2 803374 EX NU 2 Quiescent current 19 V DC 60 A Ambient temperature 20 C to 65 C 4 Specification EN 54 7...

Page 29: ...detector base IQ8Quad 805572 IP 43 Damp location surface mounting base adapter for IQ8Quad detector base incl three attachable cable fittings 805573 IP 43 protection for IQ8Quad detector base deep bo...

Page 30: ...h barrier Part No 764744 Max number of detectors on the FACP IQ8Control FlexES control max 10 fire detectors per spur with barrier Part No 804744 9 1 Mounting information Observe category area and tem...

Page 31: ...d with a high reliability that the electric impedance from the connector to the grounding point of the high power current system must not exceed 1 This could be realised by using a grounding rail or s...

Page 32: ...IC C0 182 nF Max inductivity Ex i circuit II C L0 650 H IIC L0 560 H Max capacity Ex i circuit IIB C0 1 264 F Max inductivity Ex i circuit IIB L0 2 24 mH Max capacity Ex i circuit IIA C0 4 774 F Max i...

Page 33: ...System requirements Loop length per zone max 300 m Total length measured from the terminals of the detector zone The barrier must be installed as close as possible to the Ex zone to be monitored Zone...

Page 34: ...le equipotential bounding bar EBB min 2 x 1 5 mm Cu or 1 x 4 mm Cu Ex barrier Part No 764744 1 4 2 8 5 7 Housing Part No 764752 Fig 3 Principal wiring with Ex barrier Part No 764744 Accessories Depend...

Page 35: ...be monitored Zone 1 for example in a housing Part No 764752 or in another suitable location Number of detectors max 10 fire detectors per Ex barrier Max 4 Ex barriers per loop At least one esserbus de...

Page 36: ...tic fire detectors series IQ8Quad Ex i 36 TI 798920 01 13 Fig 5 System overview with Ex barrier Part No 804744 Example Fig 6 Connection of the Ex barrier Part No 804744 incl fire detector as spur conn...

Page 37: ...798920 D 01 2013 AA G 209223 G 209224 G 209225 G 210047 GB Technische nderungen vorbehalten Technical changes reserved 2013 Honeywell International Inc Anhang Appendix...

Page 38: ...Anhang Appendix 38 TI 798920 01 13 EG Konformit tserkl rungen EC Declarations of Conformity Brandmelder Serie IQ8Quad Ex i Fire detector series IQ8Quad Ex i...

Page 39: ...Anhang Appendix TI 798920 01 13 39...

Page 40: ...Anhang Appendix 40 TI 798920 01 13 Ex Barrieren Ex barriers Art Nr Part No 764744 und 804744...

Page 41: ...Anhang Appendix TI 798920 01 13 41...

Page 42: ...Anhang Appendix 42 TI 798920 01 13 EG Baumusterpr fbescheinigung T V Brandmelder Serie IQ8Quad Ex i...

Page 43: ...Anhang Appendix TI 798920 01 13 43...

Page 44: ...Anhang Appendix 44 TI 798920 01 13 EC Type Examination Certificate T V Fire detector series IQ8Quad Ex i...

Page 45: ...Anhang Appendix TI 798920 01 13 45...

Page 46: ...Anhang Appendix 46 TI 798920 01 13 EC Type Examination Certificate Baseefa Ex barrier Part No 764744...

Page 47: ...Anhang Appendix TI 798920 01 13 47...

Page 48: ...Anhang Appendix 48 TI 798920 01 13...

Page 49: ...Anhang Appendix TI 798920 01 13 49...

Page 50: ...Anhang Appendix 50 TI 798920 01 13...

Page 51: ...Anhang Appendix TI 798920 01 13 51...

Page 52: ...Anhang Appendix 52 TI 798920 01 13...

Page 53: ...Anhang Appendix TI 798920 01 13 53 EC Type Examination Certificate EECS Baseefa Ex barrier Part No 804744...

Page 54: ...Anhang Appendix 54 TI 798920 01 13...

Page 55: ...Anhang Appendix TI 798920 01 13 55...

Page 56: ...Anhang Appendix 56 TI 798920 01 13...

Page 57: ...Anhang Appendix TI 798920 01 13 57...

Page 58: ...Anhang Appendix 58 TI 798920 01 13 Notizen Notes...

Page 59: ...Anhang Appendix TI 798920 01 13 59 Notizen Notes...

Page 60: ...ovar GmbH a Honeywell Company Dieselstra e 2 D 41469 Neuss Telefon 49 0 21 37 17 0 Verwaltung Internet www esser systems de 49 0 21 37 17 600 KBC E Mail info esser systems de Telefax 49 0 21 37 17 286...

Reviews: