![ESP Safety SGOES Operating Manual Download Page 9](http://html1.mh-extra.com/html/esp-safety/sgoes/sgoes_operating-manual_2427703009.webp)
SGOES Infrared Combustible Gas Detector
820-0006
Operating Manual
Page 8
Ordering Guide
For simplicity of ordering, the SGOES is factory configured for detection specific gases. For gases not included in the
table below, please contact ESP Safety.
Scale Range
SGOES Model to
Order
Detected
Hydrocarbon
%LEL
%vol IEC6007920-
2000/BSEN617791:200
0
%vol ISO 10156
100-0001-M11-C1
Methane
0 to 100
0 to 4.4
0 to 5.0
100-0001-M11-C2
Propane
0 to 100
0 to 1.7
0 to 2.1
100-0001-05
Butane
0 to 50
0 to 0.7
0 to 0.9
100-0001-07
Isobutane
0 to 50
0 to 0.65
0 to 0.9
100-0001-09
Pentane
0 to 50
0 to 0.7
0 to 0.75
100-0001-11
Cyclopentane
0 to 50
0 to 0.7
0 to 0.75
100-0001-13
Hexane
0 to 50
0 to 0.5
0 to 0.55
100-0001-15
Propylene/Propene
0 to 50
0 to 0.1
0 to 1.5
100-0001-17
Methanol Vapor
0 to 50
0 to 2.75
0 to 3.65
100-0001-19
Ethanol Vapor
0 to 25
0 to 50
0 to 0.78
0 to 1.55
0 to 1.08
0 to 2.15