MAGPRO-DBS is
а
n addressable Fire Base with built-in Sounder in its body. The fire base is designed for installing in
addressable fire alarm systems which support operation via MAGPRO communication protocol. The device is powered on from
the panel and can be controlled via the communication protocol.
The addressable MAGPRO-DBS fire base supports 32 different tone types at two sound levels. The tone type and sound level are
programmed from the control panel.
The MAGPRO-DBS is compatible for operation with MAGPRO addressable detectors series: HD1, SD1 and HSD1. The device is
designed for easy installation and consists from two parts: mounting plane basis and sounder is a body with factory mounted fire base.
Installation Instructions
Attention
:
Power off the loop circuit
before installing the MAGPRO-DBS addressable fire base
!
1.
Choose the proper place for installation of the device
.
2. Set the device address
using
MAGPRO-PROG or directly from addressable fire panel
.
The address must be in the range from
1
to
250.
3. Fix the mounting plane basis
on the ceiling of the protected premises using fixings
according the mounting surface.
4. Run the loop wires and fix the sounder
body to the mounting basis using the supplied screws in the spare parts kit.
5. Connect the fire base
to the fire panel using the wiring diagram.
6. Insert a detector - MAGPRO HD1/ SD1/ HSD1 - into the fire base
and rotate clockwise until it drops into place - the short mark on
the base fits with that on the sounder body. Continue to rotate the detector until its mark coincides with the long mark on the base - a
click is heard.
Note:
The mounted detector on the MAGPRO-DBS base is assigned at different address to the control panel
!
7. Program the sounder parameters.
Refer to the Programming manual of the control panels MAGPRO16 and MAGPRO96 for
more details.
8. Test the sounder for proper operation.
I
P21C
-10°C
÷
+
60
°C
Installation
~127
g
Indoor use
Outdoor use
!
Operating Voltage Range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
-
32
VDC
Maximal consumption at communication . . . . . . . . . . . . . . . . .
470
μ
А
@
27
VDC
Maximal consumption
:
-
main tone type 27, low volume level . . . . . . . . . . . . . . . . .
2,8
m
А
@
27
VDC
- main tone type 27, high volume level . . . . . . . . . . . . . . . . .
9,8
m
А
@
27
VDC
Power volume (main tone type 27)
:
-
low volume (up to 100 pcs MAGPRO DBS to the loop) . . . ~ 92dB (A)
±
3dB @ 1m
- high volume
(up to
30
pcs MAGPRO DBS to the loop) . . . ~ 99dB (A)
±
4dB @ 1m
Power volume (other tone types)
: . . . . . . . . . . . . . . . . . . . . . . .
-
low volume (up to 100 pcs MAGPRO DBS to the loop) . . .
8
2
-92
dB
±
3dB @ 1m
- high volume
(up to
30
pcs MAGPRO DBS to the loop) . . .
90-
100dB
±
3dB @ 1m
Number of tone types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
32
Supported communication protocol . . . . . . . . . . . . . . . . . . . . . . MAGPRO
2
Wire Gauge for terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0,4 - 2.0mm
Relative humidity resistance
. . . . . . . . . . . . . . . . . . . . . . . . . . .
(93
± 3)%
@
+
40°
C
Color . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . White
Material . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ABS
Dimensions with mounted detector MAGPRO HD1/ SD1 . . . . .
102
x 63mm
Dimensions with mounted detector MAGPRO HSD1 . . . . . . . . 102 x 70mm
TECHNICAL SPECIFICATIONS
18020177; RevB; 04/2015
!
A-weighted sound
level diagram
96
dB
102
dB
10
3
dB
95
dB
98
dB
1m
97
dB
15°
45°
75°
105°
135°
165°